Enable pump anti-seize function
in the “Enable” field: You can enter the days of
inactivity after which the control unit will make the pump work for a number of minutes
set in the Operation field.
A
NTI
-
SEIZE
PARAMETERS
You can set the following parameters:
Enable:
• Yes: Anti-seize function activation
• No: Anti-seize function deactivation.
Days of Inactivity: Number of days when the system remains inactive after which the
anti-seize function starts.
Operation: Minutes of pump forced operation following the previously set days of
inactivity.
Anti-Seize
──────────────────────
Enable: NO
Days of Inactivity: 15
Operation time: 05
──────────────────────
Parameters
Start/stop logics
FREE COOLING
Enable Free-Cooling in AHUs
En.Sum: Enabling the operation in summer
En.Win: Enabling the operation in winter
T.FC su: summer starting temperature, when the room temperature exceeds the set
value.
T.FC wi: winter starting temperature, when the room temperature exceeds the set
value.
Del.Tmp: difference between room temperature (zone) and outdoor temperature.
Time check: sample time to check if the activation of the function is convenient
(control time to switch off the function once it has been enabled).
Free Cooling
──────────────────────
Ab.Est:No Ab.Inv:No
T.FC su: 25.0 Del.Tmp:
T.FC wi: 20.0 06.0
Time check: 300 sec
──────────────────────
Start/stop logics
AUTOMATIC SEASON
Enable automatic change of season
when set to “Auto”, the control unit automatically switches from summer/winter
operation under appropriate conditions
Automatic Season
──────────────────────
Auto
Set change:22.0 °C
Sampling:030 sec
Neutral Temp.:1.0 °C
──────────────────────
Change mode
PRODUCTION TYPE
Set the parameters of the production type
Type: Chiller / Heat pump, it represents the energy source feeding the system
En Switch Prod: (only with type = Heat pump) Yes/No, if “Yes” is set in the system,
there is another heat generator (es. boiler) apart from the heat pump.
t. Switch: (default 30 sec) delay time before changing primary resource into secondary
resource.
Tmp Ext: (default 5°C) set value for outside temperature below which the controller
switches the energy production from the primary source (Heat pump) to the
secondary one (boiler).
PRODUCTION TYPE
──────────────────────
Type: Chiller
En Switch Prod:No
t.Switch:030 sec
Tmp Ext:05.0
──────────────────────
Production type