Finned copper tube gas boilers & water heaters – Boiler Manual

8

F

F

OUTDOOR VENTING

When installed outdoors the Spectrum must be fi tt ed with the 
factory supplied outdoor hood assembly, see Figure 3.  Multiple 
units must be spaced per Figure 3A.

Th e boiler/water heater must be at least 

10 ft 

3.1 m

 from any 

door, window or gravity air inlet into any building and at least 

3 ft 

0.9 m

 from any overhang unless local codes dictate diff erently.

Avoid locations where wind defl ection off  of adjacent walls, buildings 
or shrubbery might cause a down draft . Th e unit(s) should be located 
at least 

3 ft 

0.9 m

 from structures. Outdoor installations are not 

recommended in areas where the danger of snow blockage exists. 

  Do not place the boiler/water heater in a location that 

would subject it to runoff  from adjacent buildings or 
damage may occur voiding the warranty!

Figure 3 

Outdoor Venting 

Figure 3A 

Multiple Outdoor Units 

GENERAL PIPING REQUIREMENTS

  Improper piping of this boiler/water heater will void the 

manufacturer’s warranty and can cause boiler failure 
resulting in fl ooding and extensive property damage! 
Excessive water hardness causing lime build-up in 
the copper heat exchanger tubes is NOT covered under 
the manufacturer’s warranty. Excessive pitt ing and 
erosion of the internal surface of the copper heat 
exchanger tubes is NOT covered under the 
manufacturer’s warranty if the result of high water 
fl ow rates, see Table 7 or 8. Return water temperatures 
below 

110°F

43°C

 will result in heat exchanger 

damage from excessive condensation voiding the 
manufacturer’s warranty, see Primary/Secondary 
Piping Figure 5.

  Shut off  valves and unions should be installed at the 

inlet and outlet connections of the boiler water heater 
to provide for isolation of the unit should servicing 
be necessary

.

Freeze Protection

Th is boiler/water heater is CSA designed certifi ed for outdoor 
installation. Outdoor installations in areas where the danger of 
freezing exists are not recommended unless proper freeze protection 
is provided. If the unit is to be installed in such an area the following 
precautions MUST be observed:
1.   A continuous fl ow of water through the boiler/water heater 

MUST be maintained! Th e pump responsible for fl ow through 
the boiler/water heater must run continuously! 

2.   An ethylene glycol/water mixture suitable for the minimum 

temperature that the unit will be exposed to must be used. Th e 
pump must be capable of producing 15% more fl ow and 
overcoming a 20% increase in head loss. Domestic water systems 
must be isolated from the water heater by the use of a 
heat exchanger or other approved method. 

3.   If the boiler/water heater must be shut off  for any reason the 

electric, gas and water supplies MUST be shut off  and the unit 
and its pump completely drained.

  Improper outdoor installation of this boiler/water heater 

can cause boiler failure voiding the manufacturer's 
warranty!

SP

E

CTRUM

HEADER
HOOD

SUPPLY/RETURN

HEADER HOOD

EXHAUST
HOOD

COMBUSTION

AIR HOOD

3'

0.9 m

4'

1.2 m

RIOM-53

RIOM-54

Summary of Contents for SPECTRUM Series

Page 1: ...dust and particulate particularly drywall dust will cause contamination of the burner resulting in possible severe personal injury death or substantial property damage The boiler can only be operated...

Page 2: ...IV FOR A MAXIMUM ALLOWABLE WORKING PRESSURE OF 160 PSI 1103 kPa WATER INSTALLER THESE INSTRUCTIONS TO BE AFFIXED ADJACENT TO THE HEATER CONSUMER RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE PURPOSES...

Page 3: ...2 18 457 Left Side 6 152 24 609 Right Side 6 152 24 609 Front 6 152 24 609 Flue 6 152 6 152 2 Anoptimumsitewillbelevel centraltothepipingsystem close toachimneyandhaveadequatefreshairforcombustion Ens...

Page 4: ...o less than 100 in2 64 516 mm2 in size The upper opening must be within 12 in 305 mm of but not less than 3 in 76 mm from the top of the enclosure The bottom opening must be within 12 in 305 mm of but...

Page 5: ...part of the boiler s draft hood This includes the removal or alteration of any baffles Neverinstallaventpipeofadiameterdifferent than that of the boiler draft hood flue collar Failure to comply with...

Page 6: ...ing after 5 minutes of main burner operation Use the flame of a match or candle or smoke from a cigarette cigar or pipe Faire fonctionner le br leur principal pendant 5 min ensuite d terminersilecoupe...

Page 7: ...Finned copper tube gas boilers water heaters Boiler Manual 7 F F Figure 1 Vertical Venting with a Metal Chimney System and Inside Air Figure 2 Vertical Venting using a Metal Chimney and Inside Air 10...

Page 8: ...f high water flowrates seeTable7or8 Returnwatertemperatures below 110 F 43 C will result in heat exchanger damage from excessive condensation voiding the manufacturer s warranty see Primary Secondary...

Page 9: ...stem pressure of 12 psig 82 7 kPa must be maintained Heating Boiler Piping Connections The supply and return connections should be sized to suit the system see Table 6 Table 6 Supply and Return Pipe S...

