D2212 Installation Manual
Page 13
© 1996 Radionics
74-07361-000-C 11/11/96
Optional Compatible Equipment
You can use UL listed components that do not require evaluation for
electrical compatibility in many applications when installed according
to the manufacturer’s instructions.
Burglary Applications
You can use UL listed burglary alarm sensors that do not require
evaluation for electrical compatibility in burglary applications. In
some cases you must use a UL listed Radionics interface module in
conjunction with the sensors. Consult the individual component
specification and installation documents to determine suitability.
In burglary applications with one 7.0Ah, 12 VDC battery the panel
supports an auxiliary output of 1 A and an alarm (bell) output of
1.85A configured as necessary. For additional loadings refer to the
Current Rating Chart for Standby Battery Calculations.
For commercial burglary installations use a maximum of 45 seconds
of entry delay and a maximum of 60 seconds of exit delay.
Test weekly: UL Standard 1023 requires a weekly test. Configure
the User System Test to test the battery. See
User Configuration in
the
D2212 Program Entry Guide for instructions.
Fire Applications
You can use UL listed fire initiating devices not requiring electrical
compatibility evaluation in any application. For example: four-wire
smoke detectors, heat detectors, waterflow switches, and manual
pull stations are suitable fire initiating devices. Consult the individual
component specification and installation documents to determine
suitability.
When using four-wire smoke detectors, install a suitable power
supervision unit according to the manufacturer’s instructions. Use
the D133 Relay Module to provide reset capability.
In fire applications with one 7.0Ah, 12 VDC battery the panel
supports an auxiliary output of 140mA; it supports a total combined
continuous and alarm current daw during alarm conditions of 1 A.
For additional loadings refer to the
Current Rating Chart for Standby
Battery Calculations.
Two-wire detectors must be electrically compatible, and must be UL
listed for use with the D2212. See the Radionics Technogram
Smoke Detectors Compatible with the D2212 (73-07358-000), or
you may contact the detector manufacturer.
Test weekly: Radionics recommends testing fire and combined fire/
burglary systems weekly. Configure the User System Test to test the
battery. See
User Configuration in the D2212 Program Entry Guide
for instructions.
For all Burglary applications the panel must be programmed to send
a supervisory signal to the central station a minimum of once every
24 hours.
Do not set or program an automatic telephone dialer or similar
device to place a call to a police station number that is not
specifically assigned by that station for such service.
Sounding Device
The sounding device shall operate for at least four minutes before
an automatic cutoff for Household Burglary applications and at least
15 minutes for Commercial Burglary applications.
For all Commercial Burglary applications the system must be
programmed to sound the audible device every time the system is
armed.
Enclosures
The D2203 enclosure is suitable for Household Fire and Burglary
applications only.
Enclosure tamper protection causing an immediate alarm signal is
required for all burglary applications.
Radionics offers three optional enclosures.
The D8103 enclosure is suitable for residential fire and/or burglary
installations and commercial applications. See System Chart for
acceptible applications.
The D8109 is normally used for fire alarm applications. The D8109
is approved by Factory Mutual, California State Fire Marshal, and
the New York City Materials and Equipment Acceptance System.
The D8108A is attack resistant. It is intended primarily for UL
commercial burglary alarm and mercantile safe and vault
applications requiring a local bell. You can use the D8108A in any
burglary application where the D8103 or D8109 enclosure is
suitable. The D8108A is approved by Factory Mutual, California
State Fire Marshal, and the New York City Materials and Equipment
Acceptance System.
The D2212 control panel is suitable for Police Station connect
applications, including Grade A Mercantile Premises and Grade A
Mercantile Safe and Vault alarm systems. Suitable for Grade AA
Mercantile Premises and Grade AA Mercantile Safe and Vault alarm
systems when the Model D2212 DACT unit is installed in
conjunction with the Model D8122 derived channel subscriber
terminal unit. For all Police Station applications and grades, the
Model D8108A Attack Resistant Enclosure with a UL Listed local
sounding device is required. Per UL 365, keyswitches mounted
outside the protected area must employ high security locking
cylinders complying with the requirements for key locks, UL 437.
Tamper protection must also be provided.
The D2212 control panel is suitable for Local, Grade A Mercantile
Premises and Local, Grade A Mercantile Safe and Vault alarm
systems. For all Local applications and grades, the Model D8108A
Attack Resistant Enclosure and a UL Listed local sounding device
are required. Per UL 609, when keyswitches are mounted outside
the protected area, tamper protection must be provided.
The D2212 control panel is suitable for Central Station, Grade C
applications. It is suitable for Central Station, Grade B applications
when the Model D2212 DACT unit is installed with a UL Listed local
sounding device. Also suitable for Central Station Mercantile, Grade
AA applications when installed with the Model D8122 derived
channel subscriber terminal unit.
Installation Guide for UL
Applications
Introduction
The
System Chart references components evaluated and listed by
Underwriters’ Laboratories for compatibility with the panel. These
components meet the basic system requirements for the applicable
standard.
The
System Wiring Diagram, Issue A shows the relationship
between the panel and the accessory components referred to in the
System Chart. See the installation and operation instructions for
each component for detailed instructions.