D9024/D10024 Operation

    

Page 8 of 13

D10024

SHIFT

G

T

6

[Active]  1)Commission 2)Test   3)Time  [1]
4)Enable 5)Disable     6)PRINT  7)View

O

A

N

0

B

C

P

1

2

D

Q

E

R

3

4

F

S

5

H

U

7

V

I

J

W

8

9

K

X

L

Y

M

Z

CHANGE

Figure 3: Operator’s Menu, Main Level

D.4.a.  System Tests

Select the second option, 

2) Test

,  key from the Main Level Menu to open the Test Menu.  This

allows the operator to test:

• 

the LEDs on the Front Panel Display

• 

the devices connected to the system.

If no action is taken, the display reverts to the normal display after one minute.
The third option on this menu, 

3) Outputs

, is not available to Level Two.

D10024

SHIFT

G
T

6

 1) LEDs   2) Walk Test zone  3) Outputs

O

A
N

0

B

C
P

1

2

D
Q

E
R

3

4

F
S

5

H
U

7

V

I

J

W

8

9

K
X

L
Y

M
Z

CHANGE

Figure 4:  Test Menu

D.4.a.1.  LEDs Test

Select the first option,

 1) LEDs

, by pressing the

 1

 key.  The panel will flash all LEDs on the

LED Display and step through all the 

Alarm

 and 

Trouble

 LEDs in the ZONE/AREA Display.

On completion of the test, the Display will report the results of the test and automatically

revert to the normal menu after one minute.
To interrupt and end the test, press the NO key.

D.4.a.2.  Walk Test

The Walk Test allows the operator to test the system devices without having to reset the

panel after each device is tested.  Select the second option, 

2) Walk Test zone

, by pressing

the 

2

 key.

Note: If no action is taken within one minute, the display reverts to the normal display.  Press the >

key to restore the test display.

The display prompts, “Ring bells?”
Press the 

YES 

key to activate notification appliances briefly as each device is tested, or

press the 

NO

 key to bypass the indicator test.

The display prompts, “Test from zone? (Please key in number, then press Enter).”
Enter the number of the first zone to be tested.

Summary of Contents for D9024

Page 1: ...nt to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a commercial installation This equipment generates uses and can radiate radio...

Page 2: ...ble Signal Response 6 D 3 Alarm Conditions 6 D 3 a Alarm Signals 6 D 3 b Alarm Signal Response 7 D 4 Operator s Menu 7 D 4 a System Tests 8 D 4 a 1 LEDs Test 8 D 4 a 2 Walk Test 8 D 4 b Time Setting 9...

Page 3: ...of Radionics 1800 Abbott Street Salinas CA 93901 USA 74 07661 000 B 01 97 D9024 D10024 Operation Page 3 of 13 Figure 1 Front Panel Display 4 Figure 2 Level Two Controls 7 Figure 3 Operator s Menu Main...

Page 4: ...on on system events and status and displays interactive prompts The middle display is a row of LEDs that indicate the type of system event and status The lower display area is the ZONE AREA LED displa...

Page 5: ...by 120 V AC the greenAC PowerLED at the right end of the LED Display will be lit The normal Alphanumeric Display will alternate between a time and date message and a system status message If the 120...

Page 6: ...the amberSystem Troubleor Fault LED will light In addition the amber Trouble LED in the ZONE AREA section of the panel will light to indicate the location the panel s internal buzzer will sound and t...

Page 7: ...ing theAlarm Silencekey again turns on the external notification appliances Press theTrouble silencekey to turn off the panel buzzer The amberTrouble Silenced LED will light Press theSystem Reset key...

Page 8: ...V I J W 8 9 K X L Y M Z CHANGE Figure 4 Test Menu D 4 a 1 LEDs Test Select the first option 1 LEDs by pressing the1 key The panel will flash all LEDs on the LED Display and step through all theAlarm a...

Page 9: ...the LED at the device in alarm After a few seconds the panel will automatically reset and turn off the device LED The panel allows up to one minute for smoke devices to clear The operator may then te...

Page 10: ...cuit number and press ENTER The display then prompts for the address of the device Key in the address and press ENTER The display repeats the circuit number and address Press the YES key Note Any disa...

Page 11: ...e Alphanumeric Display message indicates that the relays are disabled Press theTrouble Silencekey to silence the buzzer TheTrouble SilencedLED will light Note The disabled output must be enabled befor...

Page 12: ...tion about the selected option on the Alphanumeric Display After viewing an option press theNO key to return to the View Menu Press the NO key again to return to the Main Level of the Operator s Menu...

Page 13: ...oning and programming the Fire Alarm Control Panel E 1 Disable Enable Sounders Notification Appliances All sounders notification appliances and relays can be disabled or enabled from the control panel...

Reviews: