D7212 Installation and Troubleshooting Quick Reference

Page  3

74-06914-000-A 8/93

© 1993 Radionics

Problems with Points

Symptom

Diagnosis

Remedy

Point appears as
missing at command
centers and in reports
to the receiver.

POPIT is not
connected or
incorrectly connected
to the data expansion
loop.

Disconnect the EOL resitor from the loop
output of the POPIT. You should measure 8 to
13 VDC, constant.

Sensor loop switch (1
to 8) is turned off on
OctoPOPIT.

If the sensor loop switch on an OctoPOPIT is
turned off for a programmed point, the point
reports as missing.

Switch 12 ON for more
than one OctoPOPIT
connected to ZONEX.   

Switch 12 ON for
OctoPOPIT
connected to same
ZONEX as a D8125.

Connect only one OctoPOPIT with switch 12
ON to ZONEX.  

If ZONEX is connected to a D8125, turn switch
12 OFF for all OctoPOPITs connected to that
terminal.

POPIT is not
programmed correctly.

Verify that the switches on the POPIT are set
for the missing POPIT number. Switches set
incorrectly can cause both missing and extra
POPITs.  

Points intermittently
appear as missing.
Points are erratic.

Problem with data
expansion loop.   

See 

Problems with Data Expansion Loop.

Debounce Count
parameter set at 1. If
an off-board point is in
transition between
normal and faulted
conditions as the
panel scans it, it
appears as missing.

Radionics recommends that the Debounce
Count be left at the default of 2.  

Decreasing the Debounce Count to 1 may
cause points to appear as missing. Increasing
the Debounce may cause missed alarms.

Summary of Contents for D7212

Page 1: ...rminal Description 12 Introduction This reference contains the very basic information a trained installer needs to install and troubleshoot a D7212 system See the D7212 Operation and Installation Manu...

Page 2: ...are AREA IS ON AREA IS OFF Follow the procedure below to toggle between custom and default idle text 1 Ensure the command center is at idle text 2 Press COMMAND 5 7 3 The display will change to defau...

Page 3: ...connected to same ZONEX as a D8125 Connect only one OctoPOPIT with switch 12 ON to ZONEX If ZONEX is connected to a D8125 turn switch 12 OFF for all OctoPOPITs connected to that terminal POPIT is not...

Page 4: ...Faulted points do not generate alarms or troubles as programmed Command 47 pressed at the time the alarm or trouble was generated The D7212 ignores input from all points in the same area programmed fo...

Page 5: ...FOR TYPICAL BURGLAR ALARM APPLICATIONS SUITABLE FOR VALVE TAMPER AND OTHER TYPES OF EXTINGUISHING SYSTEM SUPERVISION TYPICAL INITIATING DEVICES ARE DOOR CONTACTS NO NC FLOOR MATS MOTION SENSORS GLASS...

Page 6: ...keys is stuck under the faceplate Press each of the keys on the command center to be certain none of them is stuck Data connections yellow and green wires on one or more command centers are reversed...

Page 7: ...is plugged securely into the D5200 programmer 3 Check each conductor in the data power cord for continuity AC induction through the on board point sensor loops the DATA BUS or the ZONEX BUS 1 Verify...

Page 8: ...s 1 and 8 5 Verify that all telephones are on hook Leaving a telephone on hold after the other party hangs up creates an off hook condition Verify that no phones are on hold If completing the steps ab...

Page 9: ...y signal for all ten attempts to reach the receiver Calls are not reaching the receiver 1 Verify that correct prefixes and phone numbers for the receiver have been programmed into the D7212 2 Verify t...

Page 10: ...7 8 SWITCHED AUX POWER Supplies up to 1 4 Amps at 10 0 VDC to 13 9 VDC Use terminal 9 for common Programmed as Relay C Continuous output interrupted by CMD 47 or alarm verification Shares circuit bre...

Reviews: