13.4
Low Input Voltage
•
When the input voltage of the system is below the minimum voltage (battery supply) the system will
raise an alarm. The primary module will display ‘
IN VLT LOW
’ message when this condition remains
for more than 3 seconds. The alarm is cleared when the input voltage increases to normal level.
13.5
High Input Voltage
•
When the input voltage of the system is above the maximum voltage the system raise an alarm. The
primary module will display ‘
IN VLT HIGH
’ message when this condition remains for more than 3
seconds. The alarm is cleared when the input voltage decreases to normal level.
13.6
Extra Low Input Voltage
•
In any configuration (parallel/single) when the input voltage of the system is below 38V for more than
200msec, then the master turn the system in bypass mode until the input voltage increase in normal
levels. All modules of the system will display ‘
EXTRA LOW Vin
’ message.
13.7
High RRU Input Voltage
•
When the input voltage of the RRU is above the maximum operational voltage the system will
decrease the output voltage rapidly. Then the primary module will raise an alarm and will display
‘
RRU VLT HIGH
’ message in case that this condition remains for more than 3 seconds. The alarm is
cleared by when the RRV‘s input voltage decreases to normal level.