6.2
Module Failure
•
When a Secondary module fails the Primary module will raise an alarm. The front panel’s LED will
change from
GREEN
to
RED
, the remote contact will change toFailed and the Primary module will
display the “
MODULE FAILURE
” message.
•
After removing the failed Secondary module, the Primary module will search for a newly installed
module. When detected, the Primary module will transfer the original configured output voltage to the
new Secondary module.
•
The alarm is cleared after pressing the ‘
ENTER
’ button on the Primary module for more than 3 seconds.
6.3
Primary Module Failure
•
When the Primary module fails another Secondary module will takeover the role of Primary and raise
an alarm. The front panel’s LED will change from
GREEN
to
RED
, the remote contact will change to
Failed and the new Primary module will display the “
PRIMARY FAILURE
” message.
•
After removing the module the newly assigned Primary module will search for a replacement module
to be installed. When this occurs, the current Primary module will transfer output voltage to the new
module. The new module will be configured as a new Secondary module.
•
The alarm will disappear after pressing the ‘
ENTER
’ button on the current Primary module for more
than 3 seconds.