69
Register
Parameter
Read/Write
Format
Note
Register Address
System Status
Registers
MODBUS
R
S16
"0 = Off, 1 =
Monitor, 2 =
Temp, 3 = Rate"
0
System Supply
Temperature
1
6
1
S
R
Outdoor
Temperature
2
6
1
S
R
3
6
1
S
R
e
r
u
t
a
r
e
p
m
e
T
W
H
D
Aux 1
Temperature
4
6
1
S
R
Aux 2
Temperature
5
6
1
S
R
6
6
1
S
R
p
m
u
P
m
e
t
s
y
S
System Pump
Runtime
7
6
1
S
R
8
6
1
S
R
p
m
u
P
W
H
D
DHW Pump
Runtime
9
6
1
S
R
Setback
R
S16
Only relevant if
MODBUS =
MNTR
10
reserved
Table V: Modbus System Status Registers
ITEM
RANGE
DEFAULT
USER
SETTINGS
WHEN
DISPLAYED
DESCRIPTION
MODBUS
OFF – MNTR – TEMP
– RATE
OFF
Always
ModBus Operating Mode: Off,
Monitor, Temp Control, Rate
Control
ADDRESS
1 to 247
1
MODBUS ON
ModBus slave address
DATA
TYPE
RTU <> ASCI
RTU
MODBUS ON
ModBus data type
BAUD
RATE
2400 <> 9600 <> 19K2
<> 57K6 <> 115K
19K2
MODBUS ON
PARITY
NONE - EVEN - ODD
EVEN
MODBUS ON
Even/Odd=1 stop bit,
None=2 stop bits
Table U: Modbus Screens