D9024/D10024 Operation

    

Page 6 of 13

D.1.a.  Power Failure Signal

If the 120 

V

 AC power source is interrupted, the 

AC Power 

LED will flash, the panel buzzer will

sound, and the amber 

System Trouble 

and 

Earth Fault 

LEDs will light.  The illumination will go

out on the Alphanumeric Display, and the Display will show an “AC Fail” message and provide

information about the failure and the status of the standby batteries.
If the standby batteries fail, the 

AC Power

 LED will go out.

D.1.b.  Power Failure Signal

To silence the panel buzzer, press the 

Trouble Silence

 key.  The amber 

Trouble Silenced

 LED

will light.
When the 120 

V

 AC power is restored, the green 

AC Power 

LED stops flashing and remains on,

and the 

System Trouble 

and 

Earth Fault 

LEDs go out.  The amber 

CPU Reset 

LED lights while

the system resets itself and goes out when the reset is complete.  The Alphanumeric Display

returns to normal.

D.2.  Trouble Conditions

The system responds to other-than-normal conditions, which are not alarm conditions, by sounding

the internal buzzer and initiating a Trouble Condition.

D.2.a.  Trouble Signals

If a device fails to respond, is disabled, the response is not within normal parameters, or the
system detects a fault, the amber 

System Trouble

 or

 Fault

 LED will light.  In addition, the

amber 

Trouble

 LED in the ZONE/AREA section of the panel will light to indicate the location, the

panel’s internal buzzer will sound, and the Alphanumeric Display will provide detailed

information.

D.2.b.  Trouble Signal Response

To acknowledge the event, press the 

Trouble Silence

 key to mute the internal buzzer.  (Under

certain circumstances, the system may override the mute.)  The amber 

Trouble Silenced

 LED

lights to indicate that condition.  The system will not allow a reset until the problem is corrected.

If necessary, the system allows disabling of individual devices and zones.  See Section D.4.c. of
this guide.  After correcting the problem, press the System Reset key.  The amber 

Trouble

Silenced

 LED goes out and the Alphanumeric Display returns to normal.

D.3.  Alarm Conditions

The panel will signal an alarm if it detects an Alarm condition or a Fire Drill test.

D.3.a.  Alarm Signals

If the control panel  initiates an alarm condition, the red 

Alarm

 LED at the left of the LED Display

flashes to indicate the system has detected a fire condition and has activated the system
notification appliances, the internal buzzer sounds, ZONE/AREA 

Alarm

 LED(s) light indicating

the event location, and the Alphanumeric Display provides detailed information.
To test the alarm system, press the 

Fire Drill

  key.  The panel will activate system notification

appliances.  The red 

Alarm

 LED at the left of the LED Display flashes and the internal buzzer

sounds.  The Alphanumeric Display indicates a “Fire Test.”

Summary of Contents for D9024

Page 1: ...nt to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a commercial installation This equipment generates uses and can radiate radio...

Page 2: ...ble Signal Response 6 D 3 Alarm Conditions 6 D 3 a Alarm Signals 6 D 3 b Alarm Signal Response 7 D 4 Operator s Menu 7 D 4 a System Tests 8 D 4 a 1 LEDs Test 8 D 4 a 2 Walk Test 8 D 4 b Time Setting 9...

Page 3: ...of Radionics 1800 Abbott Street Salinas CA 93901 USA 74 07661 000 B 01 97 D9024 D10024 Operation Page 3 of 13 Figure 1 Front Panel Display 4 Figure 2 Level Two Controls 7 Figure 3 Operator s Menu Main...

Page 4: ...on on system events and status and displays interactive prompts The middle display is a row of LEDs that indicate the type of system event and status The lower display area is the ZONE AREA LED displa...

Page 5: ...by 120 V AC the greenAC PowerLED at the right end of the LED Display will be lit The normal Alphanumeric Display will alternate between a time and date message and a system status message If the 120...

Page 6: ...the amberSystem Troubleor Fault LED will light In addition the amber Trouble LED in the ZONE AREA section of the panel will light to indicate the location the panel s internal buzzer will sound and t...

Page 7: ...ing theAlarm Silencekey again turns on the external notification appliances Press theTrouble silencekey to turn off the panel buzzer The amberTrouble Silenced LED will light Press theSystem Reset key...

Page 8: ...V I J W 8 9 K X L Y M Z CHANGE Figure 4 Test Menu D 4 a 1 LEDs Test Select the first option 1 LEDs by pressing the1 key The panel will flash all LEDs on the LED Display and step through all theAlarm a...

Page 9: ...the LED at the device in alarm After a few seconds the panel will automatically reset and turn off the device LED The panel allows up to one minute for smoke devices to clear The operator may then te...

Page 10: ...cuit number and press ENTER The display then prompts for the address of the device Key in the address and press ENTER The display repeats the circuit number and address Press the YES key Note Any disa...

Page 11: ...e Alphanumeric Display message indicates that the relays are disabled Press theTrouble Silencekey to silence the buzzer TheTrouble SilencedLED will light Note The disabled output must be enabled befor...

Page 12: ...tion about the selected option on the Alphanumeric Display After viewing an option press theNO key to return to the View Menu Press the NO key again to return to the Main Level of the Operator s Menu...

Page 13: ...oning and programming the Fire Alarm Control Panel E 1 Disable Enable Sounders Notification Appliances All sounders notification appliances and relays can be disabled or enabled from the control panel...

Reviews: