background image

 

Dominion PX Quick Setup Guide 

2

QSG-DPX-0F-E 

y

 255-80-6081-00 

 

software has finished loading, the outlet LEDs display a 
solid color and the meter illuminates. 

 

QS Rule 

 

Connect the Dominion PX to a Computer 

1.  Connect the RJ-45 end of the null modem cable to the port 

labeled Serial on the front of the Dominion PX.  

2.  Connect the DB9 end of the null modem cable to the serial 

port (COM) of the computer. 

 

QS Rule 

 

Connect the Dominion PX to Your Network 

1.  Connect a standard Cat 5e UTP cable to the LAN port on 

the front of the Dominion PX. 

2.  Connect the other end of the cable to your LAN. 

 

QS Rule 

 

Configure the Dominion PX 

1.  Go to the computer that you connected to the Dominion 

PX and open a terminal emulation program such as 
HyperTerminal or PuTTY. Make sure the port settings are 
configured as follows: 

ƒ

  Bits per second = 9600 

ƒ

  Data bits = 8 

ƒ

  Stop bits = 1 

ƒ

  Parity = None 

ƒ

  Flow control = None 

2.  Point the communications program at the serial port 

connecting the unit and open a window. 

3. Press 

Enter

. The opening configuration prompt appears. 

4. Type 

config 

and press 

Enter

. You are now prompted to 

enter several networking parameters. 

 

IP address

 

The default IP address is: 192.168.0.192. To 
assign the Dominion PX an IP address, 
Choose either: 

Auto configuration:

 

Select 

dhcp

 or 

bootp

 and let the DHCP or BOOTP server 

provide the IP address. 
Static IP address:

 

Select 

None

 and when 

prompted, enter a an IP address, network 
mask and gateway. 

IP access 
control

 

Leave this disabled for now. This disables 
the Dominion PX's firewall. You can enable 
the firewall and create access control rules 
after the initial installation and configuration. 

LAN 
interface 
speed

 

Leave the default 

Auto

, or select 

10

 or 

100

 

Mbps. 

LAN 
interface 
duplex 
mode

 

Leave the default

 Auto

, or select 

half

 or 

full

 

5.  Once you have entered the network parameters, the 

values you entered are shown, and you are asked if they 
are correct. If any are incorrect, type n, press Enter, and 
go back and change them. When they are correct, type

 y

 

and press 

Enter

.  

Note: 

The default IP address is 192.168.0.192. The default IP 

configuration method is DHCP, and the default IP address will 
be replaced by the address assigned by DHCP or BOOTP, or 
the static IP address you entered, as soon as the 
configuration process is complete. To use the factory default 
IP address, please type in “none” as the IP autoconfiguration 
command. 

Congratulations! Installation and configuration are complete.  

 

QS Rule 

 

What to do Next 

1.  Connect devices to the outlets on the Dominion PX. 
2.  From a computer connected to your LAN, open a browser 

and point it at the IP address of the Dominion PX. 

3. Enter 

admin 

and 

raritan

 (lowercase) when prompted for a 

username and password. 

4.  You will be prompted to change the admin password. 

Once this is done, the Dominion PX Home page appears. 

5.  Dominion PX is sent from the factory with all the outlets 

ON

. Turn OFF the outlets without devices connected from 

the Home Page if you wish. 

6.  Under Device Settings, configure PX with the proper date 

and time or synchronize it with an NTP server. Dominion 
PX's time must be in sync with the LDAP server to use 
LDAP authentication. 

7.  Use the menu across the top of the page to create user 

profiles and groups, set up security, and configure outlet 
thresholds. 

Note: Detailed instructions are available in the Dominion PX 
User Guide. 

 

QS Rule 

 

Safety and Installation Information 

Notice 

This instruction should be used in conjunction with the 
Dominion PX User Guide. 

This product must be installed by suitably qualified personnel 
in accordance with the requirements of relevant legislation 
and regulations for the region (e.g. the National Electric Code 
in the USA, the Canadian Electric Code in Canada, the IEE 