HORIZONTAL WALL TERMINAL, TYPE C11
Horizontal wall terminal, type C11
Dimensions of flue pipe:
The fireplace is supplied with an outlet spigot, dimension Ø100/Ø150 mm . This flue dimension can be used
for the entire flue . Alternatively, a Ø130/Ø200 adapter can be fitted, so that this flue dimension can be
used for the rest of the flue .
Flue terminal:
Ø130/Ø200 Item no . USDHC 130
Ø100/Ø150 Item no . USDHC 100
Maximum length of flue pipe to outer wall (H)
= 4 X vertical flue pipe length (V) -1 for Ø130 / Ø200 pipe .
= 2 X vertical flue pipe length (V) for Ø100 / Ø150 pipe .
Maximum permitted length (V + H) = 15 m .
Minimum vertical height of flue pipe = 0 .5 m .
Vertical length of
flue pipe (V) in
metres
Maximum length of
horizontal flue pipe
(H) in metres Ø130/
Ø200
Maximum length of
horizontal flue pipe
(H) in metres Ø100/
Ø150
0 .5 1 1
1 3 2
1 .5 5 3
2 7 4
2 .5 9 5
3 11 6
3 .5 13 7
4 15 8
4 .5 15 9
5 15 10
5 .5 15 11
6 .5 15 13
7 15 14
7 .5 <
15
15
Flue gas restrictor for Ø100/Ø150
Vertical height < 1 m: No restrictor
Vertical height < 1–2 m: Ø62 mm restrictor
Vertical height > 2 m: Ø76 mm restrictor
32 - GB
GB
Summary of Contents for Nexo 100
Page 15: ...DIMENSIONAL DRAWINGS VIVA L GAS Viva L 140 Gas GB 15 GB...
Page 87: ...DECLARATION OF PERFORMANCE GB 87 GB...
Page 88: ...DECLARATION OF PERFORMANCE 88 GB GB...
Page 89: ...DECLARATION OF PERFORMANCE GB 89 GB...
Page 90: ...DECLARATION OF CONFORMITY 90 GB GB...
Page 91: ...DECLARATION OF CONFORMITY GB 91 GB...
Page 92: ...DECLARATION OF CONFORMITY 92 GB GB...
Page 94: ...94 GB GB...