background image

SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS

Page 5

Figure 1 - Vertical Venting Using A Metal Chimney And Inside Air (8900/8800 Series)

10 FT 3.4 m

2 FT .6 m

3 FT 1 m

3 FT 1 m

5 FT 1.52 m

RIOM-40

Where communicating with the outdoors through 

horizontal ducts, each opening shall have a minimum 

free area of 

1 in

2

/2000 Btu/hr

1100 mm

2

/kW

 of the total 

input rating of all of the equipment in the enclosure. 

When ducts are used, they must have the same cross-

sectional area as the free area of the opening to which 

they connect.

Canadian installations must comply with CSA B149.1 

when 

air supply is provided by natural air flow from the 

outdoors for 

natural draft

, partial fan-assisted, fan-

assisted, or power draft-assisted 

burners

, there shall  

be a permanent 

air supply

 opening(s) having a cross-

sectional area of not less than 

1 in

2

 per

 

7,000 Btuh

 

 

(310 mm

2

 per kW)

 up to 

and including

 

1 million Btuh, 

plus

 1 in

2

 per 14,000 Btuh

 

(155 mm

2

 per kW)

 

in excess 

of

 

1 million Btuh

When calculating the free area necessary to meet  

the make-up air requirements of the enclosure, 

consideration must be given to the blockage effects  

of louvers, grills and screens. Screens must have  

a minimum mesh size of 

1/4 in

6.4 mm

. If the free  

area through a louver or grill is not known, ducts  

should be sized per Table 2.

Table 2 - Make-up Air Louver Sizing

Required Cross Sectional Area  

 Input 

1/4 in

 

6.4 mm

  75% Free Area   25% Free Area

 (MBH)    Wire Screen   Metal Louvers   Wooden Louvers     

    

in

2

 

cm

in

2

 

cm

in

2

 

cm

2

   420   

  

105

      

677 

    

140

     

903

 

  

420

     

2710

   530 

  

133

    

858

 

  

177

 

1142

 

  

530

     

3419

   630 

  

158

  

1019

 

  

210

 

1355

 

  

630

     

4064

   735  

  

184

 

1187

 

  

245

 

1581

 

  

735

     

4742

   840 

  

210

 

1355

 

  

280

 

1806

 

  

840

     

5419

   950 

  

238

 

1535

 

  

317

 

2032

 

  

950

     

6129

 1050 

  

263

 

1697

 

  

350

 

2258

 

1050

     

6774

 1160 

  

290

 

1871

 

  

387

 

2497

 

1160

     

7484

 1260 

  

315

 

2032

 

  

420

 

2710

 

1260

     

8129

 1370 

  

343

 

2213

 

  

457

 

2948

 

1370

     

8839

 1470 

  

368

 

2374

 

  

490

 

3161

 

1470

     

9484

 1580 

  

395

 

2548

 

  

527

 

3400

 

1580

 

10,194

 1685 

 

 421

 

2716

 

  

562

 

3626

 

1685

 

10,871

 1790 

  

448

 

2890

 

  

597

  

3852

 

1790

 

11,548

 1900 

 

 475

 

3065

 

  

633

 

4084

 

1900

 

12,258

 2000 

  

500

 

3226

 

  

667

 

4303 

2000 12,903

 2400 

  

600

 

3871

 

  

800

 

5161

 

2400

 

15,483

 2800 

  

700

 

4516

  

 933

 

6019

 

2800

 

18,064

 3200 

  

800

 

5161

 

1067

 

6884

 

3200

 

20,645

 3600 

 

 900

 

5806

 

1200

 

7742

 

3600

 

23,226

 4000 

1000

 

6452

 

1333

 

8600

 

4000

 

25,806

Summary of Contents for 8800 Series

Page 1: ...tion dust and particulate particularly drywall dust will cause contamination of the burner resulting in possible severe personal injury death or substantial property damage The boiler can only be oper...

Page 2: ...not followed exactly a fire or explosion may result causing property personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any...

Page 3: ...for the job The Net Ratings specify the equivalent amount of direct copper radiation that the unit can supply under normal conditions Also ensure that the unit has been set up for the type of gas ava...

Page 4: ...store objects on or around the boiler water heater CAUTION Combustion air contaminated with fluorocarbons or other halogenated compounds such as cleaning solvents and refrigerants will result in the f...

Page 5: ...he free area necessary to meet the make up air requirements of the enclosure consideration must be given to the blockage effects of louvers grills and screens Screens must have a minimum mesh size of...

Page 6: ...age 6 Figure 2 Vertical Venting Using A Masonary Chimney And Inside Air 8900 8800 Series Figure 3 Dual Flue Outlets And Inside Air 8900 8800 Series 10 FT 3 1 m 3 FT 1 m 5 FT 1 52 m 3 FT 1 m 10 FT 3 4...

Page 7: ...10FT 3 1 m 3 FT 1 m 5 FT 1 52 m PITCH PIPE DOWN TOWARDS TERMINAL CAP 1 4 IN PER FOOT 20MM M OF RUN TO ALLOW FOR CONDENSATE DRAINAGE BUILDING OVERHANG 4 FT 1 2 M MAX 3 FT 9 m 1 5 FT 0 5m MINIMUM DISTAN...

Page 8: ...nce is connected to the same chimney flue the flue must be large enough to safely vent the combined output of all the appliances WARNING If an appliance using any type of a mechanical draft system ope...

Page 9: ...ord s au syst me d vacuation commun et tous les ventilateurs d extraction comme les hottes de cuisin re et les ventilateurs des salles de bain S assurer que ces ventilateurs fonctionnent la vitesse ma...

Page 10: ...low switch must be installed in the supply piping adjacent to the boiler outlet connection CAUTION Failure to properly install the flow switch may result in damage to the boiler water heater heat exch...

Page 11: ...1900 2000 2400 2800 3200 3600 4000 Model Table 7 Temperature Rise Table 2 Pass Headers 35 F 0 4 0 7 1 1 1 6 2 4 3 3 4 4 5 8 4 1 6 8 34 3 40 8 47 6 54 4 61 6 68 0 75 2 81 6 88 8 95 3 131 2 157 4 183 7...

Page 12: ...n Water Temperatures To prevent the problems associated with condensation of the products of combustion due to low return water temperatures a primary secondary piping system with a bypass and bypass...

Page 13: ...onfiguration and valving Check with local codes and ordinances for specific requirements NOTES 1 Boiler circuit piping must be sized large enough to handle maximum flow through unit 2 Boiler pump size...

Page 14: ...ler circuit piping must be sized large enough to handle maximum flow through unit 4 All boilers furnished with factory mounted outlet water temperature gauge 5 Boiler pump purging required Use termina...

Page 15: ...on and or a level of dissolved solids exceeding 350 ppm will require a recalculation of the pump size and temperature rise Acupro nickel heat exchanger may also be required The manufacturer should be...

Page 16: ...loyed to prevent this condition from occurring A balancing valve should be installed on the outlet side of the water heater for purposes of adjusting the flow rate through the heat exchanger Thermomet...

Page 17: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 17 Table 9 8900 Pumping Performance Requirement Table Table 10 8800 Pumping Performance Requirement Table...

Page 18: ...formance Table before making selection 6 Common piping must be sized for maximum combined heater flow 7 Hot water tanks should be equipped with a combination temperature pressure relief valve 8 MA Cod...

Page 19: ...on site call the nearest RBI representative to resolve the problem NOTE A minimum gas supply presssure of 6 in 152 mm W C natural or 11 in 279 mm W C propane and maximum 14 in 356 mm W C natural or pr...

Page 20: ...diagram supplied with the boiler water heater for proper wiring connections GENERAL OPERATION WARNING Before proceeding read and fully understand the instructions contained in this manual Do not attem...

Page 21: ...pas vous servir des t l phones se trouvant dans le b timent Appelez imm diatement votre fournisseur de gaz depuis un voisin Suives les instructions du fournisseur Si vous ne pouvez rejoindre le fourni...

Page 22: ...reil ne se met pas en marche suivez les instructions intitul es Comment couper l admission de gaz de l appareil et appelez un technicien qualifi ou le fournisseur de gaz inches W C mm W C Natural 3 5...

Page 23: ...anifold pressure tap plug CAUTION Never force the regulator adjustment screw beyond the stop limits or damage to the regulator will occur PROPANE GAS Optimum results are obtained when the boiler water...

Page 24: ...water is 130 F 54 C The operating control should be set to the lowest setting that will satisfy the consumer s needs WARNING Setting the thermostat or operation control too high can result in scaldin...

Page 25: ...osion or other deposits that would impair the boiler water heater s performance Refer to page 29 8900 or page 38 8800 for component identification Combustion Chamber Inspection 1 Remove the left or ri...

Page 26: ...the GENERAL OPERATION and CHECKING AND ADJUSTMENTS sections of this manual for reference 1 Check the thermostat or operating controls for proper operation 2 A float type low water cutoff device must...

Page 27: ...ose or broken wire between pilot valve and PV MV PV terminals 24V at pilot gas valve leads Replace module Adjust the pilot gas pressure using the pilot regulator Pilot ignition problems can be caused...

