D9024/D10024 Operation

    

Page 7 of 13

D10024

SHIFT

Alarm

Silence

LED DISPLAY

ZONE/AREA DISPLAY

">" KEY

ALPHANUMERIC DISPLAY

SYSTEM RESET

KEY

TROUBLE SILENCE

KEY

SYSTEM TROUBLE

LED

TROUBLE SILENCED

LED

ALARM

LED

ALARM SILENCED

LED

AC POWER

LED

ALARM SILENCE

KEY

FIRE DRILL

KEY

System
Trouble

1

3

Alarm

5

4

6

Trouble
Silenced

Point

Bypassed

7

8

9

Earth
Fault

A
N

0

B
O

C
P

1

2

System

Reset

Trouble
Silence

E
R

4

D
Q

3

F
S

5

10

11

12

Fault

Sounder

13

14

15

Alarm

Silenced

16

17

CPU
Reset

19

20

AC Power

Fire
Drill

6

7

I

V

J

W

8

9

Letters

Numbers

ENTER

NO

Keyword

YES

K
X

L
Y

M

Z

CHANGE

Figure 2: Level Two Controls

D.3.b.  Alarm Signal Response

Press the 

Alarm Silence

 key to turn off notification appliances external to the panel.  The

 Alarm

Silenced

 LED will light.  Pressing the 

Alarm Silence

 key again turns on the external notification

appliances.  Press the 

Trouble silence

 key to turn off the panel buzzer.  The amber 

Trouble

Silenced

 LED will light.  Press the

 System Reset

 key to reset the system.  The 

Alarm

 and

Silenced

 LEDs will go out and the Alphanumeric Display will return to normal.

Note: The panel will not allow a reset from an Alarm condition until the notification appliances have

been silenced.

To return the system to Level Two, press the “>“ key, and select 

5) Disable

 from the

Alphanumeric Display.  Select 

3)Keys

 from the display.  The display will return to normal.  Press

the 

Fire Drill

 key to verify that the keys are disabled.  The display will prompt, “do you want to

enable the Control Keys?”  Press the 

NO

 key.  The display will return to normal.

D.4.  Operator’s Menu

Pressing the “>“ key will open the Operator’s Menu, Main Level, on the Alphanumeric Display.  The

first option, 

1 Commission

, is not available to Level Two Operators.  See the Programmer’s Guide

for commissioning and programming information.  The other options on the Main Level permit tests

and enabling/disabling of various system functions.

Summary of Contents for D9024

Page 1: ...nt to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a commercial installation This equipment generates uses and can radiate radio...

Page 2: ...ble Signal Response 6 D 3 Alarm Conditions 6 D 3 a Alarm Signals 6 D 3 b Alarm Signal Response 7 D 4 Operator s Menu 7 D 4 a System Tests 8 D 4 a 1 LEDs Test 8 D 4 a 2 Walk Test 8 D 4 b Time Setting 9...

Page 3: ...of Radionics 1800 Abbott Street Salinas CA 93901 USA 74 07661 000 B 01 97 D9024 D10024 Operation Page 3 of 13 Figure 1 Front Panel Display 4 Figure 2 Level Two Controls 7 Figure 3 Operator s Menu Main...

Page 4: ...on on system events and status and displays interactive prompts The middle display is a row of LEDs that indicate the type of system event and status The lower display area is the ZONE AREA LED displa...

Page 5: ...by 120 V AC the greenAC PowerLED at the right end of the LED Display will be lit The normal Alphanumeric Display will alternate between a time and date message and a system status message If the 120...

Page 6: ...the amberSystem Troubleor Fault LED will light In addition the amber Trouble LED in the ZONE AREA section of the panel will light to indicate the location the panel s internal buzzer will sound and t...

Page 7: ...ing theAlarm Silencekey again turns on the external notification appliances Press theTrouble silencekey to turn off the panel buzzer The amberTrouble Silenced LED will light Press theSystem Reset key...

Page 8: ...V I J W 8 9 K X L Y M Z CHANGE Figure 4 Test Menu D 4 a 1 LEDs Test Select the first option 1 LEDs by pressing the1 key The panel will flash all LEDs on the LED Display and step through all theAlarm a...

Page 9: ...the LED at the device in alarm After a few seconds the panel will automatically reset and turn off the device LED The panel allows up to one minute for smoke devices to clear The operator may then te...

Page 10: ...cuit number and press ENTER The display then prompts for the address of the device Key in the address and press ENTER The display repeats the circuit number and address Press the YES key Note Any disa...

Page 11: ...e Alphanumeric Display message indicates that the relays are disabled Press theTrouble Silencekey to silence the buzzer TheTrouble SilencedLED will light Note The disabled output must be enabled befor...

Page 12: ...tion about the selected option on the Alphanumeric Display After viewing an option press theNO key to return to the View Menu Press the NO key again to return to the Main Level of the Operator s Menu...

Page 13: ...oning and programming the Fire Alarm Control Panel E 1 Disable Enable Sounders Notification Appliances All sounders notification appliances and relays can be disabled or enabled from the control panel...

Reviews: