Standby Battery Requirements
Household Burglary and Commercial Burglary
Four hours of standby battery capacity required.
Standby Battery Calculation for Fire Alarm Applications
NFPA 72 (Ch. 2) Household Fire Warning Equipment
The NFPA 72 (Chapter 2) Household Fire Warning
Equipment Standard requires 24 hours of s 4 min.
(.067 hrs) of alarm operation at the end of the 24 hr. period.
You must use battery ampere hour (Ah) calculations to verify
compliance. The formula below includes a 10% contingency
factor for depletion of battery capacity with age.
NFPA 72 (Ch. 2) Ampere-Hour Calculation Formula
(Total B ___ x 24 Hrs) + (Total C ___ x .067 Hrs) +
(10%
Contingency) = Total Ah required.
Total Ah requirements must not exceed Ah capacity of
batteries.
The D2212 control panel is suitable for Proprietary Burglar Alarm,
Grade C applications. Also suitable for Proprietary Burglar Alarm,
Grade B applications when the Model D2212 DACT unit is installed
with a UL Listed local sounding device. Also suitable for Proprietary
Burglar Alarm, Grade AA when the Model D2212 DACT is installed
with the Model D8122 derived channel subscriber terminal unit.
The D2212 control panel is suitable for Household, Grade A
applications.
UL Standard 681 for Installation and Classification of Mercantile and
Bank Burglary Alarm systems requires foil lining or equivalent
protection of the control unit enclosure. The D8108A enclosure does
not have a foil lining, but acceptable protection can be provided by
mounting listed electronic vibration sensors inside the enclosure.
Proximity alarms (capacitance) cannot be used for this
purpose.
Install electronic vibration sensors in the D8108A enclosure that are
identical to those used to protect the safe or vault. Sentrol 5402,
Potter EVD-S, or Arrowhead S-3810 electronic vibration detection
(EVD) systems which can be mounted inside the enclosure meet the
requirements of UL 681. Mount the electronic vibration sensor
directly inside the metal cabinet of the D8108A. Do NOT install the
sensor within a quarter inch (1/4”) of the components or traces of the
printed circuit assembly.
System Chart
Household Burglar
(Grade A)
Household Fire
Household Fire/
Burglary Combined
Central Station
Burglary (Grade C)
Police Connected
Burglary
Local Burglary
Proprietar
y
Bur
g
lar
y
NFPA Standard
72
72
Min. Hours of Standby
Battery
4
24 +
4 min
alarm
24 +
4 min
alarm
4
4
4
4
D2203 Enclosure
Included with panel
No
No
No
D8103 Enclosure
Optional
*
No
No
No
D8108A Enclosure
Optional
Choose
Req.
Req.
Req.
D8109 Enclosure
Optional
One
No
No
No
D126 Battery
1
1
1
1
1
1
1
D127 Reversing Relay
Opt.
No
Opt.
Opt.
Opt.
Opt.
Opt.
D164 Telephone Cord
Required to connect panel to RJ31X Telco Block
D205, D206 Command
Center
1+
1+
1+
1+
1+
1+
1+
D262 Smoke Detector Head
D261 Base
1•
1•
D431, D435, D438, D440,
D442, D448 Indicating
Device
1+
1+
1+
Opt.
u
u
u
D133, D134 Relays
Opt.
Opt.
Opt.
Opt.
Opt.
Opt.
Opt.
D1640 Transformer
Required for all applications
D8004 Transformer
Enclosure
Opt.
Opt.
Opt.
Opt.
Opt.
Opt.
D8122 Derived Channel
S.T.U.
Opt. Contact TelCo for availability of derived channel service
D8130 Release Module
Optional
The D2212 is not listed for these applications: Local Fire/Burglary Combined, Local Fire, Local and
Central Station Fire Combined, Local and Central Station Fire/Burglary (Grade C), Central Station
Fire/Burglary (Grade C), Central Staion Fire, and Electrically Actuated Transmitter.
Key
No
=
Not acceptable for this
application.
Req
=
Required for this
application.
Opt.
=
Optional for this application.
1+
=
One or more required for
this application. Consult the
appropriate standard.
2+
=
Two or more required for
this application. Consult the
appropriate standard.
1•
=
At least one detector
required. You can substitute
other 2-wire detectors
listed for use with the
D2212. You could use the
D262 with the D270 4-wire
base or other
manufacturer’s 4-wire
detectors. You must use a
listed power supervision
relay with 4-wire detectors.
u
=
Listed bell (siren) housing
required for burglary alarm
bell or siren.
¨
=
(Empty Box) Not used with
this application.
*
=
D101 required for D8103
enclosure.
www.PDF-Zoo.com
firealarmresources.com