Page 10: ...19 4 1 20 1 2 3 4 400 33 2 3 54 2 1 10 4 22 1 1 70 1 4 4 9 Note Unit equipped with 2 pass headers see Table 7 Flow exceeds recommended maximum use a greater temperature rise or consult manufacturer Cu...

Page 11: ...ested piping configuration and valving Check with local codes and ordinances for specific requirements NOTES 1 Boiler circuit piping must be sized large enough to handle maximum flow through unit 2 Bo...

Page 12: ...ess than Temp Min slowly close valve B until T1 climbs to desired operating temperature above Temp Min 3 If T1 is greater than desired operating temperature slowly close valve A to adjust to lower des...

Page 13: ...g Requirements Ensurethatthewaterheaterisequippedwithbronzeheaders Piping and components connected to the water heater must be suitable for use with potable water The water heater must not be connecte...

Page 14: ...condensation of the products of combustion will damage the water heater voiding the warranty The method outlined below can be employed to prevent this condition from occurring A balancing valve shoul...

Page 15: ...Fi d b b il h B il M l Finned copper tube gas boilers water heaters Boiler Manual 15 F F Table 9A Spectrum Heat Exchanger Selection Graph Table 9B Spectrum Pumping Performance Requirement Table...

Page 16: ...making selection 6 Common piping must be sized for maximum combined heater flow 7 Hot water tanks should be equipped with a combination temperature pressure relief valve 8 MA Code requires an 1 8 in...

Page 17: ...ss and a 0 3 WC pressure drop Nominal Iron Pipe Size Pipe length in feet 10 20 30 40 50 60 80 100 150 Maximum gas volume of pipe ft3 hr 3 4 278 190 152 130 115 105 90 79 64 1 520 350 285 245 215 195 1...

Page 18: ...isher must be installed to prevent increase creep of gas pressure when the units are not operating This pressure regulator suppliedbyothers maybeinstalledattheserviceentrance to each unit or a master...

Page 19: ...g If a make up water pump is used adjust to maintain a minimum 12 psig 82 7 kPa system pressure Open the system bleed and drain valves one at a time to purge the air trapped in the heating system pipi...

Page 20: ...ntrol access panel 6 Push in gas control knob slightly and turn clockwise to OFF 7 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B i...

Page 21: ...tional 1000 ft 305 m Check the input rate as follows 1 Turn off all other gas appliances that use the same gas meter as the boiler water heater 2 Call your gas supplier and ask for the heating value o...

Page 22: ...fectu s par un installateur ou un service d entretien qualifi ou le foumisseur de gaz qui doivent avoir lu les in structions foumies avant de faire l installation l entretien ou l enl vement de la cha...

Page 23: ...3 Right Top 4 Left Bottom 5 Left Top 6 Right Bottom Heat Exchanger Replacement 1 Sagging or distorted heat exchanger tubes are an indication of low water flow through the system 2 A damaged heat exch...

Page 24: ...Fi d b b il h B il M l Finned copper tube gas boilers water heaters Boiler Manual 24 F F Figure 14 Replacement Parts REPAIR PARTS...

Page 25: ...0 1244 1 70 1245 1 70 1246 1 Combustion Chamber Rear Panel 03 0886 1 03 0887 1 03 0888 1 03 0889 1 03 0890 1 03 0891 1 03 0892 1 Combustion Chamber Front Panel 03 0894 1 03 0895 1 03 0896 1 03 0897 1...

Page 26: ...330 1 70 1331 1 70 1332 1 70 1333 1 Burner Drawer Assembly NG Intermittent Pilot 70 1341 1 2 Stage 70 1342 1 70 1343 1 70 1344 1 70 1345 1 70 1346 1 70 1347 1 Burner Drawer Assembly LP Intermittent Pi...

Page 27: ...0725 1 11 Jacket Left Side Panel 03 0774 1 1 1 1 1 1 1 12 Jacket Right Side Panel 03 0775 1 1 1 1 1 1 1 13 Jacket Front Panel 03 0767 1 03 0768 1 03 0769 1 03 0770 1 03 0771 1 03 0772 1 03 0773 1 14...

Page 28: ...turn Headers 06 0001 16 16 16 16 16 16 16 NS Nut Inlet Outlet Return Headers 57 0492 12 12 12 12 12 12 12 NS Stud Inlet Outlet Return Headers 57 0220 12 12 12 12 12 12 12 21 Inlet Outlet Header Cast I...

Page 29: ...4 1 1 1 Ignition Module S8610M SW 2 Stage 16 0054 1 1 1 1 1 1 1 31 Transformer 50 VA 15 0007 1 1 1 1 1 1 1 NS High Limit EMf 1 SB 14 0118 1 1 1 High Limit EMF 5 SB 14 0009 1 1 1 1 High Limit EMf 1 SW...

Page 30: ...10 0037 2 3 4 5 6 7 8 Orifice 34 6 000 ft 7 999 ft NG 10 0043 2 3 4 5 6 7 8 Orifice 47 LP 10 0038 2 3 4 5 6 7 8 Orifice 49 2 000 ft 3 999 ft LP 10 0040 2 3 4 5 6 7 8 Orifice 50 4 000 ft 5 999 ft LP 10...

Page 31: ...erminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUC...

Page 32: ...the manufacturer s warranty Excessive pitting and erosion on the inside of the heat exchanger tubes caused by high water velocity through the tubes and is not covered by the manufacturer s warranty Se...

Reviews: