background image

10

TROUBLESHOOTING GUIDE

SYMPTOM

CAUSE

CORRECTION

Display shows "Err"

1.

 The automatic circuit

breaker has found an elec-
trical problem.

The "Err" in the display indicates a short cir-
cuit or an electrical overload on a particular
station. The station's number should also be
displayed; for example "2 Err" means the
problem is in Station Two's circuit.

Usually, the short circuit is in the solenoid on
the electric valve, but short circuits can also
occur in the wire connectors at the valve.
Occasionally, nicked or "skinned" field wires
can cause a short. A large pump start relay
can also produce a momentary overload that
may be detected by the controller.

Locate and repair the cause of the short cir-
cuit. See the "Diagnostic Circuit Breaker" on
page 9 for instructions on clearing the prob-
lem indicator from the display and testing
the station.

Display shows "Err" for a few sec-
onds and then the station in opera-
tion for a few seconds.

2.

Same as Cause #1.

See correction for Cause #1.

Display is blank.

3.

 Power is off to the con-

troller

4.

If the controller is still

receiving power, an electri-
cal surge exceeding the
controller's built-in surge
protection may have dam-
aged the controller's micro-
processor.

Re-establish power to the controller. If the
current time is not shown or your program is
no longer in the memory, reprogram the
controller.

Open the lower access cover and erase all
programs as described on page 9.

If the display remains blank, the controller
may be permanently damaged.
In the U.S.A., Call 1-800-247-3782 for a ser-
vice referral.

Display shows numbers and let-
ters, but is not counting or advanc-
ing.

5.

 Same as Cause #4.

See correction for Cause #4.

Watering will not start.

6.

 Programming incom-

plete.

7.

 Sensor function may be

preventing irrigation.

8.

 Water supply may be

shut off.

Check to see if:
• program start time is correct
• stations are assigned to the program
• the date and time are correct in the display
• AM and PM settings are mixed up
• the dial is set to OFF instead of AUTO

Set sensor switch to OFF position and man-
ually start a station.

Check to see if water supply line has pres-
sure.

Watering will not stop.

9.

Programs may have ac-

cidentally been set to over-
lap.

10.

 A valve is stuck in the

open position.

Check to see if another program's start time
came due during the previous program's cy-
cle. The overlapped program would immedi-
ately follow the earlier one. Change pro-
gramming if necessary.

Turn dial to OFF and wait 10-20 seconds. If
the irrigation does not stop, shut off the
valve manually and repair the valve.

Summary of Contents for E-3

Page 1: ...Please read the in structions carefully and keep this manual in a handy location for future reference PROGRAMMING CONTROLS The following is a key to the buttons and icons on the E Class controller fa...

Page 2: ...ll struggling with your old sprinkler timer Having a hard time complying with local watering restrictions Upgrading to a new Rain Bird sprinkler timer is easier than you might think New timers are eas...

Page 3: ...6 will flash in the display Press or to set to the current year 3 Press ENTER ENTER to enter your selection 4 The digits for the current month will now flash 01 Press or to set to the current month 5...

Page 4: ...s with today s number and abbreviation The seven weekdays are dis played as a row of numbers For example Mon day is 1 Tuesday is 2 etc 1 2 The square around a day s number means it is a water day To t...

Page 5: ...ress ENTER until the start time you want to delete appears in the display 4 Move the start time to the blank screen just before midnight The E Class controller automatically arranges start times in th...

Page 6: ...pears A B or C and then start over with STEP II VI ADJUST WATER BUDGET PERCENTAGE 1 WATER BUDGET allows you to increase or decrease watering time length for all stations on a Pro gram with just one ad...

Page 7: ...of minutes you want Normal station running times in the Automatic Programs are not affected 2 STATION 2 4 STOP AT ANY STATION YOU WANT use or to set a running time for it Use ENTER ENTER to put the s...

Page 8: ...the first stacked Program will blink 4 IX TO RUN THE TEST PROGRAM 1 2 3 You can manually advance through the stations of any program by setting the dial to AUTO and repeatedly pressing the ENTER ENTE...

Page 9: ...ean method use this dial posi tion and the ENTER button XII MOISTURE SENSOR SETTING IF INSTALLED You can tell the controller to stop watering when an attached sensor reaches it s wet condition You can...

Page 10: ...r automatically shuts off the station with the fault After 30 40 seconds while the E Class unit is checking again to confirm the fault the controller advances to the next station in the program Every...

Page 11: ...the controller s micro processor Re establish power to the controller If the current time is not shown or your program is no longer in the memory reprogram the controller Open the lower access cover a...

Page 12: ...controller down over the wall mounting bracket on models with a sliding door this overhead clearance also allows the door to be removed or rein stalled Note 2 For indoor units that do not have a slidi...

Page 13: ...controller down over the mounting bracket until lower mounting hole D aligns with the hole in the back of the terminal strip compartment You may want to wait until after you have cut your wire conduit...

Page 14: ...etely bare cop per wire from the power source to the green yellow wire from the controller In a similar manner con nect each of the two remaining power source wires to one of the controller s input wi...

Page 15: ...VALVES NOTE The E Class residential controller is designed to work best with 18 gauge multi conductor cable that is approved for low voltage direct burial applications These cables usually have a whi...

Page 16: ...trip Then if a prolonged power outage outlasts the controller s memory protection and the controller activates its default program when the pump and stations 5 or 6 are running station 4 s valve allow...

Page 17: ...by one or more of the follow ing measures Reorient the receiving antenna Move the controller away from the receiver Plug the controller into a different outlet so that the controller and receiver are...

Reviews: