background image

Fi

d

b

b il

&

h

B il

M

l

Finned copper tube gas boilers & water heaters – Boiler Manual

21

F

F

CHECKING & ADJUSTMENTS

Pilot Adjustment

Th e pilot burner fl ame should envelope 

3/8 in to 1/2 in

9.5 mm to 12.7 mm

 of the fl ame sensing probe, Figure 11. To 

adjust the pilot the following steps must be taken:
1.   Remove the pilot gas pressure regulator cap.
2.   Turn the pressure regulator adjustment screw clock-wise to 

decrease the fl ame and counterclockwise to increase it.

3.   Replace the pressure regulator adjustment screw cap.

Figure 11 

Pilot Flame Adjustment 

Gas Pressure Adjustment

  Th e maximum inlet gas pressure listed on the rating 

plate must not be exceeded or damage to the boiler/
water heater may occur!

Th e minimum supply pressure listed on the rating plate is for input 
adjustment.

NATURA

  L GAS: Optimum results are obtained when the boiler/

water heater is operated at its full input rating, with 

3.8 in to 4.2 in

96.5 mm to 106.7 mm

 WC of manifold pressure. Th e manifold 

pressure should not vary outside this range. Th e gas valve pressure 
regulator has been preset at the factory. If adjustment is necessary the 
following steps must be followed:
1.   Att ach a 

20 in

508 mm

 WC manometer to the tap on the 

manifold.

2.  Remove the regulator adjustment screw cap from the gas 

regulator. On systems that do not use a separate gas regulator, 
remove the adjustment screw cap from the gas valve body on 
the valve closest to the gas supply piping.

3.   Rotate the regulator adjustment screw clockwise to increase the 

manifold pressure, counterclockwise to decrease it.

4.    Replace the regulator adjustment screw cap and manifold pressure 

tap plug.

  Never force the regulator adjustment screw beyond 

the stop limits or damage to the regulator will occur!

PROPANE GAS: A manifold pressure of 

11 in

279 mm 

WC 

must be maintained for proper operation of the boiler. If the manifold 
pressure is off  by more than 5% adjust it according to steps 1 through 
4.

Input Rate, Natural Gas

Gas appliances are rated based on sea level operation with no 
adjustment required at elevations up to 

2000 ft 

610 m

. At 

elevations above 

2000 ft 

610 m

, input ratings should be reduced 

by 4% for each additional 

1000 ft 

305 m

.

Check the input rate as follows:
1.   Turn off  all other gas appliances that use the same gas meter 

as the boiler/water heater.

2.   Call your gas supplier and ask for the heating value of the gas.
3.   Start the boiler/water heater and let it run for 15 minutes.
4.   Using the gas meter and a stopwatch, clock the time that it takes 

to burn 

10 ft 

3

,

 

0.28m

3

 of gas and divide this time by 10.

5.    Insert the heating value and the time, in seconds, into the formula 

below.

6.   Input = (heating value, Btu/hr)(3600)/(time, seconds)
7.   If the computed rate deviates by more than 5% from the rated 

input value of the unit adjust the manifold pressure accordingly. 
DO NOT adjust the manifold pressure by more than 5%. If a 
proper rate cannot be maintained without adjusting the manifold 
pressure beyond the 5% limit, the main burner orifi ces must 
be replaced. If the input rate is too low, go to the next larger 
size of main burner orifi ces. If the input rate is too high, go to 
the next smaller size.

  Never increase the input to the boiler/water heater 

above that for which it is rated. Doing so can cause 
premature failure of the unit!

CONTROL DESCRIPTION

Low  Water Cutoff 

If the boiler is to be installed above radiation or if required by other 
codes or regulations, install a low water cutoff  in appropriate piping.

If installed, ensure that the low water cutoff  device(s) function 
properly. Test in accordance with the manufacturer’s instructions 
included with the device(s).

Boiler Thermostat

If a thermostat is to be used to control the boiler always follow the 
instructions included with the thermostat. Proper location of the 
thermostat will ensure effi  cient trouble-free operation of the boiler. 
Mount the thermostat to an inside wall at a height approximately 
fi ve feet above the fl oor.

Avoid placing the thermostat in areas that will not provide an accurate 
measurement of the room temperature. Locating the thermostat 
behind a door, in an alcove, close to a source of thermal radiation 
or in a draft y area will cause poor or sporadic heating.

For a thermostat that employs an adjustable heat anticipator, adjust 
the anticipator to match the current measured in the thermostat 
circuit. An increased anticipator sett ing may be necessary if the unit 
cycles frequently. If the room temperature over-shoots the thermostat 
sett ing, reduce the anticipator sett ing.

RIOM-48

Summary of Contents for SPECTRUM Series

Page 1: ...dust and particulate particularly drywall dust will cause contamination of the burner resulting in possible severe personal injury death or substantial property damage The boiler can only be operated...

Page 2: ...IV FOR A MAXIMUM ALLOWABLE WORKING PRESSURE OF 160 PSI 1103 kPa WATER INSTALLER THESE INSTRUCTIONS TO BE AFFIXED ADJACENT TO THE HEATER CONSUMER RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE PURPOSES...

Page 3: ...2 18 457 Left Side 6 152 24 609 Right Side 6 152 24 609 Front 6 152 24 609 Flue 6 152 6 152 2 Anoptimumsitewillbelevel centraltothepipingsystem close toachimneyandhaveadequatefreshairforcombustion Ens...

Page 4: ...o less than 100 in2 64 516 mm2 in size The upper opening must be within 12 in 305 mm of but not less than 3 in 76 mm from the top of the enclosure The bottom opening must be within 12 in 305 mm of but...

Page 5: ...part of the boiler s draft hood This includes the removal or alteration of any baffles Neverinstallaventpipeofadiameterdifferent than that of the boiler draft hood flue collar Failure to comply with...

Page 6: ...ing after 5 minutes of main burner operation Use the flame of a match or candle or smoke from a cigarette cigar or pipe Faire fonctionner le br leur principal pendant 5 min ensuite d terminersilecoupe...

Page 7: ...Finned copper tube gas boilers water heaters Boiler Manual 7 F F Figure 1 Vertical Venting with a Metal Chimney System and Inside Air Figure 2 Vertical Venting using a Metal Chimney and Inside Air 10...

Page 8: ...f high water flowrates seeTable7or8 Returnwatertemperatures below 110 F 43 C will result in heat exchanger damage from excessive condensation voiding the manufacturer s warranty see Primary Secondary...

Page 9: ...stem pressure of 12 psig 82 7 kPa must be maintained Heating Boiler Piping Connections The supply and return connections should be sized to suit the system see Table 6 Table 6 Supply and Return Pipe S...

Page 10: ...19 4 1 20 1 2 3 4 400 33 2 3 54 2 1 10 4 22 1 1 70 1 4 4 9 Note Unit equipped with 2 pass headers see Table 7 Flow exceeds recommended maximum use a greater temperature rise or consult manufacturer Cu...

Page 11: ...ested piping configuration and valving Check with local codes and ordinances for specific requirements NOTES 1 Boiler circuit piping must be sized large enough to handle maximum flow through unit 2 Bo...

Page 12: ...ess than Temp Min slowly close valve B until T1 climbs to desired operating temperature above Temp Min 3 If T1 is greater than desired operating temperature slowly close valve A to adjust to lower des...

Page 13: ...g Requirements Ensurethatthewaterheaterisequippedwithbronzeheaders Piping and components connected to the water heater must be suitable for use with potable water The water heater must not be connecte...

Page 14: ...condensation of the products of combustion will damage the water heater voiding the warranty The method outlined below can be employed to prevent this condition from occurring A balancing valve shoul...

Page 15: ...Fi d b b il h B il M l Finned copper tube gas boilers water heaters Boiler Manual 15 F F Table 9A Spectrum Heat Exchanger Selection Graph Table 9B Spectrum Pumping Performance Requirement Table...

Page 16: ...making selection 6 Common piping must be sized for maximum combined heater flow 7 Hot water tanks should be equipped with a combination temperature pressure relief valve 8 MA Code requires an 1 8 in...

Page 17: ...ss and a 0 3 WC pressure drop Nominal Iron Pipe Size Pipe length in feet 10 20 30 40 50 60 80 100 150 Maximum gas volume of pipe ft3 hr 3 4 278 190 152 130 115 105 90 79 64 1 520 350 285 245 215 195 1...

Page 18: ...isher must be installed to prevent increase creep of gas pressure when the units are not operating This pressure regulator suppliedbyothers maybeinstalledattheserviceentrance to each unit or a master...

Page 19: ...g If a make up water pump is used adjust to maintain a minimum 12 psig 82 7 kPa system pressure Open the system bleed and drain valves one at a time to purge the air trapped in the heating system pipi...

Page 20: ...ntrol access panel 6 Push in gas control knob slightly and turn clockwise to OFF 7 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B i...

Page 21: ...tional 1000 ft 305 m Check the input rate as follows 1 Turn off all other gas appliances that use the same gas meter as the boiler water heater 2 Call your gas supplier and ask for the heating value o...

Page 22: ...fectu s par un installateur ou un service d entretien qualifi ou le foumisseur de gaz qui doivent avoir lu les in structions foumies avant de faire l installation l entretien ou l enl vement de la cha...

Page 23: ...3 Right Top 4 Left Bottom 5 Left Top 6 Right Bottom Heat Exchanger Replacement 1 Sagging or distorted heat exchanger tubes are an indication of low water flow through the system 2 A damaged heat exch...

Page 24: ...Fi d b b il h B il M l Finned copper tube gas boilers water heaters Boiler Manual 24 F F Figure 14 Replacement Parts REPAIR PARTS...

Page 25: ...0 1244 1 70 1245 1 70 1246 1 Combustion Chamber Rear Panel 03 0886 1 03 0887 1 03 0888 1 03 0889 1 03 0890 1 03 0891 1 03 0892 1 Combustion Chamber Front Panel 03 0894 1 03 0895 1 03 0896 1 03 0897 1...

Page 26: ...330 1 70 1331 1 70 1332 1 70 1333 1 Burner Drawer Assembly NG Intermittent Pilot 70 1341 1 2 Stage 70 1342 1 70 1343 1 70 1344 1 70 1345 1 70 1346 1 70 1347 1 Burner Drawer Assembly LP Intermittent Pi...

Page 27: ...0725 1 11 Jacket Left Side Panel 03 0774 1 1 1 1 1 1 1 12 Jacket Right Side Panel 03 0775 1 1 1 1 1 1 1 13 Jacket Front Panel 03 0767 1 03 0768 1 03 0769 1 03 0770 1 03 0771 1 03 0772 1 03 0773 1 14...

Page 28: ...turn Headers 06 0001 16 16 16 16 16 16 16 NS Nut Inlet Outlet Return Headers 57 0492 12 12 12 12 12 12 12 NS Stud Inlet Outlet Return Headers 57 0220 12 12 12 12 12 12 12 21 Inlet Outlet Header Cast I...

Page 29: ...4 1 1 1 Ignition Module S8610M SW 2 Stage 16 0054 1 1 1 1 1 1 1 31 Transformer 50 VA 15 0007 1 1 1 1 1 1 1 NS High Limit EMf 1 SB 14 0118 1 1 1 High Limit EMF 5 SB 14 0009 1 1 1 1 High Limit EMf 1 SW...

Page 30: ...10 0037 2 3 4 5 6 7 8 Orifice 34 6 000 ft 7 999 ft NG 10 0043 2 3 4 5 6 7 8 Orifice 47 LP 10 0038 2 3 4 5 6 7 8 Orifice 49 2 000 ft 3 999 ft LP 10 0040 2 3 4 5 6 7 8 Orifice 50 4 000 ft 5 999 ft LP 10...

Page 31: ...erminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUC...

Page 32: ...the manufacturer s warranty Excessive pitting and erosion on the inside of the heat exchanger tubes caused by high water velocity through the tubes and is not covered by the manufacturer s warranty Se...

Reviews: