6-2 Generator
(1) Exciting Amperage
Amperage fluctuates based upon the winding temperature. Following is for reference only.
Frequency/Rated Output
Load
Exciting Amperage (Measured)
3-Phase
60Hz: 120 kW
No load
0.57A
Full load( power factor=1.0)
1.04A
(2) Resistance Value
Nominal resistance of the winding is tolerated
within
± 10% at 32
°
F(
220
℃
) of the ambient temperature.
The resistance must be measured by low resistance tester. It can not be measured by multi-purpose
tester cause of index error.
Generator
Exciter (Measured)
Stator
Rotor
Stator
Rotor
Armature
Exciter Winding
J
-
K
Armature
Between
T1-T4, T7-T10
T2-T5, T8-T11
T3-T6, T9-T12
-
-
0.048
Ω
1.574
Ω
14.96
Ω
0.185
Ω
[Color Code]
(B)
(W)
(R)
(G)
(Y)
(Br)
(L)
(Or)
(Gr)
Black
White
Red
Green Yellow Brown Blue Orange
Gray
(3) Technical Specifications
It
e
ms
Article
Method
Condition to verify
Criterion
C
h
e
c
k
b
e
fo
re
o
p
e
ra
ti
o
n
Shape, Dent, Blot
Visual
Inspection
No dent, blot and deformation
Coating
No looseness
Joint
Meet the criteria
Oil, Coolant
Meet the required level
Wiring
Lead wires to be securely fastened
against
abrasion and damage to bring by
vibration
G
ro
u
n
d
in
g
Continuity
Tester
“GROUNDING” is connected;
-with Engine (bolt for grounding)
-with Bed (bolt for grounding)
-with grounding for Receptacle
Continuity is to be confirmed
I
n
s
u
la
ti
o
n
C
h
e
c
k
Insulation Resistance
DC500V
Mega
Tester
Main Breaker ON.
1-phase breaker (50A) ON
1-phase breaker (20A) OFF
Disconnect one coupler from the
stator.
Voltage Selector: 480V (3-phase)
- Remove all output lines connecting
to “T10 & T11” in terminal rest.
- Remove the output line “T12” from
the terminal rest.
-Open a pc terminal in the output line
“U2” from the stator.
*Insulate all terminals after removal
Over 3MΩ
Dielectric Voltage
Tester
AC2400V (1 sec)
Electric Current: 10mA
14
Summary of Contents for RDA150T3
Page 8: ...4 General 4 1 Appearance 4 2 Dimension Unit in the drawings below is shows by mm 5...
Page 9: ...6...
Page 10: ...5 General Parts Description 5 1 Equipment 7...
Page 11: ...8...
Page 12: ...9...
Page 25: ...10 Wiring Diagram 22...
Page 26: ...23...
Page 27: ...Call us toll free at 1 866 733 3272 US and Canada reddarc com...