70
Register
Parameter
Read/Write
Format
Note
Register Address
Boiler 1 Status
Registers
Boiler1 detected
R
S16
"0 = boiler not
detected, 1 = boiler
detected"
16
Boiler1 On/Off
R/W
S16
"0 = offline, 1 =
online"
1028
Boiler1 Outlet
temperature
R
S16
17
Boiler1 Inlet
temperature
R
S16
18
Boiler1 Vent
temperature
R
S16
19
Boiler1 High Limit
temperature
R
S16
20
Boiler1 Operator
temperature
R
S16
21
Boiler1 Mod
Rate
R
S16
0-100%
22
Boiler1 Mix Rate
R
S16
not available in initial
release
23
Boiler1 Ignition
Status
R
S16
24
Boiler1 Runtime
R
S16
25
Boiler1 Cycles
R
S16
26
Boiler1 Pump
R
S16
27
Boiler1 Pump
Runtime
R
S16
28
Boiler1 Error
Code
R
S16
29
Boiler1 Error
History 1
R
S16
30
Boiler1 Error
History 2
R
S16
31
Boiler1 Error
History 3
R
S16
32
Boiler1 Error
History 4
R
S16
33
Boiler1 Error
History 5
R
S16
34
Boiler1 Error
History 6
R
S16
35
Boiler1 Error
History 7
R
S16
36
Boiler1 Error
History 8
R
S16
37
Boiler1 Error
History 9
R
S16
38
Boiler1 Error
History 10
R
S16
39
Boiler1 Error
History 11
R
S16
40
Boiler1 Error
History 12
R
S16
41
Boiler1 Error
History 13
R
S16
42
Boiler1 Error
History 14
R
S16
43
Boiler1 Error
History 15
R
S16
44
reserved
Table W: Boiler 1 Status Registers
Summary of Contents for VERSA IC
Page 2: ...2 Rev 2 is a software revision J1214G Aug 2014 completely new edition of this manual...
Page 78: ...78...
Page 79: ...79...