Menu Path:
Setup > Enter Password (Default 00000) > Grid STD):
Menu Path:
Setup > Enter Password (Default 00000) > Run Setting:
Grid STD
1. China
2. Germany
3. Australia
4. Italy
5. Spain
6. UK
7. Hungary
8. Belgium
9. New
Zealand
10. Greece
11. France
12. Bangkok
6. UK
Allows the user to select the country that the system is
installed in
13. Thailand
14. South Africa
15. 50549
16. Brazil
17. 0126
18. Ireland
19. Israel
20. Poland
21. Chile
22. Local
23. 60Hz
24. Denmark
Enabled -
PF1.0 (UK)
GRID POWER
100%
Limit or increase the power exported from the system to
the grid.
264V (UK)
276V (UK)
184V (UK)
172V (UK)
52Hz (UK)
53.5Hz (UK)
47Hz (UK)
46Hz (UK)
OVER VOLT
Enabled (264V
UK)
UNDER VOLT
Enabled (200V
UK)
OVER FREQ
Enabled
(50.2Hz UK)
UNDER FREQ
Enabled
(49.25Hz UK)
REACT RESP
10 Seconds
This is the time it takes for the exported reactive power
to reach the grid standard level. This setting should not
be changed and is set according to the grid standard.
VRT ENABLE
Disable
Enable
Enable
Voltage-ride-through. This setting should not be
changed and is set automatically according to the grid
POW SI RATE
100%
This is the rate of change of the output. This setting
should not be changed and is set according to grid
standard. 100% means that the output will hit full power
These settings should not be altered. They are set
automatically according to the country selected within
Grid Setting.
If the inverter sees that these values have been reached,
or exceeded, then the inverter will stop generating.
The inverter can monitor reactive power in several ways.
This setting is set according to the selected grid standard
and should not be changed. For UK grid setting the
default method is power factor.
Power Factor
React Power
QU Curve
QP Curve
INV Max
Grid Max
INV Min
Grid Min
INV Max
Grid Max
INV Min
Grid Min
Disable
Enable
Disable
Enable
Disable
Enable
Disable
Enable
VOLT MAX
VOLT MIN
FREQ MAX
FREQ MIN
0…110%
0…60
0…300%
Run Setting
REACT MODE
Telephone : +44 (0) 1245 428500
Email : [email protected]
Page 39