background image

 

Dominion PX Quick Setup Guide 

3

QSG-DPX-0F-E 

y

 255-80-6081-00 

 

Testing 

All PDU's are fully tested and verified to conform to the 
required standards. Where further system wiring is carried 
out, or where the modules are integrated into larger systems, 
the entire installation must be tested prior to use as prescribed 
by national wiring regulations. 

For compliance with certain standards, the installer must test 
the complete electrical installation prior to use, and, in general 
use, the products should be subject to regular checking. The 
frequency of the electrical and visual checks will depend on 
the nature of the use to which the PDU is put and as such the 
test frequency must be determined by the installer. Guidelines 
for normal tests are given below. 

 

Earth Continuity 

A current of 25 amps should be passed from an alternating 
current (AC) source with a no-load voltage not exceeding 12V, 
between the earth conductor of the power supply cord and the 
earth connection of the outlet sockets. This test should be 
repeated for metal parts surrounding the installation, which 
should be earthed. 

Where the power cord specified exceeds 3M the 100m

 limit 

common on many PAT testers may be exceeded. This does 
not mean the product has failed. The length of the cord should 
be checked and the appropriate allowance made. 

 

Conductor Continuity and Polarity 

The system should be checked to ensure correct polarity and 
continuity of all wiring. 

 

Insulation Resistance 

The insulation resistance between LINE/NEUTRAL and 
EARTH should be measured using a 500VDC. test supply. 
The measured resistance should not be less than 1.0M

 

Flash Test 

A flash voltage of 1500VAC between LINE/NEUTRAL and 
EARTH should exhibit a leakage of under 1mA. Note: where 
the power cord exceeds 3M, the unit may exhibit higher 
leakage. The appropriate allowance should be made. 

Both insulation and flash testing may ONLY be carried out LN-
E. Testing between L-N may give erroneous results due to the 
Neon indicator (if fitted). 

 

Notes on units with integral filters 

Units with integral filter systems may be LN-E insulation 
tested at 500VDC but if flash tested at 1500VAC, they will 
exhibit high leakage readings under insulation tests due to the 
nature of the filtering components. 

The quiescent earth leakage of the filter unit under normal 
conditions may be checked and should not exceed 0.9mA at 
250V~ 50Hz. 

L to N flash and insulation tests would be inconclusive due to 
the presence of the filter system and may damage the surge 
suppression circuitry. 

 

Uses 

This system has been designed to conform to the latest safety 
requirements. In addition to compliance with standards for 
general use, this PDU has been factory configured for use in 
19” rack mounting environments. This does NOT preclude 
their use in other situations. 

 

Safety Precations 

Ensure all equipment is unplugged before carrying out any 
testing. 

Testing of this nature should only be carried out by suitably 
qualified individuals. 

CAUTION: USE ONLY IN DRY LOCATIONS / ATTENTION: 
UTILISER UNIQUEMENT DANS DES EMPLACEMENTS 
SECS 

THE INFORMATION GIVEN IN THIS LEAFLET IS SUBJECT 
TO CHANGE WITHOUT NOTICE. ANY GUIDANCE NOTES 
ARE GIVEN WITH REGARDS TO COMPLYING WITH 
SPECIFIC STANDARDS ARE PROVIDED AS AN AID TO 
THE INSTALLER AND ARE INTERPRETATIONS OF THOSE 
STANDARDS ONLY. 

THESE INSTRUCTIONS ARE PRIMARILY INTENDED TO 
PROVIDE DETAILS ON THE SAFE USE AND 
INSTALLATION OF THE ABOVE MAINS DISTRIBUTION 
SYSTEM. 

NOTICE: FOR PLUGGABLE EQUIPMENT, THE SOCKET 
OUTLET SHALL BE INSTALLED NEAR THE EQUIPMENT 
AND SHALL BE EASILY ACCESSIBLE. THE PRODUCT 
MUST BE INSTALLED BY A QUALIFIED ELECTRICIAN IN 
ACCORDANCE WITH NATIONAL AND LOCAL 
ELECTRICAL CODES. 

 