background image

12 

 

 

Manual defrost

 

In order to activate the manual defrost press the 

“DOWN” 

switch for more than  

3 sec. The essential condition is the temperature has to be lower than +6°C. 

Temperature checking on the defrost probe 

 

press the “SET” switch for longer than 3 sec. (in case there is the alarm is 
activated it is necessary to switch the sound alarm off first). On the display there 
will appear “PS” symbol (password); 

 

 go to the “d/” parameter be means of the “UP” and/or “DOWN” switches, then 
press the “SET” switch - there will appear temperature of defrost probe and the  
symbol      or  

 

hold the “SET” switch  for longer than 3 sec. (after 60 sec. automatic return) – 
return to the temperature probe indication. 

Access for operator to parameters configuration and its modification 
 

 

press the „SET” switch for longer than 3 sec. (in case there is alarm activated, 
switch the sound alarm first). On the display will appear the „PS” symbol (service 
parameter password protected); 

 

go to the next parameters by means of the “UP” and/or “DOWN” switches; 

 

press the “SET” switch to view the current value of parameter setting; 

 

increase or decrease setting value by means of the “UP” and “DOWN” switches; 

 

press the “SET” switch to temporarily save the entered new value – it will cause 
as well return to the parameters list;  

 

repeat the above operations – if it is necessary; 

 

press and hold the “SET” switch for longer than 3 sec. – it will cause parameters 
saving and exit from the programming procedure. 

 

Warning:

 

If no button is pressed for 60 sec., all the changes made to the parameters, 
temporarily saved in the RAM, will be cancelled and the previous settings restored. 
If power is disconnected from the instrument before saving the settings (pressing 
the “SET” switch for 3 sec.), all the changes made to the parameters and 
temporarily saved will be lost.

 

 
 
 
 
 
 
 

 

 

 

 

 

 

 

Symbol

 

Parameter

 

Unit

 

Fabric setting

 

min.

 

max.

 

d8 

Alarm bypass time after defrost 

15 

A0 

Alarm and fan temperature differential 

°C 

20 

AL 

Absolute or relative temperature for low temperature alarm 

°C 

150 

AH 

Absolute or relative temperature for high temperature alarm 

°C 

150 

Ad 

Temperature alarm delay 

min 

60 

199 

High temperature alarm activation = s AH 
High temperature alarm deactivation. = s AH – A0  

Low temperature alarm activation = setting – AL 
Low temperature alarm deactivation. = setting – AL + A0 

Summary of Contents for L-WB1

Page 1: ...1 TRANSLATED FROM ORIGINAL USER MANUAL MODULAR REFRIGERATED ISLAND L WB1 03 2021 EN...

Page 2: ...Product characteristics 5 3 Cooling system diagram 5 4 Wiring system 5 5 Wiring system diagram 6 6 Drawings 7 7 Positioning start up and operation 9 8 Maintenance 9 9 Transport and equipment 10 10 Tem...

Page 3: ...NG 1 Incorrect connecting of the device to the mains may result in an electric shock 2 In the event of sparks or breakdowns immediately disconnect the device from the power supply by pulling the plug...

Page 4: ...ated counter WB1 device model 141 127 device dimensions see table p 2 Important information on the rating label of each device In the case of contact with the service department prepare the following...

Page 5: ...ice 4 The device should be connected to a separate properly made electrical circuit protected by a fuse no greater than 10 A with a B characteristic ended with a socket with a protective pin 5 The dev...

Page 6: ...DIAGRAM SPR compressor MS condenser fan MN evaporator fan REG electronic temperature regulator CRT electronic temperature regulator sensor CKO defrost ending sensor WA aggregate switch PE protective c...

Page 7: ...7 Pic 1 6 DRAWINGS Pic 2 aggregate switch condenser evaporator compressor defrost water collection container fan loading limit air jet direction protective bumper power socket...

Page 8: ...8 Pic 3 exposure angle adjustment screw exposure angle adjustment screw...

Page 9: ...INTENANCE After disconnecting the device from power supply the general maintenance should be done by the user as follows 1 washing with water of the temperature not more than 40 C with addition of nat...

Page 10: ...flashes when the compressor s start up is delayed because of protective procedure It flashes in the cycle two flashes break when there is continuous operation mode activated 2 FAN The symbol is visibl...

Page 11: ...ng power supply of the controller on will cause return to the parameters fabric settings there will be shown CF symbol on the display In the parameters setting mode its pressing changes the informatio...

Page 12: ...parameter setting increase or decrease setting value by means of the UP and DOWN switches press the SET switch to temporarily save the entered new value it will cause as well return to the parameters...

Page 13: ...ended after exceeding the maximum duration rather than when reaching the end defrost set point The message disappears when the next defrost ends correctly EF displayed during operation or on power up...

Page 14: ...bove the storage temperature Too high ambient temperature hot air coming out of the aggregate chamber loud operation of the aggregate characteristic clicking coming out of the aggregate chamber every...

Page 15: ...ellants 3 The device is using natural and ecological refrigerant R 290 propane Warning In case of damage of the cooling system the refrigerator should be immediately disconnected from the mains any op...

Page 16: ...eramiczna Street BDO 000009031 tel 48 81 718 46 50 51 e mail rapa rapa lublin pl www rapapoland com The package should be removed according to the regulations of environmental protection The warranty...

Reviews:

Related manuals for L-WB1