User and maintenance manual for stoves with RDS technology
Pag.11
01/02/2016
6.1.1 Minimum distance from combustible material
Unit of measurement
Roma
A = clearance to mantel
Inch/mm
18,5/470
B= clearance to sidewall
Inch/mm
15/381
C = clearance to face trim (side)
Inch/mm
0/0
D = clearance to face trim (top)
Inch/mm
0/0
E = floor protection
Inch/mm
6/152.4
F = floor protection
Inch/mm
6/152.4
G = clearence to front
Inch/mm
48/1219
I = mantel depth
Inch/mm
6/152.4
J = ceiling from bottom of unit
Inch/mm
72/ 1828.8
K = combustible floor from
bottom of the glass
Inch/mm
9.5/241.3
E
A
D
B
C
F
S
ide wall
S
ide wall
May be made of combustible material
J
I
Wall may be made of combustible material (zero clearance)
Wall may be made of combustible material (zero clearance)
G
B
E
Combustible floor
K
E
A
D
B
C
F
S
ide wall
S
ide wall
May be made of combustible material
J
I
Wall may be made of combustible material (zero clearance)
Wall may be made of combustible material (zero clearance)
G
B
E