background image

24

b)

PROD 2 display will now show "Prn" and DATA display will show "End" (Print Field
End).

1)

To Print Field End, depress 

.

2)

While "End" is displayed, if Field Begin is required, depress 

to toggle DATA display to "BEGn".

c)

Momentarily depress 

 to advance to FIELD REFERENCE.

3)

FIELD REFERENCE

a)

PROD 1 display will show "SPr".  PROD 2 display will show "FrEF".  DATA display will show
"0".

b)

Enter the field number.

c)

Momentarily depress 

 to advance to BAUD RATE.

4)

BAUD RATE

a)

PROD 1 display will show "SPr".  PROD 2 display will show "bAUd".  DATA display will show
"1200".

b)

Depressing 

 momentarily changes the DATA display between "1200" and "9600".

c)

Momentarily depress 

 to advance to RATE CHANGE ALARM ON/OFF.

5)

RATE CHANGE ALARM ON/OFF

a)

PROD 1 display will show "SPr".  PROD 2 display will show "rAtE".  DATA
display will show "on".

b)

Depressing 

 momentarily changes the DATA display between "on" and

"oFF".  A value of "on" means alarm is enabled; a value of "oFF" means alarm
is disabled.

c)

Momentarily depress 

 to advance to DATA LOGGER TRIGGER VALUE.

6)

DATA LOGGER TRIGGER VALUE

a)

PROD 1 display will show "SPr".  PROD 2 display will show "TriG".  DATA display will show
"0".

b)

Enter the TRIGGER VALUE.

c)

Momentarily depress 

 to advance to DATA LOGGER TRIGGER UNITS.

Summary of Contents for SCS 700

Page 1: ...Installation Service Manual SCS 700 ...

Page 2: ...W A R N I N G Disconnect console before jump starting charging battery or welding on equipment ...

Page 3: ......

Page 4: ... ...

Page 5: ...ROGRAMMING 15 2 OTHER DISPLAY FEATURES 18 3 SELF TEST FEATURE 18 4 SEQUENCE TO ACTIVATE DATA LOCK 19 5 SEQUENCE TO CHANGE DATA LOCK 19 6 ENTER MODE SEQUENCE WITH ACTIVATED DATA LOCK 19 7 CONTROL VALVE DELAY 19 8 AUTOMATIC RATE 20 9 VOLUME AREA RATE ALARM 20 10 LOW LEVEL TANK FAULT 20 11 DATA MENU 20 12 DECIMAL SHIFT 31 PRODUCTINJECTIONINSTALLATIONANDSET UP 32 1 PLUMBING THE INJECTION MODULE 32 2 R...

Page 6: ...OCEDURE TO RE CALIBRATE FLOW METER 50 7 IMPREGNATIONMODULEINSTALLATION 51 8 INJECTIONMODULEINSTALLATION 53 9 INJECTIONMODULEMOUNTINGINSTALLATION 55 10 FLOW METER MAINTENANCE AND ADJUSTMENT PROCEDURE 57 11 PROCEDURE TO RE CALIBRATE PUMP 58 12 REMOTESWITCHOPTION 59 13 BOOM CAL DATA ENTRY FOR SCS 710 6 BOOM CONSOLE 60 14 SCS 710 6 BOOM CONSOLE WIRING DIAGRAM 61 15 SERIAL INTERFACE 62 16 SCS 700 710 C...

Page 7: ... 0 039 inch 1 centimeter cm 0 393 inch 1 meter m 3 281 feet 1 kilometer km 0 621 mile 1 inch 25 4 millimeters 2 54 centimeters 1 mile 1 609 kilometers PRESSURE 1 psi 6 89 kPa AREA 1 square meter 10 764 square feet 1 hectare ha 2 471 acres 10 000 square meters 1 acre 0 405 hectare 43 560 square feet 1 square mile 640 acres 258 9 hectares GPM Gallons per minute lit min Liters per minute dl min Decil...

Page 8: ...nt Wheel Drive and Speedometer Drive Speed Sensors are also available The Injection Module mounts to the framework of the sprayer The In Line Mixer mounts just before the Boom On Off Valves Appropriate cabling is furnished for field installation The operator sets the target application rate for each product to be sprayed and the SCS 700 automatically maintains the flow regardless of vehicle speed ...

Page 9: ...m of the radar See Figures 1 and 2 b The radar lens must be parallel to the ground from front to back Radar can be tilted out 0 15 degrees to provide more clearance and miss obstructions See Figure 2 c The radar should be mounted so that the length of the radar is parallel with direction of vehicle travel 3 Use carpenters level to verify that mounting bracket is parallel to the ground 4 Bolt mount...

Page 10: ...m be thoroughly rinsed out each day after use NOTE If system does not use carrier control for PROD 1 the injection option shown for PROD 2 is available for use in place of carrier control FIGURE 4 3 MOUNTING THE CONTROL VALVE 1 Mount the motorized Control Valve in the main hose line between the Flow Meter and the booms with motor in the upright position For flow less than 3 GPM 11 lit min the moto...

Page 11: ...ble on the sprayer Extension cables are available from a Raven Dealer Secure with plastic cable ties 4 Turn POWER ON OFF switch OFF and route the Red and White battery wires to a 12 volt battery Attach the White wire to the NEGATIVE terminal and the Red 16 gauge wire to the POSITIVE terminal DO NOT CONNECT WIRES TO THE STARTER Secure the battery wires with plastic cable ties DO NOT tie the battery...

Page 12: ... must be installed between the red 10 gauge wires and the battery The relay is normally controlled from the accessory side of the ignition switch See Figure 6A FIGURE 6B NOTE Disconnect console battery wires if the system is not used for an extended period i e two weeks With the POWER switch to OFF the system draws 9 milliamps of current to maintain information stored in the Console FIGURE 6A ...

Page 13: ...S Used to enter data into the Console to calibrate the system BOOM CAL Length of Boom Select boom number by using the UP DOWN arrrow keys SPEEDCAL Determined by Speed Sensor METER1CAL Injection Pump 1 Calibration Number METER2CAL Injection Pump 2 Calibration Number VALVE 1 CAL Injection Pump 1 Response Time VALVE 2 CAL Injection Pump 2 Response Time PROD 1 CAL Target Application Rate PROD 2 CAL Ta...

Page 14: ...Speedometer Drive Speed Sensor installation instructions Initial SPEED CAL is 598 152 Complete Steps 1 thru 6 to refine this number after INITIAL CONSOLE PROGRAMMING has been completed 1 Set POWER switches to ON all other switches to OFF 2 Enter 0 in 3 Drive 1 mile 1 kilometer To achieve the most accurate calibration accelerate and decelerate slowly CAUTION Do not use vehicle odometer to determine...

Page 15: ...en calculating METER CAL for a carrier typically METER 1 CAL is used as a carrier refer to the Flow Meter calibration number which is stamped on the label attached to the Flow Meter This number is to be used for gallon per area applications To convert original METER CAL from gallons to desired units of measure oz lbs or liters per area see METER CAL CONVER SIONS Write down this calibration number ...

Page 16: ...on Rate GPA lit ha GPK 3 Target Speed MPH km ha MPH 4 Nozzle Spacing inches centimeters inches From this information calculate the volume per minute per nozzle as follows GPM GPA GPK X MPH MPH X inches inches 5 940 137 lit min lit ha x km h x cm 60 000 Use GPM lit min and pressure to select appropriate tip from tip chart EXAMPLE 1 Application Pressure 30 PSI 200 kPa 30 PSI 2 Target Application Rat...

Page 17: ...RANGE RFM 5 0 05 5 GPM 0 2 18 9 lit min RFM 15 0 3 15 GPM 1 1 56 8 lit min RFM 60P 60S 1 60 GPM 3 8 227 lit min RFM 100 3 100 GPM 11 4 379 lit min RFM 200 200 Poly 15 200 GPM 56 8 757 lit min RFM 400 25 400 GPM 94 6 1514 lit min 2 Determine the target application rate for PROD 2 CAL that you are spraying Refer to the instructions on the product container using section DETERMINING INJECTION MODULE ...

Page 18: ...quence is always the same Depress the keys corresponding to the number you wish to enter i e 1 0 2 4 The numbers will be displayed in the DATA display as they are entered Depress the key in which you wish to enter data Depress the ENTER key An E will illuminate in the DATA display Complete the entry by again depressing the ENTER key ...

Page 19: ...show US The following steps must be followed 1 Displaying units of measure selections US acres SI hectares or TU 1000 sq ft a Depressing momentarily steps the DATA display from US to SI b Depressing momentarily steps the DATA display from SI to TU c Depressing momentarily steps the DATA display from TU to US 2 Selecting a unit of measure US SI or TU a To select US SI or TU step until the desired c...

Page 20: ... display from 2 Sd to 2 F b Depressing momentarily steps the DATA display from 2 F to 2 FC c Depressing momentarily steps the DATA display from 2 FC to 2 Sd 8 Selecting a Valve for PROD 2 2 Sd 2 F or 2 FC a To select 2 Sd 2 F or 2 FC step until desired code is displayed b Momentarily depress The DATA display will now display 0 The Console is now ready for the required Console Calibration programmi...

Page 21: ...r in If only one product is being used enter 0 15 Enter PROD 1 CAL Target Application Rate NOTE A decimal point is automatically shown in the display window Therefore 20 ounces per acre is entered as 2 0 0 but shown as 20 0 16 Enter PROD 2 CAL Target Application Rate in If only one product is being used you must perform the following two steps to complete the INITIAL CONSOLE PROGRAMMING a Enter 1 ...

Page 22: ...ime enter a 0 in this key 5 To display MPH km h momentarily depress 6 To display current VOLUME in PRODUCT 1 TANK depress 7 To display current VOLUME in PRODUCT 2 TANK depress 8 To display current UNITS OF MEASURE selection US SI or TU SPEED SENSOR selection SP1 or SP2 or VALVE selections 1 Sd 1 F or 1 FC and 2 Sd 2 F or 2 FC depress 3 SELF TEST FEATURE SELF TEST allows speed simulation for testin...

Page 23: ...K CODE If code is correct E will replace CodE in DATA display Now enter data normally NOTE The DATA LOCK feature prohibits the entry of data without first entering the DATA LOCK CODE If DATA LOCK is not desired omit Steps 4 5 and 6 The DATA LOCK CODE may be cleared by entering a code of 0 or by resetting the Console as described in REQUIRED CONSOLE PROGRAMMING 7 CONTROL VALVE DELAY Hold key until ...

Page 24: ...s 30 or more away from the target application rate for more than 5 seconds NOTE Go to DATA MENU to silence alarm 10 LOW TANK FAULT This feature will sound the alarm when the volume in the tank drops below an entered value The alarm will intermittently beep every 15 seconds and the DATA display will flash LEVL The alarm will stop when a value equal to or greater than the LOW TANK ALARM is entered i...

Page 25: ...ong beeps when a rate calibration number is changed via the serial port using a valid change request data string SPr triG 0 DATA LOGGER TRIGGER VALUE Used in data logging mode The trigger determines how often actual rate data string See Appendix 16 for data communication string formats is sent to the serial port The trigger may be either feet meters or seconds SPr Unit Ft DATA LOGGER TRIGGER UNITS...

Page 26: ...AULT PRODUCT 1 Turns alarm ON if Product 1 actual volume per minute falls below this limit Fr LL 2 0 VOLUME MINUTE RATE FAULT PRODUCT 2 Turns alarm ON if Product 2 actual volume per minute falls below this limit ALARM SCREENS ALr ALrM on AUDIBLE ALARMS ON OFF Turns audible alarms ON or OFF for the following 1 Volume Area Rate Alarm 2 Volume Minute Rate Fault 3 Low Tank Fault 4 Vacuum Alarm 5 Flow ...

Page 27: ...gitator ON or OFF for Product 2 MiSC APh 0 AREA HOUR Displays area per hour 1 Definition of Data Menu Key Depressing this key displays the selected Data Menu category in the PROD 1 display Depressing this key again increments through the Data Menu categories SPr GPS dAtE etc in the PROD 1 display Depressing this key after desired category is shown in PROD 1 display toggles up through desired featu...

Page 28: ...l show bAUd DATA display will show 1200 b Depressing momentarily changes the DATA display between 1200 and 9600 c Momentarily depress to advance to RATE CHANGE ALARM ON OFF 5 RATE CHANGE ALARM ON OFF a PROD 1 display will show SPr PROD 2 display will show rAtE DATA display will show on b Depressing momentarily changes the DATA display between on and oFF A value of on means alarm is enabled a value...

Page 29: ...S Upon each trigger the Actual Rate string Data Strings 1 2 and 3 and the Time date string are sent in that order When a Console calibration value is changed the Console will automatically send out the Cal 1 2 and 3 strings When a Console switch is changed the Data 1 2 3 Time Date and Cal 1 2 3 strings will be sent by the Console The Data with Time Date string included and Cal strings can also be ...

Page 30: ...hus 8 30 a m is entered as 8 30 but 1 30 p m is entered as 13 30 in the keyboard 12 MONTH a PROD 1 display will show dAtE PROD 2 display will show onth The DATA display will show 0 b Enter the current month by number i e 1 January 2 February etc c Momentarily depress to advance to DAY 13 DAY a PROD 1 display will show dAtE PROD 2 display will show daY The DATA display will show 0 b Enter the curre...

Page 31: ...ress to advance to VOLUME MINUTE RATE FAULT PRODUCT 1 18 VOLUME MINUTE RATE FAULT PRODUCT 1 a If the actual volume per minute falls below the set limit the injection pump stops slowing down or the control valve stops closing an alarm sounds and the PROD 1 display flashes LL The low limit value should be determined with all booms ON This value is automatically proportioned to the percentage of boom...

Page 32: ...TA display between on alarms enabled and oFF alarms disabled c Momentarily depress to advance to VACUUM AND FLOW FAULT PRODUCT 1 21 VACUUM AND FLOW FAULT PRODUCT 1 a Too much vacuum on the inlet side of the injection pump will cause inaccurate operation If pulling 10 inches of Hg for 5 seconds an audible alarm will sound and the PROD 1 display will flash VAC If there is a vacuum alarm 1 Strainer s...

Page 33: ...ntarily depressing changes the DATA display between on alarms enabled and oFF alarms disabled e Momentarily depress to advance to FLOW ERROR PRODUCT 1 23 FLOW ERROR PRODUCT 1 a If the booms are off or there is no speed but flow is detected for 5 seconds an audible alarm will sound and the PROD 1 display will flash FLo Err b PROD 1 display will show ALr PROD 2 display will show FE 1 DATA display wi...

Page 34: ...dband 4 20 Deadband 9 45 Deadband Actual rate is displayed if unit does not reach deadband within 10 seconds oFF means RATE displays the actual rate at all times c Momentarily depress to advance to AGITATOR PRODUCT 1 26 AGITATOR PRODUCT 1 a PROD 1 display will show MiSC PROD 2 display will show AG 1 DATA display will show oFF b Momentarily depressing changes the DATA display between on agitator 1 ...

Page 35: ...fting the decimal point can increase system accuracy DECIMAL PLACE LOCATIONS US METRIC TURF UNSHIFT SHIFT UNSHIFT SHIFT UNSHIFT SHIFT PROD 1 DISPLAY 000 0 00 00 0000 000 0 00 00 00 00 PROD 2 DISPLAY 000 0 00 00 0000 000 0 00 00 00 00 PROD 1 CAL 000 0 00 00 0000 000 0 00 00 00 00 PROD 2 CAL 000 0 00 00 0000 000 0 00 00 00 00 PROD 1 VOLUME 0000 000 0 0000 000 0 000 0 000 0 PROD 2 VOLUME 0000 000 0 0...

Page 36: ...e amount of product in tubing See Appendixes 7 8 and 9 for mounting instructions on various styles of injection modules 3 Inlet line from product tank to Injection Module shall be 3 4 suction hose 4 Plumb output lines of Injection Modules to Product Check Valves with 3 8 inch 10 mm tubing on low volume modules or 1 2 inch 13 mm tubing on high volume modules Product Check Valves and tubing not furn...

Page 37: ...em This will enhance the performance of the injection pump The basic components are shown below and are available through local spraying equipment supplier This system shall be installed as shown and operated per the following instructions The required frequency of flushing may vary per the product being injected 1 Drain or empty Product Injection Tank 2 Place VALVE 3 in Recirculation position 3 P...

Page 38: ... DETERMINING INJECTION MODULE METER CAL 1 Use the calibration tag attached to the Injection Pump reproduced below to determine the METER CAL for each product used NOTE Product METER CALS are oz dl per unit FIGURE 11 ...

Page 39: ... min dl min of product required by using the following formulas MAXIMUM vol min Speed x Boom Width x Rate 5 940 60 000 137 Speed Maximum Spray Speed in MPH km h Boom Width Maximum Number of Spray Nozzles x Nozzle Spacing in inches cm i e total boom width Rate Recommended Product Application Rate in Ounces per Acre dl ha oz 1 000 sq ft MINIMUM vol min Speed x Boom Width x Rate 5 940 60 000 137 Spee...

