60
d. Wait 5 minutes.
e. Reattach cap on tee. Burner should re-ignite
after pre-purge time delay.
10. To restart system, follow lighting instructions in the
Operation section.
11. Check to see that the adjustable high limit control,
if provided, is set above the design temperature
requirements of the system.
For multiple zones: Check to make sure the flow is
adjusted as required in each zone.
12. Check that the heater is cycled with the thermo-
stat. Raise to the highest setting and verify that the
heater goes through the normal start-up cycle. Re-
duce to the lowest setting and verify that the
heater goes off.
13. Observe several operating cycles for proper oper-
ation.
14. Set the room thermostat or tankstat to desired
temperature.
15. Review all instructions shipped with this heater
with owner or maintenance person, return to enve-
lope and give to owner or place the instructions
inside front panel on heater.
OPERATION
Lighting Instructions
1. Before lighting, make sure you have read all of the
safety information in this manual.
2. Set the thermostat to the lowest setting.
3. Turn off all electrical power to the appliance.
4. This appliance is equipped with an ignition device
which automatically lights the burner. Do not try to
light the burner by hand.
5. Remove upper front panel.
6. Turn on main manual gas valve.
7. Wait 5 minutes to clear out any gas. Then smell for
gas, especially near the floor. If you then smell
gas,
STOP!
Follow the steps in the safety informa-
tion on the front cover of this manual. If you do not
smell gas, go to next step.
8. Turn on all electrical power to the appliance.
9. Provide contact closure across the Enable/Disable
terminals at the field wiring block.
10. Set thermostat to desired setting. The appliance
will operate. The igniter will glow after the pre-
purge time delay (15 seconds). After igniter
reaches temperature (45 seconds) the main valve
will open. System will try for ignition three times
with standard ignition module. If flame is not
sensed, lockout will commence.
11. If the appliance will not operate, follow the instruc-
tions “To Turn Off Gas To Appliance,” and call your
service technician or gas supplier.
12. Replace access panel.
13. If heater fails to start, verify the following:
a. There are no loose connections or that the
service switch is off.
b. Adjustable high temperature limit switch is set
above water temperature (if provided).
c. Thermostat is set above room temperature.
d. Gas is on at the meter and the heater.
e. Incoming gas pressure to the gas valve is
NOT less than 5.0 in. WC for natural gas, 11.0
in. WC for propane gas.
To Turn Off Gas To Appliance
1. Set the thermostat to lowest setting.
2. Turn off all electrical power to the appliance if serv-
ice is to be performed.
3. Remove upper front panels.
4. Turn off main manual gas valve.
5. Replace access panel.
Summary of Contents for 992C
Page 54: ...54 Wiring Diagram Models 992C 1262C...
Page 55: ...55 Wiring Diagram Models 1532C 2342C...
Page 69: ...69...
Page 70: ...70...
Page 71: ...71...