background image

D7212 Installation and Troubleshooting Quick Reference

Page  4

74-06914-000-A 8/93

© 1993 Radionics

Problems with Points (Continued)

Symptom

Diagnosis

Remedy

One or more points
remain in trouble or
alarm with  
all devices connected
to the sensor loops
normal.

The sensor loop is
open, shorted, or
grounded.   

Opens,shorts, or
grounds cause
troubles or alarms
depending on point
programming.

Remove the sensor loop from the D7212 or
POPIT and meter it for continuity. There
should be no more than 100

 resistance, plus

the value of the end of line resistor on the
wires. If you meter less resistance than the
value of the end of line resistor, check the
wiring for shorts.  

With the wires for the loop removed, meter
them for continuity to ground. A ground before
the end of line resistor on an on-board point's
sensor loop is interpreted as a short. A ground
on a sensor loop for a POPIT point is
interpreted as an open.   

Faulted points do not
generate alarms or
troubles as
programmed.

Command 47 pressed
at the time the alarm  
or trouble was
generated.

The D7212 ignores input from all points in the
same area programmed for sensor reset during
sensor reset (Command 47).

Two points are
programmed with the
same address.

Points programmed with the same address do
not function correctly. Check to be certain that
you have not duplicated point addresses.

Panel transmitts PT
BUS TROUBLE
reports. Erroneous
alarm and/or trouble
reports may follow PT
BUS TROUBLE
report. Erroneous
alarm and/or trouble
events for off-board
points appear at
command centers.  

Short on D8125
POPEX module’s Data
Expansion Loop or
short on D7212’s
ZONEX data terminals
(27 & 28).

A short on the Data Expansion Loop or the
ZONEX data terminals generates a PT BUS
TROUBLE report.   

While the short remains, the panel responds as
though the sensor loop for each point
connected to the POPEX module was
shorted.

Check wiring for shorts.

A POPIT has its
switches set
incorrectly and it’s
sensor loop is
shorted.

Check to be certain all POPIT switches are set
correctly.

Summary of Contents for D7212

Page 1: ...rminal Description 12 Introduction This reference contains the very basic information a trained installer needs to install and troubleshoot a D7212 system See the D7212 Operation and Installation Manu...

Page 2: ...are AREA IS ON AREA IS OFF Follow the procedure below to toggle between custom and default idle text 1 Ensure the command center is at idle text 2 Press COMMAND 5 7 3 The display will change to defau...

Page 3: ...connected to same ZONEX as a D8125 Connect only one OctoPOPIT with switch 12 ON to ZONEX If ZONEX is connected to a D8125 turn switch 12 OFF for all OctoPOPITs connected to that terminal POPIT is not...

Page 4: ...Faulted points do not generate alarms or troubles as programmed Command 47 pressed at the time the alarm or trouble was generated The D7212 ignores input from all points in the same area programmed fo...

Page 5: ...FOR TYPICAL BURGLAR ALARM APPLICATIONS SUITABLE FOR VALVE TAMPER AND OTHER TYPES OF EXTINGUISHING SYSTEM SUPERVISION TYPICAL INITIATING DEVICES ARE DOOR CONTACTS NO NC FLOOR MATS MOTION SENSORS GLASS...

Page 6: ...keys is stuck under the faceplate Press each of the keys on the command center to be certain none of them is stuck Data connections yellow and green wires on one or more command centers are reversed...

Page 7: ...is plugged securely into the D5200 programmer 3 Check each conductor in the data power cord for continuity AC induction through the on board point sensor loops the DATA BUS or the ZONEX BUS 1 Verify...

Page 8: ...s 1 and 8 5 Verify that all telephones are on hook Leaving a telephone on hold after the other party hangs up creates an off hook condition Verify that no phones are on hold If completing the steps ab...

Page 9: ...y signal for all ten attempts to reach the receiver Calls are not reaching the receiver 1 Verify that correct prefixes and phone numbers for the receiver have been programmed into the D7212 2 Verify t...

Page 10: ...7 8 SWITCHED AUX POWER Supplies up to 1 4 Amps at 10 0 VDC to 13 9 VDC Use terminal 9 for common Programmed as Relay C Continuous output interrupted by CMD 47 or alarm verification Shares circuit bre...

Reviews: