For Raritan's DPX water sensors, the Normal state must be
Normally Open, which indicates there is no water detected. Set the
dip switch to Normally Open and verify that the LED of the channel
where the Raritan's water sensor is connected remains OFF.
5.
To set the Normal state for channel 2, repeat Step 4 for adjusting the
other dip switch's setting.
6.
Install back the dip switch cover.
Note: The dip switch setting must be properly configured, or the sensor's
LED may be incorrectly lit in the Normal state.
Contact Closure Sensor LEDs
LEDs indicate states of detectors/switches connected to the contact
closure sensor channels.
The LED is lit when the associated detector/switch enters the "alarmed"
state. For information on how to set the Normal state of DPX-CC2-TR,
see
Configuring a DPX Contact Closure Sensor
(on page 61).
The meaning of a lit LED depends on the Normal state settings. See
DX2-CC2 Contact Closure Sensor LEDs
(on page 16).
Proper LED behaviors of DPX water sensors:
For Raritan's DPX water sensors, the Normal state must be set to
Normally Open (N.O).
The following is the correct LED behavior based on proper dip switch
settings.
LED
Sensor state
Off No
water
detected
Lit Water
detected