Page 40: ...IMUM and MINIMUM oz min dl min on the horizontal line of Pump Chart See Figures 12A 12B 12C 3 Draw a vertical line from these points to the highest pump setting 4 Use highest pump setting which intersects both vertical lines on the graphs EXAMPLE MAXIMUM setting of 58 1 oz min 17 0 dl min MINIMUM setting of 10 3 oz min 3 0 dl min pump setting 6 See Figure 13 NOTE Use the 10 setting for all product...

Page 41: ...ce carrier PRODUCT OFF MAN AUTO switch to MAN 4 Place POWER ON OFF switch to ON 5 Verify correct Boom Widths SPEED CALS METER CALS VALVE CALS and RATE CALS have been entered in the Console 6 Run pump at normal operating RPM 7 If centrifugal pump is used proceed to Step 8 If positive displacement type pump is used set pressure relief valve PRV to 65 PSI 448 kPa FIGURE 12A HIGH VOLUME PUMP OUTPUT CH...

Page 42: ...rier PRODUCT rate can be achieved If not consider increasing application rate of carrier or changing type of Control Valve Consult a Raven Dealer NOTE It is recommended that PRODUCT 1 be used for a Carrier 2 INITIAL CARRIER FIELD TEST 1 Drive down field or road at target speed with sprayer booms OFF to verify speed readout on Console 2 Turn on Sprayer pump and booms place the carrier PRODUCT OFF M...

Page 43: ...ch that injection PRODUCT 2 can be varied over a wide range above and below the desired application rate in oz acre dl ha Then set injection PRODUCT 2 for normal oz acre dl ha of application 13 Repeat Steps 11 and 12 for each Product in use 14 Place OFF MAN AUTO switch for each Product in use to AUTO The system will seek the programmed injection PRODUCT RATE CAL 15 Enter a SELF TEST speed 2 MPH 3 ...

Page 44: ...not drained 3 Periodically clean strainer on Injection Module 4 Check oil level in Injection Pump daily If addition of oil is required add Mobil 1 5W30 ONLY Drain and refill the pump after every 150 hours of operation See Figure 14 5 Flush Injection system by using flush system See RECOMMENDED INJECTION PUMP FLUSH SYSTEM or by recirculating water through Injection Module until pump is clear of pro...

Page 45: ...ounted in alternating red black order 4 Mount switch assembly to stationary column with the hardware provided See Figure 15A The switch assembly need not pivot with the wheel 5 Position switch assembly so that as the wheel rotates the magnets pass across the center of the black molded switch assembly See Figures 15A 15C 6 Clearance gap between magnets and switch assembly must be between 1 4 inch 6...

Page 46: ...les must be equal within 1 8 3 mm to ensure accuracy of system RIMS WITH SIX HOLE STUD PATTERN Locate the center of the holes to be drilled by using the rim webbing as a guide See Figure 16B Obtain a small piece of wood and cut to fit exactly over the web as shown in Figure 16B Measure the length of the piece of wood and mark the center on one edge Using the center mark on the piece of wood mark e...

Page 47: ... Console MEASURE CAREFULLY Be sure tire is properly inflated before measuring Measure tire in type of soil in which you will be spraying Circumference of tire will vary when measured in soft soil versus hard packed soil For best results measure several times and average the results Large tires and very low speed applications may require additional magnets to insure accurate speed readings Any even...

Page 48: ...ll into engine compartment 2 Install adapter and key on speedometer cable and connect to Transducer Assembly Some units do not use adapter and key 3 Connect Extension Cable to Transducer Assembly 4 Push Extension Cable through fire wall and re install on speedometer 5 Connect the cable on the Transducer Assembly to the Console 6 Secure all cables with plastic cable ties You are now ready to calibr...

Page 49: ... calculation Multiply the SPEED CAL by the target distance reading then divide the sum by the actual value in DISTANCE display This will give you the corrected value to enter for SPEED CAL You must round off to the nearest 3 digit whole number EXAMPLE SPEED CAL 612 155 Target distance reading 5280 1000 Assume the actual DISTANCE display reads 5000 980 ENGLISH UNITS METRIC UNITS 612 x 5280 646 3 15...

Page 50: ...and RATE CALS have been entered correctly into the Console In SELF TEST mode enter the normal sprayer operating speed 5 With pump not running fully open main line hand valve fully open by pass 1 hand valve and completely close agitator line hand valve If positive displacement pump is used fully open the pressure relief valve PRV 6 Run pump at normal operating RPM 7 If centrifugal pump is used proc...

Page 51: ... set the desired minimum operating pressure Minimum pressure should be approximately one half the normal spraying pressure EXAMPLE If normal spraying pressure is 30 psi 210 kPa set minimum pressure at approxi mately 15 psi 105 kPa 15 Verify maximum and minimum pressures and RATE by repeating Steps 11 and 14 INITIAL SYSTEM FIELD TEST 1 Drive down field or road at target speed with sprayer booms OFF...

Page 52: ...crease by increments of 1 or more counts 4 If DISTANCE does not increase remove the section of cable and repeat test at connector next closest to Console Replace defective cable as required 5 Perform above voltage checks 6 If all cables test good replace Speed Sensor NOTE Aftertestingiscomplete re entercorrectSPEEDCALnumberbeforeapplication PIN DESIGNATIONS 2 o clock socket location is power 10 o ...

Page 53: ...s of 1 or more counts 5 If TOTAL VOLUME does not increase remove the section of cable and repeat test at connector next closest to Console Replace defective cable as required 6 Perform above voltage checks 7 If all cables test good replace Flow Sensor NOTE After testing is complete re enter correct METER CAL numbers before application PIN DESIGNATIONS 2 o clock socket location is ground 10 o clock...

Page 54: ...ns 378 liters of water 8 To verify Flow Meter calibration fill applicator tank with a predetermined amount of measured liquid i e 250 gallons DO NOT RELY ON GRADUATION NUMBERS MOLDED INTO APPLICATOR TANK Empty the applicator tank under normal operating conditions If the number displayed under PROD 1 VOLUME is different from the predetermined amount of measured liquid by more than 3 complete the fo...

Page 55: ... the Boom On Off Valves to minimize amount of product in tubing 3 Plumb three way valve on output line of Injection Module See Figure 20 Plumb recirculation line from three way valve to Product supply tank using 3 8 inch 10mm tubing Plumb injection line from three way valve to product check valve using 3 8 inch 10 mm tubing For low volume modules or 1 2 inch 13 mm tubing for high volume modules Pr...

Page 56: ...Mixer just ahead of the Boom On Off Valves as shown in Figure 4 2 Mount Injection Modules close to the Boom On Off Valves to minimize amount of product in tubing 3 Plumb output lines of Injection Modules to Product Check Valves See Figure 23 Use 3 8 inch 10 mm tubing on low volume modules and 1 2 inch 13 mm tubing on high volume modules Product Check Valves and tubing not furnished FIGURE 23 ...

Page 57: ...ur corners Reinforce vertical supports with external braces steel angle iron or tubing that are secured to structure of mobile sprayer OPERATION OF SYSTEM WITHOUT EXTERNAL BRACES MAY CAUSE FAILURE OF TANK SUPPORTS 2 See INITIAL INJECTION SET UP before operating system FIGURE 24 ...

Page 58: ...54 APPENDIX 9 INJECTION MODULE MOUNTING INSTRUCTIONS 1 TYPICALMODULEDIAGRAM ...

Page 59: ...pper slot thru the lower slot and back thru the metal loop as shown in Detail A 4 Secure with buckle and safety pin on small strap See Detail B 5 Mount pump module to frame using the 3 8 x 1 bolts lockwashers and flat washers 6 Connect hose from tank to hose barb on pump and secure with two hose clamps Position hose clamps opposite each other for best seal If Strap Assembly parts are desired 7 Att...

Page 60: ...and spin turbine The turbine should spin freely with very little drag inside the turbine hub 5 If transducer assembly is replaced or if turbine stud is adjusted or replaced verify the turbine fit before reassembling Hold turbine hub with turbine on transducer Spin turbine by blowing on it Tighten turbine stub until turbine stalls Loosen turbine stud 1 3 turn The turbine should spin freely 6 Re ass...

Page 61: ...for product under test 6 Place tank return hose into measuring container 7 Place OFF MAN AUTO switch to MAN until 50 ounces of measured product is pumped The number displayed in PROD 2 VOLUME is the new METER 2 CAL 8 Enter this new METER CAL number in METER 2 CAL key 9 Enter 0 in PROD 2 VOLUME key 10 Place OFF MAN AUTO switch to MAN until 50 ounces of measured product is pumped 11 The number in PR...

Page 62: ...58 The REMOTE switch when installed is in parallel with the MASTER switch therefore switching on the REMOTE switch or the MASTER switch will energize the Boom Valves APPENDIX 12 REMOTE SWITCH OPTION ...

Page 63: ... after selecting BOOM CAL increments the boom number EXAMPLE b 01 will increment to b 02 Depressing this key displays selected boom number in PROD 2 display EX AMPLE Boom 1 will display as b 01 APPENDIX 13 BOOM CAL DATA ENTRY FOR SCS 710 6 BOOM CONSOLE ENTERING DATA 1 Select desired boom number 2 Enter boom length as detailed in CALCULATING BOOM CAL ...

Page 64: ...60 APPENDIX 14 SCS 710 6 BOOM CONSOLE WIRING DIAGRAM ...

Page 65: ...00 Baud Rate NO Parity 8 Data Bits 2 Stop Bits b Data stream to Raven Console EXAMPLE Change PROD 1 to 123 4 and PROD 2 to 6 5 R RC 1234 65 CR LF Decimal point is not sent from Remote Computer to Raven Console 3 Optional 9 pin to 9 pin cable pinout P N 115 0159 822 DSR 6 4 CTS 8 DTR 4 6 8 TXD 3 2 RXD 2 3 GND 5 5 Communication string Printer 25 Pin RAVEN CONSOLE 9 PIN Line Feed Carriage Return PROD...

Page 66: ... revision number Calibration Strings R047F C1 switch_byte_1 switch_byte_2 boom_1_cal boom_2_cal boom_3_cal boom_4_cal boom_5_cal boom_6_cal speed_cal CR LF R047F C2 meter_1_cal meter_2_cal CR LF R047F C3 valve_1_cal valve_2_cal prod_1_cal prod_2_cal CR LF Bit Switch Byte 1 Switch Byte 2 0 boom 1 0 1 boom 2 0 2 boom 3 0 3 boom 4 prod 1 auto 4 boom 5 prod 1 manual 5 boom 6 prod 2 auto 6 0 prod 2 man...

Page 67: ...nation on these features see the DATA MENU section of the manual MAIN MENU TITLE SUB MENU TITLE SETTINGS PROD 1 display PROD 2 display DATA display SERIAL PORT MENUS SPr Prn BEGn End FrEF 0 bAUd 1200 9600 rAtE on off triG 0 Unit Ft SEC dLoG on off GLOBAL POSITIONING SYSTEM MENUS GPS FiLE 0 SySE inAC Grid 0 LAt 0 Lon 0 NodE C A n nc TIME AND DATE MENUS dAtE tiNE 0 00 onth 0 dAY 0 YEAr 0 P dn 10 FLO...

Page 68: ...4 11 Product Cable 21 ft 115 0159 562 12 Assorted Terminal Kit 117 0159 402 13 Switch Cover 063 0159 606 14 1 Set Filler Spacers 117 0159 421 15 Face Plate Assembly 063 0159 611 16 Display Board Spacer 107 0159 478 17 LCD Display Board 064 0159 454 18 Processor Board Ser Interface 064 0159 604 19 Connector Plate Assembly Ser Interface 063 0171 346 20 Back Assembly 063 0159 530 21 Boom Cable 21 ft ...

Page 69: ......

Page 70: ......

Page 71: ...e Coverage Period How Can I Get Service What Will Raven Industries Do What is not Covered by this Warranty Bring the defective part and proof of purchase to your Raven Dealer If your Dealer agrees with the warranty claim the Dealer will send the part and proof of purchase to their distributor or to Raven Industries for final approval Upon confirmation of the warranty claim Raven Industries will at...

Page 72: ...Industries Inc All rights reserved under copyright laws SCS 700 Installation Service Manual P N 016 0159 419 Rev S 2 09 Raven Industries Toll Free U S and Canada 800 243 5435 Applied Technology Division or Outside the U S 1 605 575 0722 P O Box 5107 Fax 605 331 0426 Sioux Falls SD 57117 5107 www ravenprecision com atdinfo ravenind com ...

Reviews: