D9024/D10024 Operation
Page 10 of 13
Notification appliances cannot be enabled or disabled from Level Two. See Section E. of this
manual for Level Three Instruction.
D.4.c.1. Enable/Disable by Zone
To enable or disable input signals from devices by zone, select option one,
1) zone
, from the
Enable or Disable Menu. The display will prompt for the zone number.
Key in the zone number and press the
ENTER
key. The display will repeat the zone number
and ask “OK?” Press the
YES
key to confirm. The panel will enable or disable all the input
devices in the selected zone.
Note: Any disabled circuit-driven device or relay on a circuit will still operate on output
as
programmed. Only the input signal will be disabled.
Note: Manual Alarm Boxes within the zone are not disabled.
When a device is disabled, the amber
Point Bypassed
LED on the LED Display lights. The
amber
Trouble
LED in the corresponding zone of the ZONE/AREA Display lights, and the
panel displays a disable message on the Alphanumeric Display.
D.4.c.2. Enable/Disable Individual Detection Devices (Inputs)
To enable or disable input signals from individual detection devices, select option two, 2)
Input, from the Enable or Disable Menu. The display prompts for the polling circuit (loop)
number (1-5).
Key in the circuit number and press ENTER. The display then prompts for the address of the
device.
Key in the address and press ENTER. The display repeats the circuit number and address.
Press the YES key.
Note: Any disabled circuit-driven device or relay on a circuit will still operate on output as
programmed. Only the input signal will be disabled.
D.4.c.3. Enable/Disable Panel Keys
To disable Panel Keys, select option three,
3) Keys
, from the Disable Menu. The display
indicates that the panel keys are inhibited and then returns to the normal display. This
places the panel in the Level One Control Level.
To enable Panel Keys, press any of the Control Keys except
NO
, or press the “>“ key. The
panel prompts, “Do you want to enable the control keys?”
Press the
YES
key. The panel prompts for the pass code.
Key in the Level Two pass code. The display reverts to the Operator’s Menu, Main Level.
(See Figure 3.) After one minute the display reverts to the normal display.
D.4.c.4. Enable/Disable Delayed Day Mode
The Delayed Day Mode is configured from Level Three. The Delayed Day Mode causes the
panel to respond to high sensor signals by sounding the panel buzzer and displaying a
warning message at the Alphanumeric Display. The panel delays alarm activation for a
programmed period. Configuration parameters allow variations in time of day and zones
affected. The Level Two operator may enable or disable the Delayed Day Mode through the
Enable or Disable Menu.
To enable the Delayed Day Mode, select option four, 4)
Day Modes
, from the Enable Menu.
The display will prompt for the programmed number of days.
To accept as prompted, press the
YES
key.