background image

8

    render the unit safe. This process may need to be repeated several times. Compressed air or oxygen shall not be used for 

    this task.

    Flushing shall be achieved by breaking the vacuum in the system with OFN and continuing to fill until the working press-

    ure is achieved, then venting to atmosphere, and finally pulling down to a vacuum. This process shall be repeated until 

    no refrigerant is within the system. 

    When the final OFN charge is used, the system shall be vented down to atmospheric pressure to enable work to take 

    place. This operation is absolutely vital if brazing operations on the pipe-work are to take place.

    Ensure that the outlet for the vacuum pump is not close to any ignition sources and there is ventilation available.

able. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant (i.e. special

cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off

valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.

The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at

hand and shall be suitable for the recovery of flammable refrigerants.In addition, a set of calibrated weighing scales shall

be available and in good working order. Hoses shall be complete with leak-free disconnect couplings and in good cond-

   ition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and 

   that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult 

   manufacturer if in doubt.

   The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant 

   Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders. If compressors or 

   compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that 

   flammable refrigerant does not remain within the lubricant. The evacuation process shall be carried out prior to returning 

   the compressor to the suppliers. Only electric heating to the compressor body shall be employed to accelerate this process. 

   When oil is drained from a system, it shall be carried out safely. 

13.Charging procedures

In addition to conventional charging procedures, the following requirements shall be followed. Ensure that contamination

of different refrigerants does not occur when using charging equipment. Hoses or lines shall be as short as possible to

minimise the amount of refrigerant contained in them.

Cylinders shall be kept upright.

Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.

Label the system when charging is complete (if not already).

Extreme care shall be taken not to overfill the refrigeration system.

Prior to recharging the system it shall be pressure tested with OFN. The system shall be leak tested on completion of

charging but prior to commissioning. A follow up leak test shall be carried out prior to leaving the site.

14.Decommissioning

Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its

detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an

oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant. It is essential

that electrical power is available before the task is commenced.

a)Become familiar with the equipment and its operation.

b)Isolate system electrically.

c)Before attempting the procedure ensure that:

Mechanical handling equipment is available, if required, for handling refrigerant cylinders;

All personal protective equipment is available and being used correctly;

The recovery process is supervised at all times by a competent person;

Recovery equipment and cylinders conform to the appropriate standards.

d)Pump down refrigerant system, if possible.

e)If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.

f)Make sure that cylinder is situated on the scales before recovery takes place.

g)Start the recovery machine and operate in accordance with manufacturer's instructions.

h)Do not overfill cylinders. (No more than 80 % volume liquid charge).

i)Do not exceed the maximum working pressure of the cylinder, even temporarily.

j)When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment

are removed from site promptly and all isolation valves on the equipment are closed off.

k)Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.

15.Labelling

Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated

and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.

16.Recovery

When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that

all refrigerants are removed safely.When transferring refrigerant into cylinders, ensure that only appropriate refrigerant

recovery cylinders are employed. Ensure that the correct number of cylinders for holding the total system charge is avail-

When flammable refrigerant are employed, appliance shall be stored in a well-ventilated area. 

Summary of Contents for RC-S70U

Page 1: ...RC S70U RC S90U RC S120U RC S180U RC S240U...

Page 2: ...Precautions 1 3 4 5 6 7 8 9 10 11 12 13 R32 IEC 60335 2 40 14 0 75 2...

Page 3: ...1 2 3 4 5...

Page 4: ...03 09 10 12 12 13 15 16 2018 12 31...

Page 5: ...3 R32...

Page 6: ...4 3 10mA RCD 30mA 1 2 3 4 5 6 7 1 3 8 9 10 11 PCB 220V...

Page 7: ...5 R32 R32 R32 IEC 60335 2 40 2018 R32...

Page 8: ...6 1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 R32...

Page 9: ...7 7 1 2 8 9 10 11 LFL 25 OFN 12 OFN OFN OFN 13 OFN...

Page 10: ...8 14 a b c d e f g h 80 i j k 15 16...

Page 11: ...9 18 C 43 C 64 F 109 F 17 C 32 C 62 F 90 F 1 2 3 4 5 6 7 8 1 1 9 10 1 2 3 4 5 6 7 8 9 1 2 6 1 RC S70U RC S90U RC S120U RC S180U RC S240U...

Page 12: ...10 RC S180U RC S220U RC S70U RC S90U RC S120U 17 C 30 C 17 C 30 C 1 C 30 C 1 C 17 C RC S70U RC S90U RC S120U RC S180U RC S220U...

Page 13: ...11...

Page 14: ...12 A B 1 2 3 4 50 C 122 F 1 2 A B 3 40 C 104 F 4 5 6 90...

Page 15: ...1 3 4 2 3 3 4...

Page 16: ...6 10 11 5 5 6 7 14 8 9 1 5 2 6 1 2 A B 5 7 3 7 1 8 2 3 7 1 9 2 10 8 1 2 2 11 3 4 4...

Page 17: ...15 a b c d e f 1 a b 2 PVC c 3 d e RC S180U RC S240U 4 6 7 3 2 MED HIGH...

Page 18: ...RC S70U RC S90U 450 6x350x675 RC S120U RC S180U 660x428x780 RC S240U 16...

Page 19: ...1 0 2 0 0 3 28612767 0 0 2406 5666 o o 0...

Page 20: ...W TERRITORIES HONG KONG TEL 852 2406 5666 FAX 852 2408 0316 WEBSITE www shesc com CONSUMABLES ACCESSORIES SALES HOTLINE TEL 852 2406 5666 CUSTOM SERVICE CENTRES 2 1 1ST FLOOR SHUN HING CENTRE 2 SHING...

Page 21: ...mmable refrigerant Read this manual carefully before installing or operating Make sure to save this manual for future reference Please check the applicable models technical data from the nameplate pas...

Page 22: ...ed personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants 5 Do not use means to accelerate the defrosting process or to clean other than thos...

Page 23: ...it 1 Transport of equipment containing flammable refrigerants Compliance with the transport regulations 2 Marking of equipment using signs Compliance with local regulations 3 Disposal of equipment usi...

Page 24: ...reprocessing or recycling of abandoned REE must obtain a waste disposal licence a permit is required for the import and export of abandoned REE and abandoned REE is no longer be accepted for disposal...

Page 25: ...upervised around the unit at all times operate your air conditioner in a wet room such as a bathroom or laundry room Too much exposure to water can cause electrical components to short circuit In cert...

Page 26: ...arth wire The unit should be provided with an individual circuit and the circuit breaker fuse rating should be the same as that of the power cord and wall outlet Power cord conductors are distinguishe...

Page 27: ...t authority which authorises their competence to handle refrigerants safely in acc ordance with an industry recognised assessment specification Servicing shall only be performed as recommended by the...

Page 28: ...Ventilated area Ensure that the area is in the open or that it is adequately ventilated before breaking into the system or conducting any hot work A degree of ventilation shall continue during the per...

Page 29: ...ed If a leakage of refrigerant is found which requires brazing all of the refrigerant shall be recovered from the system or isolated by means of shut off valves in a part of the system remote from the...

Page 30: ...d in them Cylinders shall be kept upright Ensure that the refrigeration system is earthed prior to charging the system with refrigerant Label the system when charging is complete if not already Extrem...

Page 31: ...n the surroundings is comparatively low at night If your feel that the noise is too loud switch the thermostat to lower numbers UNIT PARTS IDENTIFICATION NOTE Different models have different front pan...

Page 32: ...he vent It will allow internal air circulation OPEN the vent to discharge stale air OPERATING INSTRUCTIONS RC S70U RC S90U RC S120U RC S180U RC S220U TEMP Sleep Timeron Timeroff TEMP CLOSE VENT OPEN C...

Page 33: ...crease the set operating temperature of the unit Each time the keypad is pressed the temperature increases as follows 1 Celsius Scale Maximum Setting 30 TEMPERATURE SETTINGS DOWN Press the keypad to d...

Page 34: ...RC S120U only Press the ECO button by remote controller on COOL mode to enter the energy efficient mode LED Display Shows Error codes inverter type E0 Indoor EEPROM error E1 Communicaiton error betwe...

Page 35: ...stall it at the postion as you like Clean it with a hand held vacuum Model B 1 2 3 4 WATER DRAINAGE ALWAYS TURN OFF YOUR AIR CONDITIONER SYSTEM AND DISCONNECT ITS POWER SUPPLY BEFORE CLEANING OR MAINT...

Page 36: ...at water will not leak from the surrounding area when rubber plug and joint were used Please seal it in case leakage is found Rubber plug Drain pan Drain outlet Screw Rubber plug Back drain hole Drain...

Page 37: ...e such as a fence or wall within 50cm from the back of the cabinet because it will prevent heat radiation of the condenser Restriction of outside air will greatly reduce the cooling efficiency of the...

Page 38: ...the cabinet remain in position See Fig 8 2 Connect the air conditioner to the power and position excess cord length beneath the air conditioner base 3 Engage the chassis fixing brackets into the botto...

Page 39: ...it the drain pan to the cabinet and run a drain hose to a suitable location if required Fig 11 17 NOTE For the unit with power cord comes out from left side please perform the following steps 1 Pull t...

Page 40: ...the air conditioner plug is pushed completely into the outlet and switched on Check the house fuse circuit breaker box and replace the fuse or reset the breaker If power failure occurs switch off and...

Page 41: ...y SPECIFICATIONS The size of the power supply cable signal cable fuse and switch needed is determined by the maximum current of the unit The maximum current is indicated on the nameplate located on th...

Page 42: ...pecifications are subject to change without prior notice for product improvement Consult with the sales agency for details Any updates to the manual will be uploaded to the website please check for th...

Page 43: ......

Page 44: ...W TERRITORIES HONG KONG TEL 852 2406 5666 FAX 852 2408 0316 WEBSITE www shesc com CONSUMABLES ACCESSORIES SALES HOTLINE TEL 852 2406 5666 CUSTOM SERVICE CENTRES 2 1 1ST FLOOR SHUN HING CENTRE 2 SHING...

Reviews: