D2212 Installation Manual
Page 15
© 1996 Radionics
74-07361-000-C 11/11/96
AC Power On
AC Power Off
In Alarm
Normal Current
Minimum Current
Maximum Current
Model
Number
Each
Each
Each
Number
Used
Unit
Total
Unit
Total
Unit
Total
D2212
1
125
_____
125
_____
190
_____
D202A
____
45
_____
45
_____
125
_____
D220A
____
30
_____
30
_____
125
_____
D222
____
30
_____
30
_____
140
_____
D223
____
30
_____
30
_____
140
_____
D208RF
____
50
_____
50
_____
50
_____
D216RF
____
50
_____
50
_____
50
_____
______
____
____
_____
____
_____
____
_____
______
____
____
_____
____
_____
____
_____
Total A
1
=
_____
Total B =
_____
Total C
2
=
_____
1 If Total A exceeds 1 A (140mA for fire and combined fire/burglary systems), a stand-alone power supply is required to
provide additional current.
2 If Total C exceeds 860 mA for fire systems, a stand-alone power supply is required to provide additional current.
Current Rating Chart for Standby Battery Calculations
All currents are in milliamperes (1 ampere=1000 milliamperes).
System Wiring Diagram, Issue A
s
s
P
P
P
D164 Phone
Cord to RJ31X
for Phone Line
Listed Audible
Signaling Device
Rated At 10.2 TO 13.9
VDC (Do NOT Use
Vibrating Type Horns)
P
P
P
P
D133/
D134
Relay
P
P
Supervised with 1k
Ω
EOL Resistor.
Typical Initiating
Devices are Door
Contacts NO/NC,
Floor Mats, Motion
Sensors, Glass Break
Detectors, etc.
NOT
Supervised,
Normally
Closed.
Typical
Initiating
Devices are
Door Contacts,
Floor Mats,
Motion
Sensors,
Tamper
Switches, etc.
All devices
open on alarm.
P
S
Supervised with 2k
Ω
EOL Resistor.
P/N 15-03130-010
P
S
P
S
P
S
P
S
P
S
P
P
KEYPADS,
EXPANDERS
AND RF
RECEIVERS.
INSTALL UP
TO EIGHT
DEVICES ON
THE PANEL.*
1
2
3
4
5
6
7
8
9
10
11 12 13 14
15
16 17
18
19 20
21
22 23
24
25 26 27 28 29
P
S
= POWER LIMITED
= SUPERVISED
P
S
P
S
P
S
P
S
A
B
C
D
Supervised with 1k
Ω
EOL Resistor.
Typical Initiating Devices are Door Contacts
NO/NC, Floor Mats, Motion Sensors, Glass Break
Detectors, etc.
Up To Four Point
Expansion Devices
Can Be Connected
Standby Switch
Programmer
Connector
* Depending on the panel's available auxiliary power.
D133/
D134
Relay
P
S
D2212
S
-
+
D126
Battery
12V 7Ah
16.5 VAC
40 VA
60 HZ
Transformer
D1640
D8004
Transformer
Enclosure