User Manual
18
CAUTIONS
:
If there is any problem during installation, please contact Ruineng in time to avoid
damage to the equipment or cause safety accidents.
4.Communication cable installation. When using the battery alone, skip this step. When multiple batteries
are used in parallel, please set the address code of each battery according to Table 3.4 (make sure there is
no duplicate address code), and then cascade the RS485 communication interfaces. The cascade sequence is
the left side of the battery pack with the lower address bit The RS485 interface is connected to the interface
on the right side of the high address bit, and the RS485 interface on the left side of the highest-order Master
battery is connected to the serial port of the computer through a communication adapter cable (RS485 to
RS232).
Step 4. Electrical Commissioning
When these steps are completed, turn on air switch to start the battery one bye one, then boot on the whole
power system, complete the installation.
CAUTIONS
:
If
you
have
any
question
about
the
installation,
please
stop
and
contact
Realpower
technical
support
immediately.
If
the
battery
does
not
start
or
control
panel
ALM
lights,
please
disconnect
the
power
line
inspection
and
reinstall
the
start,
if
still
cannot
solve
please
contact
Realpower
avoid
damage
to
equipment
or
cause
accidents.
5. Transportation & Storage& Maintenance
5.1. Transportation and Storage
Transportation
According to the provisions of the product can be used in general means of conveyance, but should avoid
throwing, rain fall, strong radiation and corrosion erosion. during transportation, please prevent the
collision and strong vibration.
Storage
When the storage equipment is stored indoors, the ambient air temperature can be 0
°
C to +30
°
C, the
average monthly humidity is not more than 90%, and there is no corrosive, flammable and explosive gas in
the surrounding air; the storage warehouse should be ventilated and free of alkali No strong mechanical
vibration, shock, strong electromagnetic field and direct sunlight. The battery is stored at around 50% to
60%, and the battery should be recharged after three months.