background image

7

   Marking to the equipment continues to be visible and legible. Markings and signs that are illegible shall be corrected;

   Refrigeration pipe or components are installed in a position where they are unlikely to be exposed to any substance 

   which may corrode refrigerant containing components, unless the components are constructed of materials which are 

   inherently resistant to being corroded or are suitably protected against being so corroded.

9)Checks to electrical devices

Repair and maintenance to electrical components shall include initial safety checks and component inspection proced-

   ures. If a fault exists that could compromise safety, then no electrical supply shall be connected to the circuit until it is 

   satisfactorily dealt with. If the fault cannot be corrected immediately but it is necessary to continue operation, an adeq-

   uate temporary solution shall be used. This shall be reported to the owner of the equipment so all parties are advised.

   Initial safety checks shall include:

   That capacitors are discharged: this shall be done in a safe manner to avoid possibility of sparking;

   That there no live electrical components and wiring are exposed while charging, recovering or purging the system;

   That there is continuity of earth bonding.

2)Particular attention shall be paid to the following to ensure that by working on electrical components, the casing is not

altered in such a way that the level of protection is affected. This shall include damage to cables, excessive number of

connections, terminals not made to original specification, damage to seals, incorrect fitting of glands, etc.

Ensure that apparatus is mounted securely.

Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose of preventing the ingr-

ess of flammable atmospheres. Replacement parts shall be in accordance with the manufacturer's specifications.

NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. Intrinsically safe

components do not have to be isolated prior to working on them.

    source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the 

    LFL of the refrigerant and shall be calibrated to the refrigerant employed and the appropriate percentage of gas (25 % 

    maximum) is confirmed. Leak detection fluids are suitable for use with most refrigerants but the use of detergents conta-

    ining chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-work. If a leak 

    is suspected, all naked flames shall be removed/ extinguished. If a leakage of refrigerant is found which requires brazing, 

    all of the refrigerant shall be recovered from the system, or isolated (by means of shut off valves) in a part of the system 

    remote from the leak. Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the 

    brazing process.

When breaking into the refrigerant circuit to make repairs or for any other purpose conventional procedures shall be

used. However, it is important that best practice is followed since flammability is a consideration. Opening of the refrig-

    eration systems shall not be done by brazing. The following procedure shall be adhered to:

    Remove refrigerant;

    Purge the circuit with inert gas;

    Evacuate;

    Purge again with inert gas;

    Open the circuit by cutting or brazing.

    The refrigerant charge shall be recovered into the correct recovery cylinders. The system shall be flushed with OFN to 

7.Repairs to sealed components

1)During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon-

prior to any removal of sealed covers, etc. If it is absolutely necessary to have an electrical supply to equipment during se-

   rvicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a poten-

   tially hazardous situation.

8.Repair to intrinsically safe components

Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the

permissible voltage and current permitted for the equipment in use. Intrinsically safe components are the only types that

can be worked on while live in the presence of a flammable atmosphere. The test apparatus shall be at the correct rating.

Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of refrigerant in

the atmosphere from a leak.

9.Cabling

Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse

environmental effects. The check shall also take into account the effects of aging or continual vibration from sources such

as compressors or fans.

10.Detection of flammable refrigerants

Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks.

A halide torch (or any other detector using a naked flame) shall not be used.

11.Leak detection methods

The following leak detection methods are deemed acceptable for systems containing flammable refrigerants. Electronic

leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be adequate, or may need re-

    calibration. (Detection equipment shall be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential 

12.Removal and evacuation

Summary of Contents for RC-S70U

Page 1: ...RC S70U RC S90U RC S120U RC S180U RC S240U...

Page 2: ...Precautions 1 3 4 5 6 7 8 9 10 11 12 13 R32 IEC 60335 2 40 14 0 75 2...

Page 3: ...1 2 3 4 5...

Page 4: ...03 09 10 12 12 13 15 16 2018 12 31...

Page 5: ...3 R32...

Page 6: ...4 3 10mA RCD 30mA 1 2 3 4 5 6 7 1 3 8 9 10 11 PCB 220V...

Page 7: ...5 R32 R32 R32 IEC 60335 2 40 2018 R32...

Page 8: ...6 1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 R32...

Page 9: ...7 7 1 2 8 9 10 11 LFL 25 OFN 12 OFN OFN OFN 13 OFN...

Page 10: ...8 14 a b c d e f g h 80 i j k 15 16...

Page 11: ...9 18 C 43 C 64 F 109 F 17 C 32 C 62 F 90 F 1 2 3 4 5 6 7 8 1 1 9 10 1 2 3 4 5 6 7 8 9 1 2 6 1 RC S70U RC S90U RC S120U RC S180U RC S240U...

Page 12: ...10 RC S180U RC S220U RC S70U RC S90U RC S120U 17 C 30 C 17 C 30 C 1 C 30 C 1 C 17 C RC S70U RC S90U RC S120U RC S180U RC S220U...

Page 13: ...11...

Page 14: ...12 A B 1 2 3 4 50 C 122 F 1 2 A B 3 40 C 104 F 4 5 6 90...

Page 15: ...1 3 4 2 3 3 4...

Page 16: ...6 10 11 5 5 6 7 14 8 9 1 5 2 6 1 2 A B 5 7 3 7 1 8 2 3 7 1 9 2 10 8 1 2 2 11 3 4 4...

Page 17: ...15 a b c d e f 1 a b 2 PVC c 3 d e RC S180U RC S240U 4 6 7 3 2 MED HIGH...

Page 18: ...RC S70U RC S90U 450 6x350x675 RC S120U RC S180U 660x428x780 RC S240U 16...

Page 19: ...1 0 2 0 0 3 28612767 0 0 2406 5666 o o 0...

Page 20: ...W TERRITORIES HONG KONG TEL 852 2406 5666 FAX 852 2408 0316 WEBSITE www shesc com CONSUMABLES ACCESSORIES SALES HOTLINE TEL 852 2406 5666 CUSTOM SERVICE CENTRES 2 1 1ST FLOOR SHUN HING CENTRE 2 SHING...

Page 21: ...mmable refrigerant Read this manual carefully before installing or operating Make sure to save this manual for future reference Please check the applicable models technical data from the nameplate pas...

Page 22: ...ed personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants 5 Do not use means to accelerate the defrosting process or to clean other than thos...

Page 23: ...it 1 Transport of equipment containing flammable refrigerants Compliance with the transport regulations 2 Marking of equipment using signs Compliance with local regulations 3 Disposal of equipment usi...

Page 24: ...reprocessing or recycling of abandoned REE must obtain a waste disposal licence a permit is required for the import and export of abandoned REE and abandoned REE is no longer be accepted for disposal...

Page 25: ...upervised around the unit at all times operate your air conditioner in a wet room such as a bathroom or laundry room Too much exposure to water can cause electrical components to short circuit In cert...

Page 26: ...arth wire The unit should be provided with an individual circuit and the circuit breaker fuse rating should be the same as that of the power cord and wall outlet Power cord conductors are distinguishe...

Page 27: ...t authority which authorises their competence to handle refrigerants safely in acc ordance with an industry recognised assessment specification Servicing shall only be performed as recommended by the...

Page 28: ...Ventilated area Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work A degree of ventilation shall continue during the per...

Page 29: ...ed If a leakage of refrigerant is found which requires brazing all of the refrigerant shall be recovered from the system or isolated by means of shut off valves in a part of the system remote from the...

Page 30: ...d in them Cylinders shall be kept upright Ensure that the refrigeration system is earthed prior to charging the system with refrigerant Label the system when charging is complete if not already Extrem...

Page 31: ...n the surroundings is comparatively low at night If your feel that the noise is too loud switch the thermostat to lower numbers UNIT PARTS IDENTIFICATION NOTE Different models have different front pan...

Page 32: ...he vent It will allow internal air circulation OPEN the vent to discharge stale air OPERATING INSTRUCTIONS RC S70U RC S90U RC S120U RC S180U RC S220U TEMP Sleep Timeron Timeroff TEMP CLOSE VENT OPEN C...

Page 33: ...crease the set operating temperature of the unit Each time the keypad is pressed the temperature increases as follows 1 Celsius Scale Maximum Setting 30 TEMPERATURE SETTINGS DOWN Press the keypad to d...

Page 34: ...RC S120U only Press the ECO button by remote controller on COOL mode to enter the energy efficient mode LED Display Shows Error codes inverter type E0 Indoor EEPROM error E1 Communicaiton error betwe...

Page 35: ...stall it at the postion as you like Clean it with a hand held vacuum Model B 1 2 3 4 WATER DRAINAGE ALWAYS TURN OFF YOUR AIR CONDITIONER SYSTEM AND DISCONNECT ITS POWER SUPPLY BEFORE CLEANING OR MAINT...

Page 36: ...at water will not leak from the surrounding area when rubber plug and joint were used Please seal it in case leakage is found Rubber plug Drain pan Drain outlet Screw Rubber plug Back drain hole Drain...

Page 37: ...e such as a fence or wall within 50cm from the back of the cabinet because it will prevent heat radiation of the condenser Restriction of outside air will greatly reduce the cooling efficiency of the...

Page 38: ...the cabinet remain in position See Fig 8 2 Connect the air conditioner to the power and position excess cord length beneath the air conditioner base 3 Engage the chassis fixing brackets into the botto...

Page 39: ...it the drain pan to the cabinet and run a drain hose to a suitable location if required Fig 11 17 NOTE For the unit with power cord comes out from left side please perform the following steps 1 Pull t...

Page 40: ...the air conditioner plug is pushed completely into the outlet and switched on Check the house fuse circuit breaker box and replace the fuse or reset the breaker If power failure occurs switch off and...

Page 41: ...y SPECIFICATIONS The size of the power supply cable signal cable fuse and switch needed is determined by the maximum current of the unit The maximum current is indicated on the nameplate located on th...

Page 42: ...pecifications are subject to change without prior notice for product improvement Consult with the sales agency for details Any updates to the manual will be uploaded to the website please check for th...

Page 43: ......

Page 44: ...W TERRITORIES HONG KONG TEL 852 2406 5666 FAX 852 2408 0316 WEBSITE www shesc com CONSUMABLES ACCESSORIES SALES HOTLINE TEL 852 2406 5666 CUSTOM SERVICE CENTRES 2 1 1ST FLOOR SHUN HING CENTRE 2 SHING...

Reviews: