Chapter 8: Inline Monitors
193
The cord is made from stranded copper wire. (Use of aluminum
wire is NOT permitted.)
The inner diameter of each ring terminal on each wire is 5.3 mm.
The cord diameter matches the cable gland's diameter.
Model
Cable gland
diameter
Single-phase models
11-17mm
Y-wired three-phase
models
15-21mm
The cord's electrical capacity is equal to or larger than the inlet's
rating. See the table.
Model
Inlet/outlet rating
PX-3420 32A,
100-240V
PX-3220 32A,
100-240V
PX-3410 16A,
100-240V
PX-3210 16A,
100-240V
PX-3370 32A,
100-415V
PX-3270 32A,
100-415V
For other models, see the label or nameplate affixed to the PDU
for appropriate ratings or range of ratings.
Note: A maximum cable length of 4.5 m (15 feet) is permitted by UL
code. A qualified electrician can verify the maximum cable length in
your non-UL regions to meet national and local electrical codes.
Minimum cable length is 1 m (39.3 inches).
4. (Optional) For some inline monitors, the diameter of appropriate
power cords may be smaller than the cable gland's inner diameter. If
so, do the following to reduce the inner diameter:
a. Remove the dome nut from the cable gland.
b. Insert the Raritan-provided sealing ring into the one already
seated inside the cable gland so that the inner diameter becomes
smaller.
c. Install back the dome nut and slightly tighten it by turning it
clockwise.