background image

Fi

d

b

b il

&

h

B il

M

l

Finned copper tube gas boilers & water heaters – Boiler Manual

13

F

F

Variable Water Flows

Figure 5 shows a typical primary/secondary piping system. A 
dedicated pump is used to maintain a constant water fl ow through 
the boiler. Th is boiler pump is sized to overcome the head loss of 
the boiler and near piping while supplying the fl ow rate required 
to maintain the desired temperature rise across the boiler heat 
exchanger. Th e system pump is sized to provide the required fl ow 
to the heating system.

Low Return Water Temperatures

To prevent the problems associated with condensation of the 
products of combustion due to low return water temperatures a 
primary/secondary piping system with a bypass and bypass valve 
must be installed, see Figures 6 and 6A. Th e bypass and bypass 
valve must be sized the same as the secondary piping. A balancing 
valve must also be installed in the supply side of the secondary 
piping downstream of the bypass. Th e balancing valve should be 
adjusted to divert some of the heated discharge water into the return 
water until the required inlet water temperature is achieved. Th e 
primary and secondary pumps should be sized to provide the required 
fl ow through each system.

Multiple Boiler Systems

Systems using multiple boilers can also be installed using a primary/
secondary manifold system, Figure 7.

Piping For Use With Cooling Units

Th e boiler, when used in connection with a refrigeration system, 
must be installed so the chilled medium is piped in parallel with 
the boiler. Appropriate valves must be used to prevent the chilled 
water from entering the boiler.

When a boiler is connected to a heating coil that may 
be exposed to refrigerated air from an air handling device, the piping 
system must be equipped with fl ow-control valves or some other 
automatic means of preventing gravity circulation of the boiler water 
during the cooling cycle.

DOMESTIC WATER SUPPLY PIPING

 Proper controls must be used to prevent water 

supplied for domestic use from exceeding 

130°F

54°C

 or a scald injury will occur! When higher 

water temperatures are required for appliances such 
as a dishwasher, a mixing valve or some other 
tempering means must be installed. Households with 
small children may require water temperatures less 
than 

120°F

49°C

. Local codes must be complied with!

General Piping Requirements

Ensure that the water heater is equipped with bronze headers. Piping 
and components connected to the water heater must be suitable for 
use with potable water. Th e water heater must not be connected to 
any heating system piping or components previously used with a 
non-potable water heating appliance. No toxic chemicals, such as 
those used for boiler treatment, are to be introduced into any potable 
water used for space heating. If a hot water storage tank is used in the 
system, it must be equipped with a temperature and pressure relief 
valve that complies with ANSI Z21.22 or CAN-4.4 and CAN-4.6.

  Th e storage tank must be located as close to the water 

heater as possible to prevent excessive head loss which 
will reduce fl ow.

Water Chemistry

Th e required temperature rise across the water heater is based on 
water having a hardness between 5 and 25 grains per gallon with 
a level of dissolved solids not exceeding 350 ppm. Water having a 
hardness less than 5 grains can cause excessive corrosion of the 
heat exchanger. Water that has a hardness greater than 25 
grains per gallon and/or a level of dissolved solids exceeding 350 
ppm will require a recalculation of the pump size and temperature 
rise. 

A cupro-nickel heat exchanger may also be required. Th e 
manufacturer should be consulted when these water conditions 
are encountered. See Table 9A.

RBI water heaters are designed to run scale free. Due to the extreme 
variables of water conditions world wide it is necessary to consider 
pH values and water hardness in relationship to scaling. It is crucial 
to consider these two variables when making heat exchanger and 
pump selections. If local water conditions are extreme follow the 
guidelines in the Heat Exchanger Selection Table (Table 9A) and 
the Pumping Performance Table (Table 9B). Scale free operation 
can be achieved by using water with a hardness between 8 
and 18 and by maintaining the pH between 5 and 9. Follow the 
conditions listed under NORMAL in the table. In some areas of 
the country additional precautions must be observed due to unusual 
characteristics of the local water supply. Call the nearest RBI 
representative for details.

To properly size the pump a grain hardness and pH test 
must be taken at the installation site before the order is 
placed. Proper pump sizing will improve heater performance and 
help ensure heater longevity.

Expansion Tank

An expansion tank or other means to control thermal expansion 
must be installed in the water heating system if back fl ow prevention 
devices are installed.

Summary of Contents for SPECTRUM Series

Page 1: ...dust and particulate particularly drywall dust will cause contamination of the burner resulting in possible severe personal injury death or substantial property damage The boiler can only be operated...

Page 2: ...IV FOR A MAXIMUM ALLOWABLE WORKING PRESSURE OF 160 PSI 1103 kPa WATER INSTALLER THESE INSTRUCTIONS TO BE AFFIXED ADJACENT TO THE HEATER CONSUMER RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE PURPOSES...

Page 3: ...2 18 457 Left Side 6 152 24 609 Right Side 6 152 24 609 Front 6 152 24 609 Flue 6 152 6 152 2 Anoptimumsitewillbelevel centraltothepipingsystem close toachimneyandhaveadequatefreshairforcombustion Ens...

Page 4: ...o less than 100 in2 64 516 mm2 in size The upper opening must be within 12 in 305 mm of but not less than 3 in 76 mm from the top of the enclosure The bottom opening must be within 12 in 305 mm of but...

Page 5: ...part of the boiler s draft hood This includes the removal or alteration of any baffles Neverinstallaventpipeofadiameterdifferent than that of the boiler draft hood flue collar Failure to comply with...

Page 6: ...ing after 5 minutes of main burner operation Use the flame of a match or candle or smoke from a cigarette cigar or pipe Faire fonctionner le br leur principal pendant 5 min ensuite d terminersilecoupe...

Page 7: ...Finned copper tube gas boilers water heaters Boiler Manual 7 F F Figure 1 Vertical Venting with a Metal Chimney System and Inside Air Figure 2 Vertical Venting using a Metal Chimney and Inside Air 10...

Page 8: ...f high water flowrates seeTable7or8 Returnwatertemperatures below 110 F 43 C will result in heat exchanger damage from excessive condensation voiding the manufacturer s warranty see Primary Secondary...

Page 9: ...stem pressure of 12 psig 82 7 kPa must be maintained Heating Boiler Piping Connections The supply and return connections should be sized to suit the system see Table 6 Table 6 Supply and Return Pipe S...

Page 10: ...19 4 1 20 1 2 3 4 400 33 2 3 54 2 1 10 4 22 1 1 70 1 4 4 9 Note Unit equipped with 2 pass headers see Table 7 Flow exceeds recommended maximum use a greater temperature rise or consult manufacturer Cu...

Page 11: ...ested piping configuration and valving Check with local codes and ordinances for specific requirements NOTES 1 Boiler circuit piping must be sized large enough to handle maximum flow through unit 2 Bo...

Page 12: ...ess than Temp Min slowly close valve B until T1 climbs to desired operating temperature above Temp Min 3 If T1 is greater than desired operating temperature slowly close valve A to adjust to lower des...

Page 13: ...g Requirements Ensurethatthewaterheaterisequippedwithbronzeheaders Piping and components connected to the water heater must be suitable for use with potable water The water heater must not be connecte...

Page 14: ...condensation of the products of combustion will damage the water heater voiding the warranty The method outlined below can be employed to prevent this condition from occurring A balancing valve shoul...

Page 15: ...Fi d b b il h B il M l Finned copper tube gas boilers water heaters Boiler Manual 15 F F Table 9A Spectrum Heat Exchanger Selection Graph Table 9B Spectrum Pumping Performance Requirement Table...

Page 16: ...making selection 6 Common piping must be sized for maximum combined heater flow 7 Hot water tanks should be equipped with a combination temperature pressure relief valve 8 MA Code requires an 1 8 in...

Page 17: ...ss and a 0 3 WC pressure drop Nominal Iron Pipe Size Pipe length in feet 10 20 30 40 50 60 80 100 150 Maximum gas volume of pipe ft3 hr 3 4 278 190 152 130 115 105 90 79 64 1 520 350 285 245 215 195 1...

Page 18: ...isher must be installed to prevent increase creep of gas pressure when the units are not operating This pressure regulator suppliedbyothers maybeinstalledattheserviceentrance to each unit or a master...

Page 19: ...g If a make up water pump is used adjust to maintain a minimum 12 psig 82 7 kPa system pressure Open the system bleed and drain valves one at a time to purge the air trapped in the heating system pipi...

Page 20: ...ntrol access panel 6 Push in gas control knob slightly and turn clockwise to OFF 7 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B i...

Page 21: ...tional 1000 ft 305 m Check the input rate as follows 1 Turn off all other gas appliances that use the same gas meter as the boiler water heater 2 Call your gas supplier and ask for the heating value o...

Page 22: ...fectu s par un installateur ou un service d entretien qualifi ou le foumisseur de gaz qui doivent avoir lu les in structions foumies avant de faire l installation l entretien ou l enl vement de la cha...

Page 23: ...3 Right Top 4 Left Bottom 5 Left Top 6 Right Bottom Heat Exchanger Replacement 1 Sagging or distorted heat exchanger tubes are an indication of low water flow through the system 2 A damaged heat exch...

Page 24: ...Fi d b b il h B il M l Finned copper tube gas boilers water heaters Boiler Manual 24 F F Figure 14 Replacement Parts REPAIR PARTS...

Page 25: ...0 1244 1 70 1245 1 70 1246 1 Combustion Chamber Rear Panel 03 0886 1 03 0887 1 03 0888 1 03 0889 1 03 0890 1 03 0891 1 03 0892 1 Combustion Chamber Front Panel 03 0894 1 03 0895 1 03 0896 1 03 0897 1...

Page 26: ...330 1 70 1331 1 70 1332 1 70 1333 1 Burner Drawer Assembly NG Intermittent Pilot 70 1341 1 2 Stage 70 1342 1 70 1343 1 70 1344 1 70 1345 1 70 1346 1 70 1347 1 Burner Drawer Assembly LP Intermittent Pi...

Page 27: ...0725 1 11 Jacket Left Side Panel 03 0774 1 1 1 1 1 1 1 12 Jacket Right Side Panel 03 0775 1 1 1 1 1 1 1 13 Jacket Front Panel 03 0767 1 03 0768 1 03 0769 1 03 0770 1 03 0771 1 03 0772 1 03 0773 1 14...

Page 28: ...turn Headers 06 0001 16 16 16 16 16 16 16 NS Nut Inlet Outlet Return Headers 57 0492 12 12 12 12 12 12 12 NS Stud Inlet Outlet Return Headers 57 0220 12 12 12 12 12 12 12 21 Inlet Outlet Header Cast I...

Page 29: ...4 1 1 1 Ignition Module S8610M SW 2 Stage 16 0054 1 1 1 1 1 1 1 31 Transformer 50 VA 15 0007 1 1 1 1 1 1 1 NS High Limit EMf 1 SB 14 0118 1 1 1 High Limit EMF 5 SB 14 0009 1 1 1 1 High Limit EMf 1 SW...

Page 30: ...10 0037 2 3 4 5 6 7 8 Orifice 34 6 000 ft 7 999 ft NG 10 0043 2 3 4 5 6 7 8 Orifice 47 LP 10 0038 2 3 4 5 6 7 8 Orifice 49 2 000 ft 3 999 ft LP 10 0040 2 3 4 5 6 7 8 Orifice 50 4 000 ft 5 999 ft LP 10...

Page 31: ...erminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUC...

Page 32: ...the manufacturer s warranty Excessive pitting and erosion on the inside of the heat exchanger tubes caused by high water velocity through the tubes and is not covered by the manufacturer s warranty Se...

Reviews: