Copyright 2020, Al-Rakeb Oil, Electricity & Construction Services Company | Kuwait
39
8.
There is a leak detecting alarm located in the control room of the cabin. The role of this
device is to alarm the operator in case there was any leakage detected in the tank. The alarm
should specify which tank is leaking by showing a LED light next to the word “leak 1” or
“leak 2”.
9.
In order to fill both tanks with the same product make sure to open the by-pass flange that
separates tank 1 and 2. It can be reached by accessing the manhole. Refer to section 1.3
part number 34. The figure 35 shows the by-pass flange.
Figure 35. Shows the by-pass flange.
3.6.3 Filling Vehicles and other Machinery.
1.
Make sure that the MFS is supplied with an external power source of 240 V single phase
with a frequency 50 Hz. The external power source should be provided by using the input
plug located next to the condenser unit.
2.
Start filling the vehicle by removing the fuel dispensing hose and filling the vehicle. Once
the hose is displaced from the its place the fuel pump will start and the Flanged Solenoid
Valve 2'' will open letting the operator fill the vehicle.