10.2
Overcurrent
•
When the current of a Secondary module exceeds the maximum rated current (110A) for more than
3 seconds, the Secondary module will switch to its bypass mode and display the
“HIGH CURRENT”
message. The Primary module will detect the overcurrent condition of the Secondary module and
raise the
“MODULE FAILURE”
alarm.
•
When the current of a Primary module exceeds the maximum rated current (110A) for more than
3 seconds, the Primary module will switch to its bypass mode and display the
“HIGH CURRENT”
message. The Secondary module will detect the overcurrent condition of the Primary module and
take control so as to become the Primary module. This new Primary module will raise a
“PRIMARY
FAILURE”
alarm.
10.3
Low Input Voltage
•
When the system input voltage is below the minimum voltage (usually the minimum battery voltage),
the system will raise an alarm. The Primary module will display the
“IN VLT LOW”
message if this
condition is sustained for more than 3 seconds. The alarm is automatically cleared when the input
voltage returns to its normal operation level.
Halted Secondary
Module
Primary Module
Halted Primary Module
New Primary Module