RAPA L-WB1 Original User Manual Download Page 13

13 

 

 

 

 
Description of the main signals and alarms 
 

LED flashing

 

 

The activation of the corresponding function is delayed by a timer 

 

awaiting an external signal or disabled by another procedure that is 

already in progress. e.g. if is a continuous cycle in progress and a defrost is called, 
the latter will remain pending until the end of the continuous cycle, and the 
corresponding LED (defrost) will flash. 

 

OFF flashing – state of the controller - OFF, to return to working mode (ON) 
press and hold ON/OFF button for more than 3 sec. 

E0 steady

 

– control probe error (1) – active sound signal: 

 

probe not working: the probe signal is interrupted or short-circuited; 

 

probe not compatible with the instrument. 

The E0 alarm signal is constant when it is the only active alarm (the temperature 
value is not displayed). 

E0 flashing

 

– control probe error (1) – the alarm signal E0 is steady if it is the only 

active alarm (the temperature value is not displayed), while it flashes if other alarms 
are active or the second probe is displayed.

 

E1 flashing

 

– evaporator probe error (2): 

 

probe not working, the probe signal is interrupted or short-circuited; 

 

probe not compatible with the instrument. 

Ed flashing

 

– The last defrost ended after exceeding the maximum duration rather 

than when reaching the end defrost set point. The message disappears when the 
next defrost ends correctly. 

EF displayed during operation or on power-up

 

– operating parameter reading 

error (controller automatic reset). Alarm reappearance after automatic reset – it is 
necessary to check the controller as there is no guarantee to keep the original 
precision of the operation. 

EE 

 data errors 

– In certain operating conditions, the instrument may detect errors 

in the data saved. These errors may compromise the correct operation of the 
instrument. If the microprocessor detects a data saving error, the display shows the 
message 

“EE”.

 If the fault persists, the controller needs to be replaced. If, on the 

other hand, the message disappears, it can continue to be used. When 

“EE” 

error 

occurs frequently and/or remains for some time, the controller should be checked, 
as the original precision may not be guaranteed.

 

LO flashing

 

 low temperature alarm. The probe has measured a temperature 

lower than the set point by a value that exceeds parameter AL: 

 

check parameters AL, Ad and A0. 

The alarm is automatically reset when the temperature returns within the set limits  
(see parameter AL). 

HI flashing

 

– high temperature alarm. The probe has measured a temperature 

higher than the set point by a value that exceeds parameter AH. 

 

check parameters AH, Ad and A0.

 

 

Summary of Contents for L-WB1

Page 1: ...1 TRANSLATED FROM ORIGINAL USER MANUAL MODULAR REFRIGERATED ISLAND L WB1 03 2021 EN...

Page 2: ...Product characteristics 5 3 Cooling system diagram 5 4 Wiring system 5 5 Wiring system diagram 6 6 Drawings 7 7 Positioning start up and operation 9 8 Maintenance 9 9 Transport and equipment 10 10 Tem...

Page 3: ...NG 1 Incorrect connecting of the device to the mains may result in an electric shock 2 In the event of sparks or breakdowns immediately disconnect the device from the power supply by pulling the plug...

Page 4: ...ated counter WB1 device model 141 127 device dimensions see table p 2 Important information on the rating label of each device In the case of contact with the service department prepare the following...

Page 5: ...ice 4 The device should be connected to a separate properly made electrical circuit protected by a fuse no greater than 10 A with a B characteristic ended with a socket with a protective pin 5 The dev...

Page 6: ...DIAGRAM SPR compressor MS condenser fan MN evaporator fan REG electronic temperature regulator CRT electronic temperature regulator sensor CKO defrost ending sensor WA aggregate switch PE protective c...

Page 7: ...7 Pic 1 6 DRAWINGS Pic 2 aggregate switch condenser evaporator compressor defrost water collection container fan loading limit air jet direction protective bumper power socket...

Page 8: ...8 Pic 3 exposure angle adjustment screw exposure angle adjustment screw...

Page 9: ...INTENANCE After disconnecting the device from power supply the general maintenance should be done by the user as follows 1 washing with water of the temperature not more than 40 C with addition of nat...

Page 10: ...flashes when the compressor s start up is delayed because of protective procedure It flashes in the cycle two flashes break when there is continuous operation mode activated 2 FAN The symbol is visibl...

Page 11: ...ng power supply of the controller on will cause return to the parameters fabric settings there will be shown CF symbol on the display In the parameters setting mode its pressing changes the informatio...

Page 12: ...parameter setting increase or decrease setting value by means of the UP and DOWN switches press the SET switch to temporarily save the entered new value it will cause as well return to the parameters...

Page 13: ...ended after exceeding the maximum duration rather than when reaching the end defrost set point The message disappears when the next defrost ends correctly EF displayed during operation or on power up...

Page 14: ...bove the storage temperature Too high ambient temperature hot air coming out of the aggregate chamber loud operation of the aggregate characteristic clicking coming out of the aggregate chamber every...

Page 15: ...ellants 3 The device is using natural and ecological refrigerant R 290 propane Warning In case of damage of the cooling system the refrigerator should be immediately disconnected from the mains any op...

Page 16: ...eramiczna Street BDO 000009031 tel 48 81 718 46 50 51 e mail rapa rapa lublin pl www rapapoland com The package should be removed according to the regulations of environmental protection The warranty...

Reviews: