Rain Bird E-3 Installation, Programming & Operation Manual Download Page 10

9

XIII. ERASE ALL PROGRAMMING

With the dial at Auto, open and remove the lower cover. With a metal object, momentarily connect
two contacts at the back of the RESET Tunnel. When the display goes blank, remove the metal ob-
ject. You can now reprogram the controller.

1.

4.

XIV. BACK-UP MEMORY (NO BATTERIES REQUIRED)

During a power outage
1.

The display is blank

2.

 Time/Date/all Programs retained for 24-30

hrs.

3.

 Default Program if memory is lost and power re-

turns:

Date: 01/01/96
Time: 12:00 AM
Start Time: 8:00 AM
All Stations: On Program A
Day Schedule: 7-day, water everyday
Station Timing: 10 minute each

The default program disappears as you start to re-
program.

XV. TROUBLESHOOTING

DIAGNOSTIC CIRCUIT BREAKER 

(No fuse required)

If the controller detects an electrical short circuit on one of the sprinkler system's station wires or valve
solenoids, the controller automatically shuts off the station with the fault. After 30 - 40 seconds, while the E-
Class unit is checking again to confirm the fault, the controller advances to the next station in the program.

Every 3 seconds, the controller will display the problem station's number with the letters "Err". The E-Class
controller will continue to run each operable station in the program. As each station is running, the controller
(at an alternate 3-second interval) will display the station's number and time-to-go.

When the controller finishes the program, it will continue to display the problem station's number and "Err".

At this point, you should isolate and repair the short circuit. Short circuits are most often found to be in the
valve solenoid (the plastic-encapsulated coil on the valve with the two wire leads) or in the wire connectors to

the valve leads. After you have found and repaired the short, turn the dial to AUTO and press 

ENTER

ENTER

 to

clear the "Err" message from the display. You can then operate the station manually to see if it works properly.

2.

3.

Summary of Contents for E-3

Page 1: ...Please read the in structions carefully and keep this manual in a handy location for future reference PROGRAMMING CONTROLS The following is a key to the buttons and icons on the E Class controller fa...

Page 2: ...ll struggling with your old sprinkler timer Having a hard time complying with local watering restrictions Upgrading to a new Rain Bird sprinkler timer is easier than you might think New timers are eas...

Page 3: ...6 will flash in the display Press or to set to the current year 3 Press ENTER ENTER to enter your selection 4 The digits for the current month will now flash 01 Press or to set to the current month 5...

Page 4: ...s with today s number and abbreviation The seven weekdays are dis played as a row of numbers For example Mon day is 1 Tuesday is 2 etc 1 2 The square around a day s number means it is a water day To t...

Page 5: ...ress ENTER until the start time you want to delete appears in the display 4 Move the start time to the blank screen just before midnight The E Class controller automatically arranges start times in th...

Page 6: ...pears A B or C and then start over with STEP II VI ADJUST WATER BUDGET PERCENTAGE 1 WATER BUDGET allows you to increase or decrease watering time length for all stations on a Pro gram with just one ad...

Page 7: ...of minutes you want Normal station running times in the Automatic Programs are not affected 2 STATION 2 4 STOP AT ANY STATION YOU WANT use or to set a running time for it Use ENTER ENTER to put the s...

Page 8: ...the first stacked Program will blink 4 IX TO RUN THE TEST PROGRAM 1 2 3 You can manually advance through the stations of any program by setting the dial to AUTO and repeatedly pressing the ENTER ENTE...

Page 9: ...ean method use this dial posi tion and the ENTER button XII MOISTURE SENSOR SETTING IF INSTALLED You can tell the controller to stop watering when an attached sensor reaches it s wet condition You can...

Page 10: ...r automatically shuts off the station with the fault After 30 40 seconds while the E Class unit is checking again to confirm the fault the controller advances to the next station in the program Every...

Page 11: ...the controller s micro processor Re establish power to the controller If the current time is not shown or your program is no longer in the memory reprogram the controller Open the lower access cover a...

Page 12: ...controller down over the wall mounting bracket on models with a sliding door this overhead clearance also allows the door to be removed or rein stalled Note 2 For indoor units that do not have a slidi...

Page 13: ...controller down over the mounting bracket until lower mounting hole D aligns with the hole in the back of the terminal strip compartment You may want to wait until after you have cut your wire conduit...

Page 14: ...etely bare cop per wire from the power source to the green yellow wire from the controller In a similar manner con nect each of the two remaining power source wires to one of the controller s input wi...

Page 15: ...VALVES NOTE The E Class residential controller is designed to work best with 18 gauge multi conductor cable that is approved for low voltage direct burial applications These cables usually have a whi...

Page 16: ...trip Then if a prolonged power outage outlasts the controller s memory protection and the controller activates its default program when the pump and stations 5 or 6 are running station 4 s valve allow...

Page 17: ...by one or more of the follow ing measures Reorient the receiving antenna Move the controller away from the receiver Plug the controller into a different outlet so that the controller and receiver are...

Reviews: