4.1.1.Installation Environment Requirements
The required environmental conditions are shown in Table 8 below.
Table 8 Use Environment Requirements
Items
Description
Operating
Temperature
Operating temperature range: -20℃~+60℃, recommended operating temperature:
-15℃~+55℃
Storage
Temperature
-40℃ ~+50℃, the recommended storage temperature is 25℃
Relative Humidity
45%~85%, recommended: 45%~60%
Atmospheric
Pressure
86kPa~106kPa
Site Requirements
There is no conductive dust and corrosive gas, no explosion hazard, no vibration and
bumps. Keep away from heat and open flames
4.1.2.Tools and Materials
The tools and materials that may be used are shown in Table 9 below.
Table 9 Toolkit
No.
Items
No.
Items
1
Installation and Instruction Manual (User Manual)
7
Diagonal cutting pliers
2
Screwdriver (slotted, cross)
8
Multi-meter
3
Wrench
9
Clamp meter
4
Needle nose pliers
10
Insulation tape
5
Wire stripper
11
Anti-static bracelet
6
Wire pliers
12
Cable ties
4.1.3.Site Survey
Equipment Inspection
Check the properties of the device directly connected to the battery, which can be user equipment,
switching power supply or other power supply devices.
Check the position and output voltage of the DC interface in the device to confirm whether it meets the
voltage requirements in Table 6.
Check whether the maximum output current of the DC device interface matches the selected battery.
Check the maximum operating current of the equipment powered by the battery, it should be ensured