CHAPTER 3
22
VSN® Operation Manual
FIGURE 18. Calibration In Progress
NOTE:
Values displayed in red during the calibration process indicate an issue with the calibration
parameters and may cause the calibration to stop or require the calibration to be restarted.
To successfully complete calibration, the following values will be required:
•
Yaw rate must remain below 2.5° per second
•
Roll must be less than 2°
•
Quality must be above 50
7. Bring the machine to a complete stop.
8. Review the Camera Calibration Results page. To complete the calibration and save the displayed values, select
the check mark button.