26
Important:
These two following parameters must be used and
adjusted only by a confirmed user or installer (Please contact your
seller, see the last page for this)
Installation
– Calibration sensor
3.9.2
In this submenu you can calibrate the sensors.
Procedure for calibration:
- The calibration must be done after 24Hours working with the
same setting temperature.
Ambient sensor calibration:
- To check the temperature in the room, put a thermometer at 1.5M
distance to the floor in the concerned room and wait 1 hour to be
sure that the thermometer show the correct temperature.
Then you can enter the value saw on the thermometer with the
arrow buttons (
Up
) or (
Down
), valid or cancel your adjustment with
the corresponding button.
- When a calibration is made the cancel button appears.
- To erase the calibration already made press on the cancel button.
Floor (Ext) sensor calibration:
- The calibration must be done as described above if the external
sensor is connected and used like a deported ambiance sensor.
- If the external sensor is used as floor sensor, the thermometer
should be put on the floor.