14
SE
TTINGS \ GENER
AL
S0 SUPERVISOR
Set S0 Serial Bus Parameters (main BUS)
Identif No.: Communication board identification number
Spd:Transfer speed
Prot:Communication protocol
S0 S
UPERVISOR
P
ARAMETERS
These parameters allow configuring the S0 serial port of the control unit in order to
communicate with the user interface UI with external devices (e.g.: a PC).
You can set the following parameters:
Identif No.: Identification number “address” (1..207) to be used from an external device
to communicate with the control unit
Spd: Communication speed of the external device with which to communicate.
Prot: Communication protocol of the external device with which to communicate.
• pLan: User interface connection.
• MASTER RS485: PC connection.
NB: Every time the control unit restarts, communication is set to pLan.
Setting the S0 configuration parameters
Name
Description
Default value
Identif No.
Unit address if
1
Spd
Transmission speed
19200
Prot
Communication protocol
pLan
105
J7
J10
J9
J8
J5
J1
G
G0
+5V
re
f
+VDC
ID1
GND
J3
C1
NC1
NO1
J2
SYNC
B1
B2
B3
B4
B5
B6
GND
serial card 1
J4
J6
TLAN
GND
C2
NO2
GND
Y2
Y1
GNX
ISOLATED
Tx/Rx
PWM 0/10V
GND
Tx/Rx
J12
GND
ID2
B7
B8
J11
NO4
NO5
NO6
NO7
C3
NO3
C3
24 V (+10/-15%); 50/60 Hz
48 V (36Vmin…72 Vmax)
input voltage:
max. power:
14 VA /11 W
S0 SUPERVISOR
Identif. No.:001 0
Spd: 19200
Prot:5:pLAN
──────────────────────
Parameters
J4 connector
S1 SUPERVISOR
Set S1 Serial Bus Parameters (supervisor BUS)
Identif. No.: Communication board identification number
Spd: Transfer speed
Prot: Communication protocol
S1 S
UPERVISOR
PARAMETERS
These parameters allow configuring the S1 serial port of the control unit in order to
communicate with external devices.
You can set the following parameters:
Identif No.: Identification number “address” (1..207) to be used from an external device
to communicate with the control unit
Spd: Communication speed of the external device with which to communicate.
Prot: Communication protocol of the external device with which to communicate.
Used protocols:
- NET Carel RS485
- Modbus Ext
- Konnex
SETTING THE CONFIGURATION PARAMETERS “MASTER—SLAVE”
Name
Description
Default value
Identif No.
Unit address if
1
Spd
Transmission speed
19200
Prot
Communication protocol
ModBus Ext
105
J7
J10
J9
J8
J5
J1
G
G0
+5V
re
f
+VDC
ID1
GND
J3
C1
NC1
NO1
J2
SYNC
B1
B2
B3
B4
B5
B6
GND
serial card 1
J4
J6
TLAN
GND
C2
NO2
GND
Y2
Y1
GNX
ISOLATED
Tx/Rx
PWM 0/10V
GND
Tx/Rx
J12
GND
ID2
B7
B8
J11
NO4
NO5
NO6
NO7
C3
NO3
C3
24 V (+10/-15%); 50/60 Hz
48 V (36Vmin…72 Vmax)
input voltage:
max. power:
14 VA /11 W
S1 SUPERVISOR
Identif. No.:001 0
Spd: 19200
Prot:3:ModBus Ext
──────────────────────
Parameters
Serial Card 1