27
Installation
– Regulation type
3.9.3
In this submenu you must choose the type of regulation which
must be used for the room managed by the programmer.
To change the sensor, press on the desired option to frame in
green the button.
On / Off:
(Hysteresis)
Basic regulation with static differential of 0.5°C
PWM1:
(proportional band)
Advanced regulation with integral proportional band specially made
for panel heater or floor heating system with small inertia (with
liquid concrete…)
PWM2:
(proportional band)
Advanced regulation with integral proportional band specially made
for panel heater or floor heating system with bigger inertia (with
traditional concrete…)
Installation
– Pump Exercise
3.9.4
Anti-lock-braking function of the pump and actuators. When the
pump or actuat
ors hasn’t worked during more than 5 days, all
outputs on the Master(s) will be activated during few times to avoid
damage of the hydraulic components.
A green framed button will be used to show function activated.