21
RAM 100 • 1000 • 5500
RAMSET
www.ramsetinc.com
JP2 - Relay Connections:
1)
24 VDC.
5)
Relay Common
2)
24 VAC
6)
Fully Closed-N.C.
3)
Do Not Use
7-8)
Constant Warn/Prewarn - N.O.
4)
Fully Open - N.O.
9-10)
ERD Alarm (factory wired)
All Relays are rated at 125VAC, 1A.
Used with:
Lights or Sirens that show the gate is open.
•
Constant Warn/Prewarn lights or sirens.
•
Alarm that sounds when an obstruction is sensed twice in a
single travel.
See “WIRING DIAGRAMS”
PLUG CONNECTIONS
WIRING DIAGRAMS
JP9 - Input Power:
1) Common 2)
18 VAC
Connection from external transformer to power
Control Board.
JP3 - 3 Button:
1)
OP (open) - Normally open connection
2)
ST (stop) - Normally closed connection
3)
CL (close) - Normally open connection
4)
COM - (common)
Used with:
•
A 3-button station.
•
An anti-entrapment device where the gate should stop
and remained stopped.
To use the ST (stop) function, S7 - #1 must be
in the ‘OFF’ position.
JP7 - Primary/Secondary:
1)
A
2)
B
3)
C
Synchronizes the operation between two gates.
Three wire, shielded cable needed.
Align A to A, B to B & C to C from the
primary unit to the secondary unit.
1)
Wire from JP2-7 to Power supply (+)
2)
Wire from JP2-8 to light/siren (+)
3)
Wire from power supply (-) to light/siren (-)
* 24VAC, 1A max current draw.
1)
Wire from JP2-5 to Power supply (+)
2)
Wire from JP2-6 to light/siren (+)
3)
Wire from power supply (-) to light/siren (-)
* 24VAC, 1A max current draw.
Gate Open Light/Siren:
Constant Warn or Prewarn:
JP10 - Loop Inputs:
1 & 2)
Reverse loop wires
3 & 4)
Exit loop wires
5 & 6)
Phantom loop wires
Only used with the Ramset
RLD-24 & ILD-24s plug-in
loop detectors.
JP 13 - Monitored Anti-
Entrapment Device:
1)
N.C. (Normally Closed)
2)
N.O. (Normally Opened)
3)
Common
4)
VS (Voltage Supply)
5)
VS (Voltage Supply)
**Every installation must have Monitored Entrapment Pro-
tection.
Without it the operator will not function.
APPROVED ANTI-ENTRAPMENT DEVICES:
• Miller’s Edge “PrimeGaurd
• Miller’s Edge “ReflectiGaurd”
• Miller’s Edge “Wireless Edge Link”
• Miller’s Edge “The Solution”
• EMX ”IRB-MON”
JP11 - Foot Pedal Plug:
1)
Common (Foot pedal switch)
2)
Normally Open (Foot pedal switch)
Only used on models with a foot pedal (RAM 100,
1000, 5500, 300)
On the above mentioned operators, S7 must be in the ‘OFF’
position
On all other models, S7 must be in the ‘ON’ position
Factory wired to the foot pedal switch.