Page 28: ...f valve is properly sized for the system never exceed 160 psi Expansion tank is waterlogged Ensure expansion tank is properly sized for the system Expansion tank is isolated Ensure valve between expan...

Page 29: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 29 PARTS LIST MODELS 420 1900 36 33...

Page 30: ...12 12 12 12 12 12 12 12 12 12 12 12 12 Nut Inlet Outlet Return Headers ASME 57 0492 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 NS Burner Shield 03 0092 1 03 0093 1 03 0094 1 03 0095 1 03 0096 1 03 0...

Page 31: ...2 2 2 2 2 2 2 2 2 2 2 2 2 NS Bracket Refractory Lower End 03 0307 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 18 End Refractory Panel Left Right 05 0001 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 19 Center Refractory Panel 05...

Page 32: ...0 0186 1 70 0187 1 70 0188 1 70 0189 1 70 0190 1 70 0191 1 NS Upper Rear Refractory Channel 70 0162 1 70 0163 1 70 0164 1 70 0165 1 70 0166 1 70 0167 1 70 0168 1 70 0169 1 70 0170 1 70 0171 1 70 0172...

Page 33: ...5 1 70 0086 1 Heat Exchanger Assembly Cupronickel 70 0087 1 Cast Iron Headers 70 0088 1 70 0089 1 70 0090 1 70 0091 1 70 0092 1 70 0093 1 70 0094 1 70 0095 1 70 0096 1 70 0097 1 70 0098 1 70 0099 1 70...

Page 34: ...70 0108 1 70 0109 1 70 0110 1 70 0111 1 70 0112 1 70 0113 1 70 0114 1 70 0115 1 70 0116 1 Heat Exchanger Assembly Cupronickel 70 0117 1 Bronze Headers 70 0118 1 70 0119 1 70 0120 1 70 0121 1 70 0122 1...

Page 35: ...r 70 0132 1 70 0133 1 70 0134 1 70 0135 1 70 0136 1 70 0137 1 70 0138 1 70 0139 1 70 0140 1 70 0141 1 70 0142 1 70 0143 1 70 0144 1 70 0145 1 70 0146 1 30 Tube Bundle Cupronickel 70 0147 1 70 0148 1 7...

Page 36: ...631 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Ignitor PSE NA185 LP 70 0632 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 33 Solenoid Valve w Regulator NG 24V 11 0373 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Solenoid Valve w Regulator LP 24...

Page 37: ...1 1 1 1 1 1 1 1 1 1 1 41 Orifice 29 NG 10 0016 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 Orifice 47 LP 10 0009 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 NS Pressure Relief Valve 50 13 0040 1 1 1 1...

Page 38: ...SERIES 8800 8900 INSTALLATION AND OPERATING INSTRUCTIONS Page 38 PARTS LIST MODELS 2000 4000 22 7 36 33 30 8 6 39 42 18 21 25 19 21a...

Page 39: ...1 70 1738 1 1 13 13a Burner Tube Aluminized Steel 10 0256 19 23 27 30 34 38 Burner Tube Aluminized w Bracket 70 1851 1 1 1 2 2 2 Burner Tube Stainless Steel 10 0258 19 23 27 30 34 38 Burner Tube Stain...

Page 40: ...Upper Right Left Refractory Support 03 1161 2 2 2 2 2 2 NS Tube Bundle Copper 70 1696 1 70 1697 1 70 1698 1 70 1699 1 70 1700 1 70 1701 1 Tube Bundle Cupronickel 70 1702 1 70 1703 1 70 1704 1 70 1705...

Page 41: ...1003 CSD 1 Only 16 0058 1 1 1 1 1 1 BTC Staging Control 4 Stage 14 0307 1 1 1 1 1 1 NS Alarm Board CSD 1 16 0023 1 1 1 1 1 1 37 Transformer 50 VA 15 0007 1 1 1 1 1 1 Transformer 75 VA 15 0008 1 1 1 1...

Page 42: ...ve 125 30 0364 1 1 Pressure Relief Valve 125 13 0009 1 Pressure Relief Valve 125 13 0003 1 1 Pressure Relief Valve 125 13 0053 1 NS Tridicator 13 0305 1 1 1 1 1 1 NS Thermometer HB 13 0302 1 1 1 1 1 1...

Page 43: ...ing appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GASVENTDIRECTLYBELOW KEEPCLEAROFALL OBSTRUCTIONS g INSPECTION Thestateorlocalgasinspectoroftheside w...

Page 44: ...hrough the tubes and is not covered by the manufacturer s warranty See Installation Instructions for proper pump performance Chemical corrosion no corrosive chemical freon dry cleaning chemicals degre...

Reviews: