LP
GAS
HOOK-UP
A typical LP gas installation is show
n
on the right. Do not use any replacement regulator other
than that specified by the manufacturer. Use only pipe sealants that are approved for use with
natural and LP gases. An installer-supplied gas shutoff valve must be installed in an accessible
location. (Reference: leak test procedure).
Although
LP Gas Cylinder may be used, it is not recommended due to the large amount of
Gas Consumption and may freeze up the gas cylinder as well as a safety risk.
VENTING YOUR ENCLOSURE:
An enclosure or Island for LP gas cylinder must be vented on
the level of the cylinder valve and at floor level. The effectiveness of the opening(s) for purposes of
ventilation shall be determined with the LP gas supply cylinder in place. This shall be accomplished
by one of the following: a. One side of the enclosure shall be fully open; or
b. For an enclosure having four sides, a top and a bottom:
At least two ventilation openings at cylinder valve level shall be provided in the sidewall,
equally sized, spaced at 180 degrees (3.14 rad), and unobstructed. Each opening shall have
a total free area of not less than 1/2 square inch per pound (7.1 cm2/kg) of stored fuel capacity and not
less than a total free area of 10 square inches (64.5 cm2).
Ventilation opening(s) shall be provided at floor level and shall have a total free area of not
less than ½" square inch per pound (7.1 cm2/kg) of stored fuel capacity and not less than a total free
area of 10 square inches (64.5 cm2). If ventilation openings at floor level are in a sidewall, there shall
be at least two openings. The bottom of the openings shall be at floor level and the upper edge no more
than 5 inches (127 mm) above the floor. The openings shall be equally sized, spaced at 180 degrees
(3.14 rad) and un-obstructed.
See item #RVNT1 for vents.
LEAK TEST