PowerPlus RDIDC-100-3R-1U-X
INSTALLATION INSTRUCTION & OPERATION MANUAL
www.raycap.com
© Raycap | All rights reserved.
•
(
320-1674) | Rev.A
Page 26 of 28
Scan QR for Complete Installation Instructions:
Rooftop with 2 Short & 1 Long Cable Lengths
If one sector requires cable lengths
longer than 240' a RDIDC-100-3R-1U-1
will be required to boost voltage on the
long run to compensate for voltage
drop.
Rooftop with 1 Short & 2 Long Cable Lengths
If two or more sectors requires cable
lengths longer than 240' a
RDIDC-100-3R-1U-1 will be required to
boost voltage to compensate for
voltage drop.
HP
LP
HP
HP
LP
HP
HP
LP
HP
G
B
A
RDIDC-3045-PF-48
G
B
A
HP
LP
HP
HP
LP
HP
HP
LP
HP
RDIDC-3045-PF-48
HP
HP
LP
HP
HP
LP
HP
HP
LP
9
8
7
6
5
4
3
2
1
Output to Remote Radio Heads
Input from
PowerPlus Module 1
Input from
PowerPlus Module 1
Legend
A = Alpha (Blue color)
B = Beta (Orange color)
G = Gamma (Green color)
HP = High Power RRU (1350W)
LP = Low Power RRU (150W)
Grey Cables are <240'
Red Cables are >240'
Legend
A = Alpha (Blue color)
B = Beta (Orange color)
G = Gamma (Green color)
HP = High Power RRU (1350W)
LP = Low Power RRU (150W)
Grey Cables are <240'
Red Cables are >240'
HP
HP
LP
HP
HP
LP
HP
HP
LP
9
8
7
6
5
4
3
2
1
Output to Remote Radio Heads
150A Input from
the DC Plant
150A Input from
the DC Plant
Summary of Contents for PowerPlus RDIDC-100-3R-1U Series