5.5 MODBUS TCP setting
From the PLC or the PCs, etc., you may use MODBUS TCP to access the RN172, to find out the values of
CH1 and CH2 inside.
[5.MODBUS TCP SETUP MENU.]
------------------------------------------------------------------
HOLDING REGISTER (16BIT),FUNCTION CODE 3
------------------------------------------------------------------
OFFSET [0] : CH1 FLOATING 32BIT VALUE (16BIT LOW)
OFFSET [1] : CH1 FLOATING 32BIT VALUE (16BIT HIGH)
------------------------------------------------------------------
OFFSET [2] : CH2 FLOATING 32BIT VALUE (16BIT LOW)
OFFSET [3] : CH2 FLOATING 32BIT VALUE (16BIT HIGH)
------------------------------------------------------------------
OFFSET [4] : CH1 INTEGER 16BIT VALUE (16BIT)
------------------------------------------------------------------
OFFSET [5] : CH2 INTEGER 16BIT VALUE (16BIT)
------------------------------------------------------------------
A.Set MODBUS TCP PORT[ 502 ]
B.SetByteReverse [ 0] (1:Reversed,0:None)
Q.Quit.
A.
Change the port number used by MODBUS TCP. Normally, the port number is set to 502.
B.
Turn Byte Reverse ON/OFF. Select On(1) to change the sequence of the byte.