INSTALLATION CODES
Installation must be in accordance with
local codes
, or, in the absence of local codes, with the latest editions
of the
National Fuel Gas Code, ANSI Z223.1/NFPA 54,
and the
National Electrical Code, ANSI/NFPA 70.
In
Canada installations must conform with the current
CAN/CGA B149.1
or
.2
and the
Canadian Electrical Code
Part 1 CSA C22.2 No.1.
Where required by the authority having jurisdiction, the installation must conform to
American Society of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired
Heaters,
CSD-1.
INSTALLATION BASE
The heater should be mounted on a level, non-combustible surface. Heater must not be installed on
carpeting. The heater can be installed on a combustible surface only when the appropriate listed floor shield base
is provided. An optional listed floor shield base is available for factory installation with the heater on all indoor
models. Do
NOT
use the shipping base crate as an installation base.
NOTE:
The heater should be located in an area where water leakage will not result in damage to the area adjacent
to the appliance or to the structure. When such locations cannot be avoided, it is recommended that a suitable
drain pan, adequately drained, be installed under the appliance. The pan must not restrict air flow.
In addition, the heater shall be installed such that the gas ignition system components are protected from water
(dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, control replace-
ment, etc.).
Combustible floorshield ordering information:
ALTERNATE METHOD FOR PROVIDING A NON-
COMBUSTIBLE BASE
INSTALLATION INSTRUCTIONS
5
12"
Minimum
12"
Minimum
4"
Minimum
HEA
TER
Sheet Metal
24 Gauge
Fig.# 8148
Summary of Contents for 0133-4001 WH
Page 19: ...19 FLOW RATES...
Page 21: ...21 TYPE WH UNITEMP 80 SYSTEM PIPING DIAGRAMS...
Page 28: ...LOCATION OF CONTROLS 28 400 WH1 WH2 WH3 181 LOW NOx WH1 Fig 9360...
Page 29: ...29 Fig 9334 LOCATION OF CONTROLS...
Page 38: ...WIRING DIAGRAM WH2 182 260 38 WIRING DIAGRAMS...
Page 39: ...WIRING DIAGRAM WH2 330 400 39...
Page 40: ...40 WIRING DIAGRAM WH2 514 624...
Page 41: ...41 WIRING DIAGRAM WH2 724 1336...
Page 42: ...42 WIRING DIAGRAM WH2 1414 1826...
Page 43: ...43 WIRING DIAGRAM WH2 2100 2500...
Page 44: ...44 WIRING DIAGRAM WH2 3001 4001...
Page 45: ...WIRING DIAGRAM WH1 181 261 LOW NOx 45...