9.
DO NOT
apply excessive torque during rolling
operation and avoid thinning any wall of the tube
beyond 0.015".
10. Use same procedure on opposite end.
11. Apply line pressure test. Re-roll if necessary.
12. Reinstall as outlined under HEAT EXCHANGER
REASSEMBLY.
CLEANING FLUE GAS PASSAGEWAYS
Soot will clog areas between fins and cause even-
tual tube failure. Any sign of soot at base of burners or
around outer jacket indicates a need for cleaning.
1.
Lift off drafthood and flue collector by removing
bolts and screws.
2.
Remove "V" baffles from heat exchanger.
3.
Remove burner tray.
4.
Take garden hose and wash heat exchanger,
making sure soot is removed from between fins.
(Avoid excessive water against refractory).
5.
Reassemble: When heater is fired, some steam
will form from wet refractory. This is normal.
6.
Identify and correct reason for soot formation.
NOTE: In extreme cases it may be necessary to
remove the heat exchanger completely for cleaning.
The simplest method is high pressure cleaning at a
local car wash. DO NOT WIRE BRUSH!
CAUTION:
Soot is combustible, so exercise extreme care.
REPLACEMENT PARTS
See separate parts sheet in instruction envelope.
NOTE:
To supply the correct part it is important that you
state the model number, serial number and type of gas
when applicable.
Any part returned for replacement under standard
company warranties must be properly tagged with
RAYPAK return parts tag, completely filled in with the
heater serial number, model number, etc., and shipped
to the Company freight prepaid.
If determined defective by the Company and within
warranty, the part will be returned in kind or equal
substitution, freight collect. Credit will not be issued.
RAYPAK, INC.
2151 Eastman Avenue
Oxnard, CA 93030
51
ILLUSTRATED PARTS LIST
AVAILABLE AT
WWW.RAYPAK.COM
CATALOG
MODEL
NUMBER
133
9300.11
181-401
9300.203
334-824
9300.35
926-1826
9300.50
2001-2500
9300.60
Summary of Contents for 0133-4001 WH
Page 19: ...19 FLOW RATES...
Page 21: ...21 TYPE WH UNITEMP 80 SYSTEM PIPING DIAGRAMS...
Page 28: ...LOCATION OF CONTROLS 28 400 WH1 WH2 WH3 181 LOW NOx WH1 Fig 9360...
Page 29: ...29 Fig 9334 LOCATION OF CONTROLS...
Page 38: ...WIRING DIAGRAM WH2 182 260 38 WIRING DIAGRAMS...
Page 39: ...WIRING DIAGRAM WH2 330 400 39...
Page 40: ...40 WIRING DIAGRAM WH2 514 624...
Page 41: ...41 WIRING DIAGRAM WH2 724 1336...
Page 42: ...42 WIRING DIAGRAM WH2 1414 1826...
Page 43: ...43 WIRING DIAGRAM WH2 2100 2500...
Page 44: ...44 WIRING DIAGRAM WH2 3001 4001...
Page 45: ...WIRING DIAGRAM WH1 181 261 LOW NOx 45...