Fig. 95
IMPORTANT :Please,
lubricate the internal
part of the seals before
being fitted.
43
IMPORTANT
These instructions must be read in
conjunction with the main installation and
servicing
instructions
As with all fl ues the kits must be installed
taking due account of the current issue of BS
5440 parts 1 & 2 and timber frame housing
REF
DM2
Also note that the requirements will vary
depending upon the kit being installed.
Guidance is provided but unless otherwise
stated, always comply with the
recommendations of the relevant codes of
practice
Make sure that the Flue manifold rubber seal
is locate into the fl ue manifold, and lubricate
the internal part of the seal before assembly.
(see sect. 4.6)
Locate the header gasket on the twin fl ue
header and push into the Flue adaptor
(Fig.31 item 56) making sure that the inner
plastic exhaust locates fi rmly in the outlet
spigot of the fl ue manifold, and screw
the securing screw that secure the twin fl ue
header on the boiler.
Locate the 2 x 80 mm ‘O’ rings in the twin
flue header and lubricate the internal part of
the seal before assembly to ensure easy
snug fi t.(see sect. 4.6)
Figures show the versatility of this flueing
system. Measurements and bends must be
calculated correctly so as not to oversize
maximum flue lengths.
All located ‘O’ rings must be lubricated with
a silicone grease to ensure easy, snug fit.
NOTE: Exhaust flue must slope 2.5° down
towards the boiler 45 mm/m fall per metre of
flue length.
Spacing Clips
Spacing Clips are available on request should
they be required.
NOTE: for eccentric vertical flue a 125 mm
(5 in) diameter flashing plate will be required.
SECTION 11
INSTALLATION INSTRUCTIONS FOR ALTERNATIVE FLUE SYSTEM
11.1
INSTALLATION INSTRUCTIONS FOR TWIN FLUE PIPE (ECCENTRIC FLUE DUCT SYSTEM)
11.1.1 TWIN FLUE INSTRUCTIONS
This part of the installation manual covers the
installation
and
fi xing instructions of the twin
fl ue eccentric fl ue duct systems only
When ordering twin fl ue it must be stated for
CSI LOW NOX range.
Typical installation procedures are illustrated
by
drawings
Before fi xing the twin fl ue system the existing
Remove the front panel of the case(sect.8.1)
Unscrew the screw (Fig.31 item 66) on the
Flue adapter.
Part. No Description
0019SDO11005/0 Twin fl ue header F80/F80
0019PRO11020/0 Straight pipe L.1000 d80
0019CUR11015/0 90° Elbow d80
0019CUR11020/0 45° Elbow d80
0019GRI11005/0 Air inlet terminal d80
0019GRI11010/0 Exhaust terminal d80
0019TER06011/0 Vertical eccentric fl ue Terminal