Connections
2
Connections control unit
K1:
Power supply
The Sigma 600 may be connected to 1 or to 2 supplies. For greater reliability
we recommend that the Sigma 600 be connected to 2 supplies. Should the 24V
main supply fail, the Sigma 600 will continue to operate on the 24V-back-up
supply. When only 1 supply is used the connections to the main supply should
be looped through to the connection of the back-up supply. When this is not
done the supply voltage LED will light up red, indicating that a power source
is missing.
When the Sigma 600 is connected to 2 active supplies the supply voltage
indicator LED will light up green. Should one of the two supplies fail the
supply voltage indicator LED will light up red.
GND (BACKUP)
GND (MAIN)
+24VDC (MAIN)
+24VDC (BACKUP)